ECHO
3250 NE 188 Street
Master permit #2014023581
Items added to master report in numerical sequence.
7/15/15 Trash chute corridor entry and hopper doors inspected, tested and partially approved except as noted.
130. Adjust side hinged corridor vestibule doors to trash chute to close and latch without manual assistance in accordance with NFPA 101: 7.1.8 and NFPA 80.
A. Units 902, 802, 203, PH05, 708, 407, 408.
131. Adjust trash chute hopper doors and limit door from opening past the designed limit and close and latch without manual assistance in accordance with NFPA 101: 7.1.8 and NFPA 80.
A. Units 1002, 501, 903, 206, 407, 801, 502, 903, 1006, 506, 908, 608, 507, 407, 408, 207.
132. Provide installation of trash chute sprinkler guard at unit 704. NFPA 82, 13.
133. Remove sprinkler shipping guard at trash vestibule 201. NFPA 13.
134. Complete installation of concrete grouting around chute hopper door assemblies in accordance with NFPA 82.
A. Units 901, 402, 1004, 501, 1002, 703, PH07, 1008, Lobby level Core 4.
135. Provide approved fire stop system installation at all fire sprinkler pipe penetration at all Core 1-4 trash entry vestibules in accordance with NFPA 101: 8.3.
136. Remove PVC pipe penetration at trash chute shaft wall and provide approved fire stop system at unit 507.
137. Provide installation of 90-minute fire rated hopper doors at Cores 1-4 wash downs on floor 11 for inspection. NFPA 82, 101.
138. Complete installation of fire rated wall assemblies at the following trash vestibule locations in accordance with NFPA 101: 8.3.
A. 905, PH07, PH08, PH05, PH06.
139. Provide installation of floor threshold at PH06 corridor trash vestibule access door for inspection. NFPA 101.
140. Provide access to trash chute hopper doors for inspection. Doors were locked and not accessible.
A. Units 906, 806, 706, 606, 406, 306, 607, 307, 306, Lobby level at Cores 2 and 4, all Core 5 doors from floor 2-PH.
141. Provide corrections to all trash collection rooms for Cores 1-4 west as indicated in accordance with NFPA 80, 82, 101, 13.
A. Adjust fire rated entry door to close and latch without manual assistance,
B. Provide approved fire stop systems installed at all wall and slab penetrations which include chute cylinder,
C. Provide approved test and inspection of chute guillotine,
142. Remove all wood and elevator interior cab protection that does not comply with ASME A17.1 in accordance with NFPA 13: 8.15.5.5 for non-sprinklered hoistways prior to a TCO approval.
143. Provide approved Life Safety and fire alarm inspections at all Lobby level Lanai units prior to requesting a TCO in accordance with NFPA 1,101.
This is a tentative list. NFPA 1: 1.14.4 Review and approval by the AHJ shall not relieve the applicant of the responsibility of compliance of this Code. Do not occupy without TCO or CO approved by Building and Fire Departments. NFPA 1: 10.3.1.