Fire Rescue

 
 
   
Miami-Dade County miamidade.gov

Print View

Inspection Result Comments

Tuesday, April 23, 2024

Permit Number:  2014023581


Date:

8/1/2016 

Inspector:

Walter  Wray (WRAYWW) 

Type:

209 - FIRE FINAL

Status:

86 - FIRE FINAL APPRVD PENDING FEES


FIRE FINAL APPROVED PENDING PAYMENT OF ALL FEES



Date:

7/25/2016 

Inspector:

Walter  Wray (WRAYWW) 

Type:

209 - FIRE FINAL

Status:

2 - APPROVED PARTIAL


7/25/16 All permits have been finalized except for the master permit.

18. PH3 & PH7 have slide bolt locks on the foyer to laundry exit doors. This is in direct violation of the Condominium Docs. and NFPA 101:7.2.1.5.2. Remove ALL locks from these doors throughout the building. All doors will be checked and a fire final will not be given until all units are in compliance.



Date:

7/18/2016 

Inspector:

Walter  Wray (WRAYWW) 

Type:

209 - FIRE FINAL

Status:

2 - APPROVED PARTIAL


BDA TESTING AND PREVIOUS ITEMS CHECKED OFF FROM MASTER LIST. SEE COMMENTS UNDER MASTRE LIST AND BDA PERMIT #2016-020580



Date:

7/7/2016 

Inspector:

Carla  Crook (CCROOK) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY




Date:

7/7/2016 

Inspector:

Carla  Crook (CCROOK) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY




Date:

7/7/2016 

Inspector:

Carla  Crook (CCROOK) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY




Date:

7/7/2016 

Inspector:

Carla  Crook (CCROOK) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


BDA Acceptance Test passed for MDFR 450mhz.
MDPD still working with system to accommodate 800mhz.
OK to schedule the BDA Equipment Inspection to test BDA.



Date:

6/8/2016 

Inspector:

Carla  Crook (CCROOK) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


BDA Signal Strength Acceptance Testing.
BDA System not ready for inspection.
Please schedule an SRI for Acceptance Testing when system is ready.
CO will not be granted until BDA System passes signal strength testing.



Date:

5/23/2016 

Inspector:

Walter  Wray (WRAYWW) 

Type:

209 - FIRE FINAL

Status:

2 - APPROVED PARTIAL


Items completed from Master List.



Date:

5/16/2016 

Inspector:

Walter  Wray (WRAYWW) 

Type:

209 - FIRE FINAL

Status:

3 - REJECTED NOT TO CODE


Items from Master List completed



Date:

5/2/2016 

Inspector:

Walter  Wray (WRAYWW) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


1. TCO EXT RECOMMENDED FOR ALL PHASES OF THE BLDG W/CAPT S APPROVAL SIGNATURE. TAKE THIS SHEET & AVENTURA S TCO FORM TO FIRE ENGINEERING FOR APPROVAL SIGNATURE.

2. PAY ALL FEES IN FULL




Date:

2/1/2016 

Inspector:

Walter  Wray (WRAYWW) 

Type:

209 - FIRE FINAL

Status:

3 - REJECTED NOT TO CODE


Items checked off from LT Hunt s master list. List will be updated and sent to Pablo.



Date:

1/26/2016 

Inspector:

Walter  Wray (WRAYWW) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


1. TCO EXT RECOMMENDED FOR ALL PHASES OF THE BLDG W/CAPT S APPROVAL SIGNATURE. TAKE THIS SHEET & AVENTURA S TCO FORM TO FIRE ENGINEERING FOR APPROVAL SIGNATURE.

2. PAY ALL FEES IN FULL



Date:

12/28/2015 

Inspector:

Walter  Wray (WRAYWW) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


1. TCO RECOMMENDED FOR LANAI UNITS #107-110. TCO MUST BE SIGNED BY FIRE PREVENTION CAPT FOR TCO APPROVAL.

2. PAY ALL FEES



Date:

12/2/2015 

Inspector:

Walter  Wray (WRAYWW) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


1. TCO RECOMMENDED FOR FL S #9-11 AND PLUNGE POOLS EAST TOWER. LANAIS #101-106 WEST TOWER ALSO RECOMMENDED FOR TCO W/CAPT S APPROVAL SIGNATURE.

2. CORRECT STAIR UNIFORMITY OF THE RISERS FOR PLUNGE POOLS #12 & 13.

3. PAY ALL FEES IN FULL



Date:

11/12/2015 

Inspector:

Walter  Wray (WRAYWW) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


1. TCO is recommended for the FL s 6-8 of the East Tower. Take this form & the TCO form to Fire Engineering for Capt s approval signature.

2. Pay all fees in full.



Date:

10/29/2015 

Inspector:

Walter  Wray (WRAYWW) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


1. A TCO EXT FOR THE WEST BLDG IS RECOMMENDED PENDING THE CAPT S APPROVAL SIGNATURE. THIS EXT WILL ALSO INCLUDE THE PLUNGE POOLS.

2. PAY ALL FEES ON ALL THE SUBSIDIARY PERMITS.



Date:

10/26/2015 

Inspector:

Walter  Wray (WRAYWW) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


INSP WAS FOR A TCO EXT. AND INSP OF THE PLUNGE POOLS. HANDRAILS FOR THE POOLS NEED TO BE BETWEEN 34-38" IN ACCORDANCE W/NFPA 101:7.2.2



Date:

10/14/2015 

Inspector:

Walter  Wray (WRAYWW) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


TCO ITEMS FOR FLOORS 2-5 IN THE EAST TOWER WERE ADDRESSED. ITEMS #5-7 FROM LIST DATED 10/12/15 COMPLETED.



Date:

10/13/2015 

Inspector:

Kelvin Thompson (KET) 

Type:

211 - PRELIMINARY

Status:

2 - APPROVED PARTIAL


1. Elevator recall approved for elevator #14, okay


10/12/15 Smoke control testing was witnessed by LT Wray & LT Thompson today.

1. In order for a TCO to be obtained, please comply with LT Hunt?s original comments from the preliminary which states, ?All construction shall be completed and debris removed from premises for CO or TCO inspection.?
2. All doors and door hardware must be installed, whether fire-rated or not. All fire-rated doors will need to shut & latch and have fire-rated labels free of any tape. NFPA 101:8.3.3.3.
3. Unit #312 rear door has a >1/2? change in elevation.
4. Unit #213 had a sprinkler head that activated.
5. Provide proof of EM lighting checked & approved on the East tower.
6. Provide proof of re-entry being checked & approved on the East tower.
7. Provide proof of PRV testing on the East tower.



Date:

10/2/2015 

Inspector:

Alain Iglesias (IGGY) 

Type:

208 - FIRE TCO INSPECTION

Status:

2 - APPROVED PARTIAL


2014023581

FIRE TCO ISNPECTION: PARTIAL APPROVAL

ITEMS COMPLETED:

INSPECTED ALL ITEMS FROM PUNCH LIST DATED 08/23/2015 BY LT. THOMPSON AND OK.

INSPECTED ALL ITEMS FROM PUNCH LIST DATED 9/3/2015 FROM LT. WRAY S EMAIL SENT DIRECTLY TO PABLO AND OK.

4 HR. SRI.

lT. IGLESIAS



Date:

10/1/2015 

Inspector:

Alain Iglesias (IGGY) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


2014023581

TCO INSPECTION FOR ECHO

TODAY INSPECTED ALL FIRE RATED DOORS FROM FLOORS 11 - 8 EAST WING AND OK.

LT. IGLESIAS

4 HR. SRI



Date:

9/30/2015 

Inspector:

Dianne Gary (DGARY) 

Type:

208 - FIRE TCO INSPECTION

Status:

2 - APPROVED PARTIAL


Permit number: 2014023581

Echo Aventura

NFPA 1:1.14.4 Review and approval by the AHJ shall not relieve the applicant of the responsibility of compliance with this code.

1. Fire TCO partial approval.

Inspected all fire rated doors from the seventh floor down to the first floor.

Doors checked okay for fire lables and closers funtion as they should.

SRI fee applies





Date:

9/28/2015 

Inspector:

Walter  Wray (WRAYWW) 

Type:

209 - FIRE FINAL

Status:

3 - REJECTED NOT TO CODE


Phase 2 for elevator recall tested & ok for elevators #9-12. This was pending frm LT McCook s list dated 8-24-15



Date:

9/25/2015 

Inspector:

Nassoma Morgan (NMORGAN) 

Type:

208 - FIRE TCO INSPECTION

Status:

2 - APPROVED PARTIAL


LT. MORGAN 2014023581 SRI
1. TRASH CHUTE CHASE DOOR INSPECTIONS FOR EAST TOWER.
2. ALL FLOORS OKAY EXCEPT FOR 2ND FLOOR CORE 9 BY UNIT 18.
3. PROVIDE SPRINKLER COVERAGE IN TRASH CHUTE AT THE LOWEST SERVICE LEVEL IN ACCORDANCE WITH NFPA 82:5.2.6.1.4. THE LOBBY IN THIS CORE DOES NOT CONTAIN A SERVICABLE TRASH CHUTE LEVEL; THEREFORE, SPRINKLER COVERAGE IS REQUIRED AT THE SECOND FLOOR LEVEL.
4. PROVIDE AN APPROVED SPRINKLER FINAL INSPECTION FOR TRASH CHUTES.
5. REVISE PLANS ON SPRINKLERS TO REFLECT ALL CHANGES AND HAVE APPROVED BY MDFR PER NFPA 1:1.14



Date:

9/24/2015 

Inspector:

Alain Iglesias (IGGY) 

Type:

208 - FIRE TCO INSPECTION

Status:

2 - APPROVED PARTIAL


2014023581

SPRINKLER FINAL: PARTIAL APPROVAL

SPRINKLER FINAL FOR WAST SIDE UNITS FROM FLOORS 11 TO 2 AND OK EXCEPT FOR ALL "09" 4 ROOMS CORNER UNITS MASTER BATHROOM WHICH EXCEED PROPER SPRINKLER COVERAGE.

4 HR. SRI CHARGED TO MASTER PERMIT.

COMMETNS ALSO ADDED TO SPRINKLER PERMIT.

LT. IGLESIAS



Date:

9/21/2015 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

34 - INSPECTION CANCELLATION


INSPECTION CANCELED PER PABLO

ADVISED PABLO OF RE-INSPECTION FEES

C.B.WOLFF -- 09/21/15



Date:

9/21/2015 

Inspector:

Nassoma Morgan (NMORGAN) 

Type:

208 - FIRE TCO INSPECTION

Status:

34 - INSPECTION CANCELLATION




Date:

9/14/2015 

Inspector:

Walter  Wray (WRAYWW) 

Type:

209 - FIRE FINAL

Status:

3 - REJECTED NOT TO CODE


items frm master list completed



Date:

9/11/2015 

Inspector:

Alain Iglesias (IGGY) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


2014023581

FIRE ALARM FINAL: PARTIAL APPROVAL

INSPECTED FIRE DAMPERS TO STARIWAYS 13 & 15 (EAST TOWER) AND ALL ELEVATOR VEISTIBULES TO ALL UNITS BEING SERVED BY STAIRWAY 13 & 15 (EAST TOWERS) AND OK.

4 HR. SRI

LT. IGLESIAS



Date:

9/2/2015 

Inspector:

Walter  Wray (WRAYWW) 

Type:

209 - FIRE FINAL

Status:

3 - REJECTED NOT TO CODE


9/2/15 Dampers tested & ok in Stair #11



Date:

9/1/2015 

Inspector:

Walter  Wray (WRAYWW) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


COMMENTS TO BE E-MAILED TO PABLO



Date:

8/26/2015 

Inspector:

Rasheelah Brown (RBROWN) 

Type:

208 - FIRE TCO INSPECTION

Status:

1 - APPROVED


TCO APPROVED FOR 90 DAYS LT MCCOOK / FALCO



Date:

8/24/2015 

Inspector:

Michele McCook (MMW) 

Type:

208 - FIRE TCO INSPECTION

Status:

2 - APPROVED PARTIAL


insp 8-21-15 mmw
ECHO
TCO INSPECTION CONTINUE - EAST TOWER
ITEMS COMPLETED:
1. ALL PENDING ITEMS, LT WRAY S LIST 8-17-15 CHECKED OK EXCEPT:
- ITEMS #6 HANDICAPP ELEVATOR FOR POOL DECK NOT READY. SPRINKLER NOT INSTALLED.
2. ALL ITEMS LIST 8-18-15 CHECKED OK.
3. ALL UNIT GUARD RAILS CHECKED 1 THROUGH 11 FLOORS EXCEPT:
- GLASS MISSING FROM THE FOLLOWING UNITS: NORTHEAST BALCONY 218, 318 AND 718
- GLASS MISSING FROM: SOUTHEAST UNITS: 418 AND 518.
4. TCO FOR EAST POOL DECK COMPLETE THE FOLLOWING:
- COMPLETE INSTALLATION OF OF ARTIFICIAL TURF,
- ADJUST ALL POOL GATES TO CLOSE AND LATCH
5. FOR YOGA ROOM, BARN DOOR INSTALLED - PROVIDE ALTERNATE MEANS OF EGRESS.
REVISE PLANS FOR FINAL TO SHOW BAR DOOR INSTALLED.
6. PAY ALL FEES.



Date:

8/23/2015 

Inspector:

Kelvin Thompson (KET) 

Type:

209 - FIRE FINAL

Status:

2 - APPROVED PARTIAL


1. Fire final partial inspection.
2. Inspected all east wing units balconies on floors: 11, 10,9,8, and 6
okay except Item #3 of this list.
3. unit 1118 missing glass on NE balcony, unit 918 missing glass on NE balcony
unit 818 missing glass on the NE and west balconies, unit 618 missing glass
on NE balcony, and unit 617 the gap between the balcony last post and
wall exceeds 4".
4. The following stairs are missing exit tactile signage:
stair #11 11th floor
stair #13 11th floor
stair #19 11th floor
stair #17 10th floor
stair #15 10th floor
Stair #13 9th floor
Stair #15 9th floor
Stair #17 9th floor
stair #17 8th floor
stair infront of units 815
stair infront of units 814
stair infront of unit 812
stair #11 8th floor
stair #13 6th floor
stair infront of unit 614
stair #17 6th floor
stair #19 6th floor.





Date:

8/19/2015 

Inspector:

Walter  Wray (WRAYWW) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


8/18/15 Stairwell signage and EM lighting checked & ok floors #1-8 except for the following items listed:

1. Add EXIT sign at the entrance to Garage Stair 8 at the west end of the Lanai. NFPA 101:7.10
2. Unit #715 ? combo light INOP
3. Stair 10 Level 1 ? EM light INOP & EXIT sign missing
4. Stair 16 Level 1 ? EM light INOP
5. Stair 12 Level 1 - EM light INOP
6. Stair 11 Level 1 ? EXIT sign INOP



Date:

8/17/2015 

Inspector:

Walter  Wray (WRAYWW) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


EAST SIDE LOBBY AREA AND POOL DECK NOT READY FOR TCO



Date:

7/30/2015 

Inspector:

Michele McCook (MMW) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


7-29-15 mmw
ECHO TCO REINSPECTION

TCO FOLLOW UP INSPECTION COMPLETED. FIRE CAPTAIN S SIGNATURE REQUIRED FOR FINAL TCO APPROVAL. TCO INSPECTION PROVIDED.

TCO EXCLUDES THE FOLLOWING AREAS: EAST PARK AND EAST ARRIVAL DECK,
EAST EDN OF PARKING GARAGE (EAST TOWER), RECEIVING OFFICE, VALET OFFICE, BUILDING STORAGE. EAST ARRIVAL DECK RAMP, POOL DECK, LANAI UNITS 1-10, PH LEVELS ON WEST BUILDING, ENTIRE EAST BUILDING, WEST PLUNGE POOL AREAS (MAIN ROOF). REFER TO OVERALL SITE PLAN PAGES A0.3 THROUGH AO.8 INCLUDED IN TCO DOCS SUBMITTED BY ECHO REPS.

1. EAST LOBBY CANOPY MAJOR CONSTRUCTION COMPLETED. STILL PENDING COSMETIC VENEERS.

2. CONSTRUCTION OF ACCESS DRIVE TO ARRIVAL DEC COMPLETED.



Date:

7/29/2015 

Inspector:

Michele McCook (MMW) 

Type:

211 - PRELIMINARY

Status:

2 - APPROVED PARTIAL


7-29-15 MMW
TCO INSPECTION COMPLETED. TCO CONTINGENT ON COMPLETION OF WEST SIDE DRIVEWAY PAVING AND CANOPY, WEST SIDE LOBBY. FIRE CAPTAINS SIGNATURE REQUIRED FOR FINAL TCO APPROVAL.

PROVIDE HOLD HARMLESS LETTER, NOTARIZED AND TCC/TCO FORM FROM CITY BUILDING DEPARTMENT FOR CAPTAIN S SIGNATURE. DO NOT OCCUPY WITHOUT FINAL APPROVAL.



Date:

7/29/2015 

Inspector:

Michele McCook (MMW) 

Type:

211 - PRELIMINARY

Status:

2 - APPROVED PARTIAL


7-28-15 mmw
ECHO TCO INSPECTION CONTINUE

THE FOLLOWING PENDING ITEMS FOR TCO FROM LT. HUNTS LIST VARIFIED

ITEM #6 - COMPLETE. UNIT 205 TEMPORAY BALCONY INSTALL
#23 - WEST BUILDING COMPLETE
#33 - COMPLETE EXCEPT PLANS REVISION
#37 - COMPLETED, REPORTS COLLECTED BY LT. HUNT, SPRINKLER INSTALLED IN
CONDUIT ROOM. REVISION PENDING TO SHOW CHANGE IN RATED WALL.
ABOVE/UNDERGROUND CERTS COLLECTED BY LT. HUNT PER PABLO.
#47 - COMPLETE
#52 - COMPLETE
#64 - COLLECTED BY LT. HUNT
#107- PENDING
#125 - 5/8 DRYWALL INSTALLED OVER WALL.
#140 - WEST BUILDING COMPLETED A AND B. EAST BUILDING STILL PENDING.
#142 - WEST BUILDING COMPLETED. EAST BUILDING STILL PENDING.
#158 - WEST BUILDING COMPLETED EAST BUILDING STILL PENDING.
#159 - COMPLETED.
#160 - TEMPORARY SIGNAGE INSTALLED FOR TCO
#168 - COMPLETED
#173 - COMPLETED
#176 - THUMB TURN AND DEAD BOLT REMOVED. PENDING FACE PLATE FOR FINAL
#180 - PENDING EAST GARAGE NEXT TO MAIN TRASH ROOM
#182 - BARRIES INSTALLED THROUGHOUT.
#185 - RE-ENTRY SIGNAGE INSTALLED WEST TOWER. EAST TOWER STILL PENDING.
#186 - COMPLETED WEST TOWER. EAST TOWER STILL PENDING.
#189 - PENDING
#194 - PENDING
#197 - TEMPORARY SIGNAGE INSTALLED
#200 - SIGNS INSTALLED WEST TOWER. EAST TOWER STILL PENDING.
#203 - STIL PENDING
#207 - COMPLETED
#209 - COMPLETED
#210 - WEST TOWER COMPLETED. EAST TOWER STILL PENDING FROM 3RD FLOOR AND ABOVE
#211 - COMPLETED

LT DEALFARAZ S LIST 7/24/15

#7 - BRICK PAVES STILL PENDIG
#8, 10, STILL PENDING.

#13 - COMPLETED

#19 - WEST TOWER COMPLETED. EAST TOWER STIL PENDING.


#19 - COMPLETED



Date:

7/27/2015 

Inspector:

Stephen Hunt (HU1507) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


Echo Aventura 7/27/15

TCO inspections continued and disapproved pending all life safety systems and completion of construction. See detailed reports in Apps 8 for comments.

SRI fees applied.

Lt. Hunt



Date:

7/25/2015 

Inspector:

Stephen Hunt (HU1507) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


Echo Aventura 7/25/15

TCO inspections continued and disapproved pending all life safety systems and completion of construction. See detailed reports in Apps 8 for comments.

SRI fees applied.

Lt. Hunt



Date:

7/25/2015 

Inspector:

Michele McCook (MMW) 

Type:

211 - PRELIMINARY

Status:

2 - APPROVED PARTIAL


7-25-15 mmw
ECHO
TCO INSPECTION CONTINUE. LT. HUNTS LIST - REINSPECTION

1.#112 - ALL ITEMS COMPLETED EXCEPT AS NOTED.
WEST EMERGENCY BACK UP LIGHTING CHECKED OK ELEVATOR MACHINE ROOMS, BOILER AND ELECTRIC ROOMS, PARKING GARAGE TRASH ROOMS, WEST ROOF, EAST AND WEST SECURITY/COMMUNICATIONS ROOMS. NORAL LIGHT OK.

EXCEPT: EAST GARAGE AREA STILL PENDING

2.#113 ? ITEMS A, B, C, D, E, CHECKED OK, NORMAL LIGHTING OK EXCEPT:

(A) REPLACE EMERGENCY LIGHT UNIT 803 BY STAIR #4.
(B) BLANK OUT CHEVRON/ARROW UNIT 207 BY STAIR #7.

3.#141 ? EXIT SIGNS RELOCATED, WEST SIDE ? GRAND LOBBY.

NO OTHER ITEMS CHECKED.







Date:

7/24/2015 

Inspector:

Jose De Alfaraz (JOSEED) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


7/24/15
Echo
West Tower

1. Life safety inspection continued:

2. The remaining smoke alarms for units 306,307,608,1005 were tested and completed.

3. The remaining fire doors that needed to be verified for units 907,1004,1002,1107 were verified and completed.

4. The nine stairwells in the west tower were inspected today from the roof to the ground floors and parking garage for the west tower only. All stair treads, rise, stair identification signage within the stair enclosure, guardrails and handrails were inspected. The below items are the discrepancies found.

5. Garage stair 7 missing handrails for the steps at the exit discharge.

6. Provide the missing bollards to protect the sprinkler riser/standpipe from vehicular damage at stair 1 garage floor.

7. Stairwell 1 ground floor, complete the brick pavers installation at the exit discharge.

8. Stairwell 2 level 9 adjust the fire rated door.

9. Stairwell 3, 11th floor repair the wire mesh for the stair pressurization opening.

10. Stairwell 6, 11th floor need to adjust the handrail to be within 34-38 inches. NFPA 101.7.2.2.4.4

11. Stairwell 6, ground floor provide the missing Exit tactile signage.

12. Stairwell 7, 11th floor the end of the handrail needs to return to itself, the wall, or ground as per NFPA 101.

13. Stairwell 7, ground floor need to seal the penetration on the wall with fire caulking.

14. Stairwell 8, ground floor need to provide the missing Exit tactile signage

15. Stairwell 9, ground floor provide the missing handrails for the bottom steps.

16. Stairwell 9, ground floor provide the missing Exit tactile signage.

17. Stairwell 9, ground floor the pendant sprinker head cannot be greater than 12 inches from the ceiling. Per NFPA 13. Currently its approximately 24 inches from ceiling.

18. Remove all debris and clean stairwells to prevent tripping hazards. NFPA 101.7.2.2.3.3

19. Need to provide the missing Exit Tactile signs leading to the stairwells from the apartment units. As per NFPA 101.7.10.1.3

20. Nothing else was verified. Out of time.



Date:

7/24/2015 

Inspector:

Stephen Hunt (HU1507) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


Echo Aventura 7/24/15

TCO inspections continued and disapproved pending all life safety systems and completion of construction. See detailed reports for comments.

SRI fees applied.

Lt. Hunt


INSP 7-23-15 MMW
ECHO
TCO INSPECTION CONTINUE

REINSPECTION - ITEMS COMPLETED

1. LT HUNT S LIST ITEMS 17, 18, 37, 39, 42, 90, 91, 921, 112, 114, 115,116, 118 AND 119.

ITEMS PENDING:
2. ITEM 111 ALL EMERGENCY/EXIT LIGHTS IN STAIRWELLS CHECKED OK EXCEPT ITEMS LISTED BELOW:
3. ADJUST EMERGENCY LIGHTS IN STAIR #3, FLOOR 11 AND LOBBY LEVEL.
5. STAIR #5 ADJUST EM LIGHT ON LOBBY LEVEL
6. STAIR #9 ADUST EM LIGHT ON FLOOR 11 AND ROOF.

NOTE: UNIT GUARDRAILS CHECKED OK.

HAND/GUARDRAILS STILL FOR STAIR WELLS.



Date:

7/24/2015 

Inspector:

Stephen Hunt (HU1507) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


Echo Aventura 7/23/15

TCO inspections continued and disapproved pending all life safety systems and completion of construction. See detailed reports for comments.

SRI fees applied.

Lt. Hunt



Date:

7/22/2015 

Inspector:

Stephen Hunt (HU1507) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


Echo Aventura 7/22/15

Smoke control acceptance testing completed and approved for West Tower only. Firefighter override functions completed for Cores 3 and 4. All testing performed on emergency power. Sequence of Ops change on smoke control panel shall be changed. All elevator acceptance testing for West Tower completed and approved.

SRI fees applied.

Lt. Hunt



Date:

7/21/2015 

Inspector:

Stephen Hunt (HU1507) 

Type:

211 - PRELIMINARY

Status:

2 - APPROVED PARTIAL


Echo Aventura 7/21/15

Smoke control acceptance testing completed and partially approved for West Tower only pending smoke control panel acceptance testing for controls and Firefighter override functions for Cores 3 and 4 only.

SRI and Smoke control test fees applied.

Lt. Hunt



Date:

7/21/2015 

Inspector:

Michele McCook (MMW) 

Type:

211 - PRELIMINARY

Status:

2 - APPROVED PARTIAL


7-21-15 mmw
Echo - Life Safety
REINSPECTION -ITEMS COMPLETED:

1. LT HUNT S LIST ITEMS # 6, 9,12, 23, 23, 29, 34, 43 AND 50 ALL CHECKED OK.
2. LT McCOOK LIST 7-7-15 ALL HAND/GUARD RAILS CHECKED OK EXCEPT AS NOTED.
3. ALL FIRE EXTINQUISHER CABINETS CHECKED OK.
4. ALL DOOR SIGNAGES CHECKED OK EXCEPT AS NOTED.

ITEMS PENDING:
#28 ROOF ACCESS DOOR SIGNAGE MISSING
#46 ELECTRIC ROOM/SWITCH GEAR ROOM SIGNAGE NOT INSTALLED
#13 FUEL TANK SIGN NOT INSTALLED

HAND/GUARD RAILS

UNIT 205 - UPPER RAIL NOT INSTALLED.
UNIT 407 AND 607 GAP BETWEEN WALL AND RAIL GREATER THAT 4 INCHES.


insp 7-20-15 mmw
Echo - life safety

ITEMS COMPLETED LT. WRAY S LIST 7-9-15
1. ITEMS 4 THROUGH 13 CHECKED OK. DOORS ADJUSTED TO CLOSE AND LATCH.
2. LIST 7-11-15 - ITEMS 1 THROUGH 3 CHECKED OK. ALL DOORS CLOSE AND LATCH
3. UNIT 1107 - ALL DOORS CHECKED OK.
4. EGRESS DOORS FLOORS 6 THROUGH 7 CHECKED OK, DOORS CLOSE AND LATCH.

ITEMS COMPLETED, LT HUNT S LIST 7-17-15
5. ITEM # 143 - ALL VESTIBULE DOORS CLOSE AND LATCH

ITEMS PENDING:
6. UNIT 301, DOOR BY STAIR 1 - CORRECT ELEVATION CHANGES GREATER THAN 1/2 INCH.



Date:

7/19/2015 

Inspector:

Stephen Hunt (HU1507) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


Echo Aventura
7/20/15 Life Safety inspections continued for TCO. A trash chute hopper doors and trash room guillotines inspected, tested and approved.

141. Relocate exit signs installed on interior to exterior side of West and Grand Lobby doors in accordance with NFPA 101: 7.10 and the LS drawings. The egress of these doors is from the Terraces to the Lobbies.
142. Complete installation of fire rated wall assemblies at the following trash vestibule locations in accordance with NFPA 101: 8.3. PH 03, 1107.
143. Adjust side hinged corridor vestibule doors to trash chute to close and latch without manual assistance in accordance with NFPA 101: 7.1.8 and NFPA 80.
A. Units PH 01, PH 04, 1008, 1006, 1005, 1004, 1002 also tighten loose threshold, 901, 903, 808, 806, 703, 705, 706, 707, 601, 501, 503, 507, 406, 404, 403, 405, 301, 303, 305, 306, 308, 202, 206, 204, 203.
143. Replace painted sprinkler head at corridor by trash room access in unit 903 in accordance with NFPA 13: 6.2.6.2.
144. Provide Fire service phase 1 operation at Lobby level when elevator has recalled to alternate floor level in accordance with NFPA 101: 9 and ASME A17.1.

This is a tentative list. NFPA 1: 1.14.4 Review and approval by the AHJ shall not relieve the applicant of the responsibility of compliance of this Code. Do not occupy without TCO or CO approved by Building and Fire Departments. NFPA 1: 10.3.1.

Lt. M. McCook and Stephen Hunt, Lieutenant
(786)331-4882
Miami-Dade Fire Rescue Department
www.miamidade.gov
"Delivering Excellence Every Day"



Date:

7/17/2015 

Inspector:

Stephen Hunt (HU1507) 

Type:

209 - FIRE FINAL

Status:

2 - APPROVED PARTIAL


7/17/15 All building elevators in East and West Towers inspected, tested and approved with the Elevator Inspector for standby power operation and security system Fire Service override only. Fire Service recall testing approved by Lt. McCook on previous inspections. Plywood installed elevator cars shall be removed and replaced with can interior finishes that comply with ASME A17.1. The plywood would be permitted to remain only if the elevators hositways are provide with sprinkler protection and shunt trip activation at the top of the hoistways in accordance with NFPA 101: 101, 13, 72 and ASME A17.1

1. Provide fire service elevator recall upon activation of elevator hoistway detectors in accordance with NFPA 72: 6.16.3.4. The fire hat shall flash when detector in hoistway is activated. 101: 9.4.3.1.
2. Where living units are to be used by the General Contractor and Building Owner as business offices, fire alarm visual occupant notification should be provided in any common (non-private) areas used as gathering areas and at the restrooms that are accessible to office staff and public in accordance with NFPA 101: 9.6.3.5.

Lt. Hunt



Date:

7/15/2015 

Inspector:

Stephen Hunt (HU1507) 

Type:

209 - FIRE FINAL

Status:

3 - REJECTED NOT TO CODE


ECHO
3250 NE 188 Street
Master permit #2014023581

Items added to master report in numerical sequence.

7/15/15 Trash chute corridor entry and hopper doors inspected, tested and partially approved except as noted.

130. Adjust side hinged corridor vestibule doors to trash chute to close and latch without manual assistance in accordance with NFPA 101: 7.1.8 and NFPA 80.
A. Units 902, 802, 203, PH05, 708, 407, 408.
131. Adjust trash chute hopper doors and limit door from opening past the designed limit and close and latch without manual assistance in accordance with NFPA 101: 7.1.8 and NFPA 80.
A. Units 1002, 501, 903, 206, 407, 801, 502, 903, 1006, 506, 908, 608, 507, 407, 408, 207.
132. Provide installation of trash chute sprinkler guard at unit 704. NFPA 82, 13.
133. Remove sprinkler shipping guard at trash vestibule 201. NFPA 13.
134. Complete installation of concrete grouting around chute hopper door assemblies in accordance with NFPA 82.
A. Units 901, 402, 1004, 501, 1002, 703, PH07, 1008, Lobby level Core 4.
135. Provide approved fire stop system installation at all fire sprinkler pipe penetration at all Core 1-4 trash entry vestibules in accordance with NFPA 101: 8.3.
136. Remove PVC pipe penetration at trash chute shaft wall and provide approved fire stop system at unit 507.
137. Provide installation of 90-minute fire rated hopper doors at Cores 1-4 wash downs on floor 11 for inspection. NFPA 82, 101.
138. Complete installation of fire rated wall assemblies at the following trash vestibule locations in accordance with NFPA 101: 8.3.
A. 905, PH07, PH08, PH05, PH06.
139. Provide installation of floor threshold at PH06 corridor trash vestibule access door for inspection. NFPA 101.
140. Provide access to trash chute hopper doors for inspection. Doors were locked and not accessible.
A. Units 906, 806, 706, 606, 406, 306, 607, 307, 306, Lobby level at Cores 2 and 4, all Core 5 doors from floor 2-PH.
141. Provide corrections to all trash collection rooms for Cores 1-4 west as indicated in accordance with NFPA 80, 82, 101, 13.
A. Adjust fire rated entry door to close and latch without manual assistance,
B. Provide approved fire stop systems installed at all wall and slab penetrations which include chute cylinder,
C. Provide approved test and inspection of chute guillotine,
142. Remove all wood and elevator interior cab protection that does not comply with ASME A17.1 in accordance with NFPA 13: 8.15.5.5 for non-sprinklered hoistways prior to a TCO approval.
143. Provide approved Life Safety and fire alarm inspections at all Lobby level Lanai units prior to requesting a TCO in accordance with NFPA 1,101.



This is a tentative list. NFPA 1: 1.14.4 Review and approval by the AHJ shall not relieve the applicant of the responsibility of compliance of this Code. Do not occupy without TCO or CO approved by Building and Fire Departments. NFPA 1: 10.3.1.


Lt. M. McCook and Stephen Hunt, Lieutenant
(786)331-4882
Miami-Dade Fire Rescue Department
www.miamidade.gov
"Delivering Excellence Every Day"



Date:

7/14/2015 

Inspector:

Stephen Hunt (HU1507) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


Echo Aventura 7/14/15

Inspected, tested and partially approved all unit system smoke detectors at Lanai units at Lobby level. One detector in each unit. The equivalency letters require full detection and SLS to obtain approval from Captain Tola to allow for 1 system detector only in each unit. SLS letter to be provided to determine location of detector in unit 01 which is not by the main entry.

Additional Life Safety issues and concerns were discussed in addition to relocated GC Staff and Owner Staff to the East Tower. Lt. Hick s to be consulted on this issue.

Do not occupy any parts of the building without TCO or permission from MDFR and Bldg. Official. NFPA 1.

SRI fee applied.

Lt. Hunt


7-13-15 MMW
ECHO
FIRE ALARM
1. DUCT DETECTORS TESTED OK EAST LOBBY MECHANICAL ROOMS.
ITEMS PENDING:
2. REVISE PLANS TO SHOW ALL ADDED DUCT DETECTORS FOR FINAL. NFPA 1
3. SMOKE DETECTORS IN LANAIS SITLL NEEDS TESTING. REPROGRAMME TO REPORT SUPERVISORY SIGNALS PER APPROVED PLANS..

CO LIFE SAFETY INSPCTION
1. WEST STAIRS 3, 5 AND 7 EXIT/EMERGENCY LIGHTS CHECKED OK.
ITEM #16 LT HUNTS LIST OK.
2. EMERGENCY LIGHTS CHECKED OK EAS AND WEST ARRIVAL DECK AND SOUTH DECK.
3. ALL ITEMS LT HUNT S LIST 115 THROUGH 119 CHECKE OK.
ITEMS PENDING;
4. POOL DECK STILL NEED CHECKING
5. GARAGE STAIR #3 EM/EXIT LIGHTS NOT READY.
PAY ALL FEES.


7-11-15 mmw
Echo SRI FEE APPLIED TO SPRK PERMIT #2014059828
PRV TESTING APPROVED STAIRS 1, ROOF AND FLOORS 10, 8, 6, 4, 2 BASEMENT AND SUB BASEMENT.

STAIRS #2 FLOORS 11, 9, 7, AND 5

NOTE: 2 APPLIANCES WERE INITIALLY BEING USED FOR PRV TESTING WITH 2 SPRK CREWS, ONE ASSIGNED TO EACH LTS. VALVES TESTING WAS BEING ALTERNATED BETWEEN LT IGLESIAS AND LT. MCCOOK. THE APPLIANCE I WAS ASSIGNED FAILED. COMPLETED 4 HOURS INSPECTION.


7-11-15 MMW
ECHO LIFE SAFETY INSPECTION

ALL DOORS TESTED OK FOR CLOSING AND LATCHING FLOORS 11, 10 AND 9 EXCEPT ITEMS LISTED BELOW.
1. UNIT 907 HALLWAY DOOR TO CORRIDOR
UNIT 1004 HALLWAY DOOR
UNIT 1002 HALLWAY DOOR
2. UNIT 1107 ALL DOORS STILL NEED TESTING
3. TRASH CHUTE ROOM DOORS STILL NEED TESTING
PAY ALL FEES.




Date:

7/13/2015 

Inspector:

Alain Iglesias (IGGY) 

Type:

208 - FIRE TCO INSPECTION

Status:

2 - APPROVED PARTIAL


2014023581

TCO INSPECTION CONTINUES: PARTIAL APPROVAL

PERFORMED TESTING OF ALL PRESSURE RELEIF VALVES FOR ALL FLOORS IN STAIRS 1 THROUGH 9 (WEST BUILDING) AND OK

9 HOUR SRI

LT. IGLESIAS



Date:

7/11/2015 

Inspector:

Michele McCook (MMW) 

Type:

211 - PRELIMINARY

Status:

2 - APPROVED PARTIAL


7-10-15 mmw
Echo
Final fire co not approved.
1. Inspection for 5, 6, 7 floors trash chutes. Doors not latching.
2. Reinspection.



Date:

7/10/2015 

Inspector:

Michele McCook (MMW) 

Type:

211 - PRELIMINARY

Status:

2 - APPROVED PARTIAL


Insp completed 7-8-15 mmw
Echo - unit smoke alarms testing
Single station smoke alarms tested ok 11th through 6th floors EXCEPT as noted below:
1. Unit 608, bedroom next to stair #9 - Smoke alarms not interconnected
unit 1005 - east bedroom



Date:

7/10/2015 

Inspector:

Walter  Wray (WRAYWW) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


7/9/15 Fire-rated doors were checked for latching and labels on floors #2-8. All were in compliance except for the following:

1. All Trash Room doors will need to be re-checked for latching. NFPA 101:8.3.3.3
2. Need to confirm if the Electrical Room doors need to be 90 min. fire-rated doors in a 2-hour fire-rated wall. 45-min. doors were installed.
3. Need to confirm if the rear corridor doors leading from the units to the rear corridors also need to be 90 min. fire-rated doors in a 2-hour fire-rated wall.
4. All the re-entry doors on floors #3 & 7 need to be tested for latching and labels. Many of those doors missing hinges as well.
5. Stair #4 Level 8 door not latching.
6. #808 ? Double entry door not latching
7. #501 ? Laundry room door not latching
8. #406 ? Rear corridor & Laundry room doors not latching
9. #408 ? rear corridor door not latching
10. #306 ? Laundry & Lobby doors not latching
11. #201 ? Lobby door not latching
12. #203 ? rear corridor door missing hinge
13. #208 ? rear corridor door not latching



Date:

7/10/2015 

Inspector:

Alain Iglesias (IGGY) 

Type:

208 - FIRE TCO INSPECTION

Status:

2 - APPROVED PARTIAL


2014023581

FIRE ALARM FINAL FOR FIRST FLOOR LOBBY AREA: PARTIAL APPROVAL

COMMENTS ADDED TO FIRE ALARM PERMIT 2015022428

5 HR. SRI

LT. IGLESIAS



Date:

7/8/2015 

Inspector:

Michele McCook (MMW) 

Type:

209 - FIRE FINAL

Status:

2 - APPROVED PARTIAL


insp 7-7-15 mmw
Echo
Life safety items continue:

Smoke testing completed SPF 5 through 9 (roof) tested ok with smoke.

All phone jacks 11th through garage tested ok EXCEPT as noted below:

1. Unit 605 - Restest phone jack, elevator lobby. Not working
2. Garage elevator foyer 1 - Still needs testing. No access.

3. Pay all fees.



Date:

7/7/2015 

Inspector:

Alain Iglesias (IGGY) 

Type:

208 - FIRE TCO INSPECTION

Status:

2 - APPROVED PARTIAL


2014023581

TCO INSPECTION: PARTIAL APPROVAL

TESTED DUCT DETECTORS FOR UNITS AHU 1, 2-3, & 4 and ok
TESTED DUCT DETECTORS FOR SPF 1 - SPF 4 AND OK

PENDING SPF 5 - SPF 9

4 HR. SRI

LT. IGLESIAS


7-6-15 mmw
Echo Life Safety

Life safety inspections continue:
All unit signage, fire extinquishers, unit guardrail checked ok, floors 11 through 2nd floor EXCEPT as noted below:

1. Fire extinquishers
missing certification tags - units 207, 208, PH08,707

Cabinet boxes missing glass or handles ? units 606, 701, 901
2.Guard Rails . North side - gaps between wall and railings greater that 4 inches - units 205, 207, 208,307, 407, 607, 806, 807, 808, 907, 608, 901, 904, 1002,
3.Unit Signage - #1108 installed at 10th floor next to 1008.
4.Pay all fees.







Date:

6/30/2015 

Inspector:

Stephen Hunt (HU1507) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


Echo Aventura 2014023581 6/30/15

Emergency lighting inspected, tested and partially approved for emergency battery back-up fixtures only at West tower roof-floor 2 including exit stairs. See master report for detailed deficiencies.


SRI fee applied.

Lt. Hunt


Inspected 6-26-15 mw
Echo
Fire smoke dampers teste dok floors 6 through 11.

Firefigther ops tested ok elevator core 2, 6-25-15

Pay all fees.



Date:

6/29/2015 

Inspector:

Stephen Hunt (HU1507) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


Echo Aventura 2014023581 6/29/15

Emergency lighting inspected, tested and partially approved for West tower roof-garage including east garage. Lobby and East tower excluded. See master report for detailed deficiencies.


SRI fee applied.

Lt. Hunt



Date:

6/29/2015 

Inspector:

Alain Iglesias (IGGY) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


2014023581

GENERATOR LOAD BANK TEST: PARTIAL APPROVAL

GENERATOR LOAD BANK TEST WITNESSED AND OK (REPORTS AND CERTIFCATE RECIEVED ON SITE AT TIME OF INSPECTION.)

FOR TCO PURPOSES, THE ENTIRE WEST SIDE AND ALL COMMON AREAS ON THE EAST SIDE TO INCLUDE ELEVATORS BEING USED WILL HAVE TO BE TESTED ON GENERATOR POWER FOR LIGHTING AND ELEVATOR FUNCTIONALITY.

ITEMS PENDING FOR GENERATOR ACCEPTANCE:

1. PROVIDE A WEATHER PROOF REMOTE EMERGENCY STOP OUTSIDE OF THE BUILDING HOUSING THE PRIME MOVER; NFPA 110: 5.6.5.6

2. PROVIDE ALL APPROPRIATE SIGNS; FUEL TYPE, FUEL CAPACITY, NO SMOKING, AND NFPA 704 PLACARDING (ASSURE TO HAVE ONE NFPA 704 PLACARD INSTALLED SO AS TO BE VISIBLE FROM THE STREET.)

3. PROVDE MEANS TO TEST AT LEAST ONE ELEVATOR PER SHAFT WHILE ON GENERATOR POWER. (ELEVATORS WERE NOT WORKING AT TIME OF INSPECTION. NFPA 110: 11.8.5.2.4 (5)

4. PROVIDE MEANS TO TEST STANBY POWER TRANSFERABILITY TO ALL ELEVATORS ON EMERGENCY POWER. NFPA 110: 11.8.5.2.4 (5)

ITEMS FOR LIFE SAFETY IN GENERTOR ROOM:

1. PROVIDE PANIC HARDWARE TO DOOR AS PER PLANS.

2. PROVIDE HANDRAILS TO STAIRS AS PER NFPA 101: 7.2.2.4.4

3. PROVIDE A CERTIFIED AND TAGGD FIRE EXTIGUISHER TO BE MOUNTED NO HIGHTER THAT 5 FEET FROM GRADE AT THE HANDLE. NFPA 101: 9.7.4.1

EM LIGHTS TESTED - OK

7 HR. SRI

FEES ADDED

LT. IGLESIAS



Date:

6/27/2015 

Inspector:

Alain Iglesias (IGGY) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


2014023581
ECHO AVENTURA
6/25/15

SRI INSPECTION PERFORMED FOR TCO PROCESS: CONTINUES

TODAY VERFIRED ALL INDEPENDANT SMOKE ALARMS FOR FLOORS 6 THROUGH 2 AD OK WITH THE FOLLOWING EXCPETIONS:

UNITS 306, 307, & 608 NOT WORKING.

SPRINKLER FINAL FOR CERTAIN AREAS ALSO PERFOMED AND COMMETNS HAVE BEEN ADDED UNDER THE SPRINKLER PERMIT# 2014059828

5 HR. SRI.

LT. IGLESIAS



Date:

6/26/2015 

Inspector:

Michele McCook (MMW) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


Insp 6-25-15 mmw
Echo
Elevator recall approved for cores 3 and 4
1. All testing completed EXCEPT:
2. Elevator security card reader still needs to be tested to variy phase 2 override. Security pad not installed at time of inspection.
3. Elevator shaft moke detector tested ok. Roof damper activation ok.
4. Phase 1 and 2 tested ok.



Date:

6/26/2015 

Inspector:

Michele McCook (MMW) 

Type:

211 - PRELIMINARY

Status:

2 - APPROVED PARTIAL


6-24-15 mmw
Echo
Elevator recall for core 2 tested ok EXCEPT:
1. Fire operations still needs tested.
2. Smoke detector elevator shaft tested ok. Roof damper activation.



Date:

6/24/2015 

Inspector:

Michele McCook (MMW) 

Type:

209 - FIRE FINAL

Status:

2 - APPROVED PARTIAL


insp 6-23-15
Echo
Elevator recall approved for core 1 pending:
1. Elevator security card reader not installed at time of inspection.Phase 1 and 2 will need to be retested to varify fire ops override.
2. Elevator shaft smoke detector tested ok. Damper tested ok.

Note: Elevator inspector requesting load testing of all 19 elevators before TCO.



Date:

6/22/2015 

Inspector:

Walter  Wray (WRAYWW) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


1. 15 Points for the Generator were transmitted and verified.

2. Both EM stops were tested & OK

3. 10 sec Transfer took 1 sec

4. Witnessed generator acceptance test still pending.

5. 4 hr min. SRI fee applied



Date:

10/23/2014 

Inspector:

Michele McCook (MMW) 

Type:

209 - FIRE FINAL

Status:

86 - FIRE FINAL APPRVD PENDING FEES


10-23-14 mmw
Echo, 2014023581, M2014001079
1. Preliminary inspection completed 10/20/14. Report filed in fire app8.
2. Sri fee apply.