Permit Number: 2014023581 |
Date:8/1/2016 |
Inspector:Walter Wray (WRAYWW) |
Type:209 - FIRE FINAL |
Status:86 - FIRE FINAL APPRVD PENDING FEES |
FIRE FINAL APPROVED PENDING PAYMENT OF ALL FEES |
Date:7/25/2016 |
Inspector:Walter Wray (WRAYWW) |
Type:209 - FIRE FINAL |
Status:2 - APPROVED PARTIAL |
7/25/16 All permits have been finalized except for the master permit.
|
Date:7/18/2016 |
Inspector:Walter Wray (WRAYWW) |
Type:209 - FIRE FINAL |
Status:2 - APPROVED PARTIAL |
BDA TESTING AND PREVIOUS ITEMS CHECKED OFF FROM MASTER LIST. SEE COMMENTS UNDER MASTRE LIST AND BDA PERMIT #2016-020580 |
Date:7/7/2016 |
Inspector:Carla Crook (CCROOK) |
Type:219 - FIRE - INSPECTION COMMENT |
Status:90 - FIRE - COMMENTS ONLY |
Date:7/7/2016 |
Inspector:Carla Crook (CCROOK) |
Type:219 - FIRE - INSPECTION COMMENT |
Status:90 - FIRE - COMMENTS ONLY |
Date:7/7/2016 |
Inspector:Carla Crook (CCROOK) |
Type:219 - FIRE - INSPECTION COMMENT |
Status:90 - FIRE - COMMENTS ONLY |
Date:7/7/2016 |
Inspector:Carla Crook (CCROOK) |
Type:219 - FIRE - INSPECTION COMMENT |
Status:90 - FIRE - COMMENTS ONLY |
BDA Acceptance Test passed for MDFR 450mhz.
|
Date:6/8/2016 |
Inspector:Carla Crook (CCROOK) |
Type:219 - FIRE - INSPECTION COMMENT |
Status:90 - FIRE - COMMENTS ONLY |
BDA Signal Strength Acceptance Testing.
|
Date:5/23/2016 |
Inspector:Walter Wray (WRAYWW) |
Type:209 - FIRE FINAL |
Status:2 - APPROVED PARTIAL |
Items completed from Master List. |
Date:5/16/2016 |
Inspector:Walter Wray (WRAYWW) |
Type:209 - FIRE FINAL |
Status:3 - REJECTED NOT TO CODE |
Items from Master List completed |
Date:5/2/2016 |
Inspector:Walter Wray (WRAYWW) |
Type:208 - FIRE TCO INSPECTION |
Status:47 - APPROVED FOR TEMPORARY ONLY |
1. TCO EXT RECOMMENDED FOR ALL PHASES OF THE BLDG W/CAPT S APPROVAL SIGNATURE. TAKE THIS SHEET & AVENTURA S TCO FORM TO FIRE ENGINEERING FOR APPROVAL SIGNATURE.
|
Date:2/1/2016 |
Inspector:Walter Wray (WRAYWW) |
Type:209 - FIRE FINAL |
Status:3 - REJECTED NOT TO CODE |
Items checked off from LT Hunt s master list. List will be updated and sent to Pablo. |
Date:1/26/2016 |
Inspector:Walter Wray (WRAYWW) |
Type:208 - FIRE TCO INSPECTION |
Status:47 - APPROVED FOR TEMPORARY ONLY |
1. TCO EXT RECOMMENDED FOR ALL PHASES OF THE BLDG W/CAPT S APPROVAL SIGNATURE. TAKE THIS SHEET & AVENTURA S TCO FORM TO FIRE ENGINEERING FOR APPROVAL SIGNATURE.
|
Date:12/28/2015 |
Inspector:Walter Wray (WRAYWW) |
Type:219 - FIRE - INSPECTION COMMENT |
Status:90 - FIRE - COMMENTS ONLY |
1. TCO RECOMMENDED FOR LANAI UNITS #107-110. TCO MUST BE SIGNED BY FIRE PREVENTION CAPT FOR TCO APPROVAL.
|
Date:12/2/2015 |
Inspector:Walter Wray (WRAYWW) |
Type:208 - FIRE TCO INSPECTION |
Status:47 - APPROVED FOR TEMPORARY ONLY |
1. TCO RECOMMENDED FOR FL S #9-11 AND PLUNGE POOLS EAST TOWER. LANAIS #101-106 WEST TOWER ALSO RECOMMENDED FOR TCO W/CAPT S APPROVAL SIGNATURE.
|
Date:11/12/2015 |
Inspector:Walter Wray (WRAYWW) |
Type:208 - FIRE TCO INSPECTION |
Status:47 - APPROVED FOR TEMPORARY ONLY |
1. TCO is recommended for the FL s 6-8 of the East Tower. Take this form & the TCO form to Fire Engineering for Capt s approval signature.
|
Date:10/29/2015 |
Inspector:Walter Wray (WRAYWW) |
Type:208 - FIRE TCO INSPECTION |
Status:47 - APPROVED FOR TEMPORARY ONLY |
1. A TCO EXT FOR THE WEST BLDG IS RECOMMENDED PENDING THE CAPT S APPROVAL SIGNATURE. THIS EXT WILL ALSO INCLUDE THE PLUNGE POOLS.
|
Date:10/26/2015 |
Inspector:Walter Wray (WRAYWW) |
Type:208 - FIRE TCO INSPECTION |
Status:3 - REJECTED NOT TO CODE |
INSP WAS FOR A TCO EXT. AND INSP OF THE PLUNGE POOLS. HANDRAILS FOR THE POOLS NEED TO BE BETWEEN 34-38" IN ACCORDANCE W/NFPA 101:7.2.2 |
Date:10/14/2015 |
Inspector:Walter Wray (WRAYWW) |
Type:208 - FIRE TCO INSPECTION |
Status:3 - REJECTED NOT TO CODE |
TCO ITEMS FOR FLOORS 2-5 IN THE EAST TOWER WERE ADDRESSED. ITEMS #5-7 FROM LIST DATED 10/12/15 COMPLETED. |
Date:10/13/2015 |
Inspector:Kelvin Thompson (KET) |
Type:211 - PRELIMINARY |
Status:2 - APPROVED PARTIAL |
1. Elevator recall approved for elevator #14, okay |
10/12/15 Smoke control testing was witnessed by LT Wray & LT Thompson today.
|
Date:10/2/2015 |
Inspector:Alain Iglesias (IGGY) |
Type:208 - FIRE TCO INSPECTION |
Status:2 - APPROVED PARTIAL |
2014023581
|
Date:10/1/2015 |
Inspector:Alain Iglesias (IGGY) |
Type:219 - FIRE - INSPECTION COMMENT |
Status:90 - FIRE - COMMENTS ONLY |
2014023581
|
Date:9/30/2015 |
Inspector:Dianne Gary (DGARY) |
Type:208 - FIRE TCO INSPECTION |
Status:2 - APPROVED PARTIAL |
Permit number: 2014023581
|
Date:9/28/2015 |
Inspector:Walter Wray (WRAYWW) |
Type:209 - FIRE FINAL |
Status:3 - REJECTED NOT TO CODE |
Phase 2 for elevator recall tested & ok for elevators #9-12. This was pending frm LT McCook s list dated 8-24-15 |
Date:9/25/2015 |
Inspector:Nassoma Morgan (NMORGAN) |
Type:208 - FIRE TCO INSPECTION |
Status:2 - APPROVED PARTIAL |
LT. MORGAN 2014023581 SRI
|
Date:9/24/2015 |
Inspector:Alain Iglesias (IGGY) |
Type:208 - FIRE TCO INSPECTION |
Status:2 - APPROVED PARTIAL |
2014023581
|
Date:9/21/2015 |
Inspector:Curtis Wolff (WOLFFC) |
Type:208 - FIRE TCO INSPECTION |
Status:34 - INSPECTION CANCELLATION |
INSPECTION CANCELED PER PABLO
|
Date:9/21/2015 |
Inspector:Nassoma Morgan (NMORGAN) |
Type:208 - FIRE TCO INSPECTION |
Status:34 - INSPECTION CANCELLATION |
Date:9/14/2015 |
Inspector:Walter Wray (WRAYWW) |
Type:209 - FIRE FINAL |
Status:3 - REJECTED NOT TO CODE |
items frm master list completed |
Date:9/11/2015 |
Inspector:Alain Iglesias (IGGY) |
Type:219 - FIRE - INSPECTION COMMENT |
Status:90 - FIRE - COMMENTS ONLY |
2014023581
|
Date:9/2/2015 |
Inspector:Walter Wray (WRAYWW) |
Type:209 - FIRE FINAL |
Status:3 - REJECTED NOT TO CODE |
9/2/15 Dampers tested & ok in Stair #11 |
Date:9/1/2015 |
Inspector:Walter Wray (WRAYWW) |
Type:208 - FIRE TCO INSPECTION |
Status:3 - REJECTED NOT TO CODE |
COMMENTS TO BE E-MAILED TO PABLO |
Date:8/26/2015 |
Inspector:Rasheelah Brown (RBROWN) |
Type:208 - FIRE TCO INSPECTION |
Status:1 - APPROVED |
TCO APPROVED FOR 90 DAYS LT MCCOOK / FALCO |
Date:8/24/2015 |
Inspector:Michele McCook (MMW) |
Type:208 - FIRE TCO INSPECTION |
Status:2 - APPROVED PARTIAL |
insp 8-21-15 mmw
|
Date:8/23/2015 |
Inspector:Kelvin Thompson (KET) |
Type:209 - FIRE FINAL |
Status:2 - APPROVED PARTIAL |
1. Fire final partial inspection.
|
Date:8/19/2015 |
Inspector:Walter Wray (WRAYWW) |
Type:208 - FIRE TCO INSPECTION |
Status:3 - REJECTED NOT TO CODE |
8/18/15 Stairwell signage and EM lighting checked & ok floors #1-8 except for the following items listed:
|
Date:8/17/2015 |
Inspector:Walter Wray (WRAYWW) |
Type:208 - FIRE TCO INSPECTION |
Status:3 - REJECTED NOT TO CODE |
EAST SIDE LOBBY AREA AND POOL DECK NOT READY FOR TCO |
Date:7/30/2015 |
Inspector:Michele McCook (MMW) |
Type:208 - FIRE TCO INSPECTION |
Status:47 - APPROVED FOR TEMPORARY ONLY |
7-29-15 mmw
|
Date:7/29/2015 |
Inspector:Michele McCook (MMW) |
Type:211 - PRELIMINARY |
Status:2 - APPROVED PARTIAL |
7-29-15 MMW
|
Date:7/29/2015 |
Inspector:Michele McCook (MMW) |
Type:211 - PRELIMINARY |
Status:2 - APPROVED PARTIAL |
7-28-15 mmw
|
Date:7/27/2015 |
Inspector:Stephen Hunt (HU1507) |
Type:208 - FIRE TCO INSPECTION |
Status:3 - REJECTED NOT TO CODE |
Echo Aventura 7/27/15
|
Date:7/25/2015 |
Inspector:Stephen Hunt (HU1507) |
Type:208 - FIRE TCO INSPECTION |
Status:3 - REJECTED NOT TO CODE |
Echo Aventura 7/25/15
|
Date:7/25/2015 |
Inspector:Michele McCook (MMW) |
Type:211 - PRELIMINARY |
Status:2 - APPROVED PARTIAL |
7-25-15 mmw
|
Date:7/24/2015 |
Inspector:Jose De Alfaraz (JOSEED) |
Type:211 - PRELIMINARY |
Status:3 - REJECTED NOT TO CODE |
7/24/15
|
Date:7/24/2015 |
Inspector:Stephen Hunt (HU1507) |
Type:211 - PRELIMINARY |
Status:3 - REJECTED NOT TO CODE |
Echo Aventura 7/24/15
|
INSP 7-23-15 MMW
|
Date:7/24/2015 |
Inspector:Stephen Hunt (HU1507) |
Type:208 - FIRE TCO INSPECTION |
Status:3 - REJECTED NOT TO CODE |
Echo Aventura 7/23/15
|
Date:7/22/2015 |
Inspector:Stephen Hunt (HU1507) |
Type:211 - PRELIMINARY |
Status:3 - REJECTED NOT TO CODE |
Echo Aventura 7/22/15
|
Date:7/21/2015 |
Inspector:Stephen Hunt (HU1507) |
Type:211 - PRELIMINARY |
Status:2 - APPROVED PARTIAL |
Echo Aventura 7/21/15
|
Date:7/21/2015 |
Inspector:Michele McCook (MMW) |
Type:211 - PRELIMINARY |
Status:2 - APPROVED PARTIAL |
7-21-15 mmw
|
insp 7-20-15 mmw
|
Date:7/19/2015 |
Inspector:Stephen Hunt (HU1507) |
Type:219 - FIRE - INSPECTION COMMENT |
Status:90 - FIRE - COMMENTS ONLY |
Echo Aventura
|
Date:7/17/2015 |
Inspector:Stephen Hunt (HU1507) |
Type:209 - FIRE FINAL |
Status:2 - APPROVED PARTIAL |
7/17/15 All building elevators in East and West Towers inspected, tested and approved with the Elevator Inspector for standby power operation and security system Fire Service override only. Fire Service recall testing approved by Lt. McCook on previous inspections. Plywood installed elevator cars shall be removed and replaced with can interior finishes that comply with ASME A17.1. The plywood would be permitted to remain only if the elevators hositways are provide with sprinkler protection and shunt trip activation at the top of the hoistways in accordance with NFPA 101: 101, 13, 72 and ASME A17.1
|
Date:7/15/2015 |
Inspector:Stephen Hunt (HU1507) |
Type:209 - FIRE FINAL |
Status:3 - REJECTED NOT TO CODE |
ECHO
|
Date:7/14/2015 |
Inspector:Stephen Hunt (HU1507) |
Type:208 - FIRE TCO INSPECTION |
Status:3 - REJECTED NOT TO CODE |
Echo Aventura 7/14/15
|
7-13-15 MMW
|
7-11-15 mmw
|
Date:7/13/2015 |
Inspector:Alain Iglesias (IGGY) |
Type:208 - FIRE TCO INSPECTION |
Status:2 - APPROVED PARTIAL |
2014023581
|
Date:7/11/2015 |
Inspector:Michele McCook (MMW) |
Type:211 - PRELIMINARY |
Status:2 - APPROVED PARTIAL |
7-10-15 mmw
|
Date:7/10/2015 |
Inspector:Michele McCook (MMW) |
Type:211 - PRELIMINARY |
Status:2 - APPROVED PARTIAL |
Insp completed 7-8-15 mmw
|
Date:7/10/2015 |
Inspector:Walter Wray (WRAYWW) |
Type:219 - FIRE - INSPECTION COMMENT |
Status:90 - FIRE - COMMENTS ONLY |
7/9/15 Fire-rated doors were checked for latching and labels on floors #2-8. All were in compliance except for the following:
|
Date:7/10/2015 |
Inspector:Alain Iglesias (IGGY) |
Type:208 - FIRE TCO INSPECTION |
Status:2 - APPROVED PARTIAL |
2014023581
|
Date:7/8/2015 |
Inspector:Michele McCook (MMW) |
Type:209 - FIRE FINAL |
Status:2 - APPROVED PARTIAL |
insp 7-7-15 mmw
|
Date:7/7/2015 |
Inspector:Alain Iglesias (IGGY) |
Type:208 - FIRE TCO INSPECTION |
Status:2 - APPROVED PARTIAL |
2014023581
|
7-6-15 mmw
|
Date:6/30/2015 |
Inspector:Stephen Hunt (HU1507) |
Type:208 - FIRE TCO INSPECTION |
Status:3 - REJECTED NOT TO CODE |
Echo Aventura 2014023581 6/30/15
|
Inspected 6-26-15 mw
|
Date:6/29/2015 |
Inspector:Stephen Hunt (HU1507) |
Type:208 - FIRE TCO INSPECTION |
Status:3 - REJECTED NOT TO CODE |
Echo Aventura 2014023581 6/29/15
|
Date:6/29/2015 |
Inspector:Alain Iglesias (IGGY) |
Type:219 - FIRE - INSPECTION COMMENT |
Status:90 - FIRE - COMMENTS ONLY |
2014023581
|
Date:6/27/2015 |
Inspector:Alain Iglesias (IGGY) |
Type:219 - FIRE - INSPECTION COMMENT |
Status:90 - FIRE - COMMENTS ONLY |
2014023581
|
Date:6/26/2015 |
Inspector:Michele McCook (MMW) |
Type:219 - FIRE - INSPECTION COMMENT |
Status:90 - FIRE - COMMENTS ONLY |
Insp 6-25-15 mmw
|
Date:6/26/2015 |
Inspector:Michele McCook (MMW) |
Type:211 - PRELIMINARY |
Status:2 - APPROVED PARTIAL |
6-24-15 mmw
|
Date:6/24/2015 |
Inspector:Michele McCook (MMW) |
Type:209 - FIRE FINAL |
Status:2 - APPROVED PARTIAL |
insp 6-23-15
|
Date:6/22/2015 |
Inspector:Walter Wray (WRAYWW) |
Type:208 - FIRE TCO INSPECTION |
Status:3 - REJECTED NOT TO CODE |
1. 15 Points for the Generator were transmitted and verified.
|
Date:10/23/2014 |
Inspector:Michele McCook (MMW) |
Type:209 - FIRE FINAL |
Status:86 - FIRE FINAL APPRVD PENDING FEES |
10-23-14 mmw
|