THESE COMMENTS ARE FOR THE PRELIMINARY INSPECTION PERFORMED ON 21 October 2021
Permit number: 2015033676
The Shul
9540 Collins Avenue
Town of Surfside, FL.
1. Fire preliminary inspection performed.
A preliminary inspection was conducted at the request of the client, and the report will be emailed to the client within 24 hours of this inspection.
NFPA 1:1.14.4 Review and approval by the AHJ shall not relieve the applicant of the responsibility of compliance of this Code.
1. Provide mounted Supra Max elevator boxes mounted in elevator lobbies for each bank of elevators. Mounting height shall be 5 to 6 from the finished floor. Provide all keys to operate each bank of elevator cars in its appropriate box in addition to a machine room key. If providing a Supra Max box at the Fire Command room, provide a key for the Fire Command room, Fire Pump room, generator room, roof access door, and the Elevator machine rooms. Supra Max boxes are available by calling: 1-800-547-0252, Reference # 164144, Code # 6538.
2. Provide an additional Supra-Max box to be installed in the Fire Command room for the elevator status panel override keys.
3. Post the address on the street side of the bldg. (Collins Avenue) Minimum of 6" in size and of contrasting color to its background. NFPA 1:10.12.1.1.
4. Install signage on all electrical rooms doors, generator room, elevator machine room, and fire pump room doors states "NO STORAGE." NFPA 1:11.1.7.2
5. Install tagged and certified fire extinguishers in the parking garage with a bare minimum rating of 10-B. Travel distance shall not exceed 30 , and the top of the extinguisher shall not exceed 5 from the floor when mounted. NFPA 10: Table 5.3.1 and 1:13.6.8.1.3.7. If the fire extinguisher has a minimum rating of 20-B, the travel distance can be every 50 . Need signage above Garage F/E s.
6. Fire extinguishers are required every 75 of travel distance inside the building. Provide a minimum 2A:10BC tagged & certified fire extinguishers mounted on the wall ? top no higher than 5 from the floor. NFPA 101:13.6.3.10.
7. Bollard protection shall be provided at all exit access doors and exterior swinging doors in a parking garage blocked by vehicular traffic. Bollards will be no more than 4 apart. NFPA 101:7.1.10.1
8.Exit signs in the parking garage will be positioned so as not to be obstructed by sprinkler piping or any other obstruction. Exit signs can be adjusted so that they are no less than 80" from the finished floor. NFPA 101:7.10
9. 11.10.2 Where required by the AHJ, two-way radio communication enhancement systems shall comply with NFPA 1221. To schedule a BDA pretest to determine if a system installation is required, contact MDFRBDAS@miamidade.gov.
10. Normal lighting and emergency lighting shall comply with NFPA 101:7.9. The client is to schedule a nighttime inspection is to verify compliance with the required illumination of emergency lighting. The electrical contractors should be on site for this inspection. All areas shall not be served exclusively by an Emergency circuit or a Normal circuit fed from a house electrical panel. No one action shall leave any space in darkness. Battery backup bug eyes will serve as a sufficient remedy in areas with only EM lighting circuits.
11. Normal and emergency lighting is required at all exterior stairs and ramps that are part of the exit discharge leading to the public way under NFPA 101:11.8.1.2.
12. Emergency lighting will need to be installed outside on the North exit discharge. Ensure that this light is weatherproof.
13. The client will provide the necessary documentation to show approval of all inspection types to include but not limited to the following:
(a) Fire alarm test
(b) Fire suppression system final approval
(c) Special door locking arrangements
(d) Life Safety inspection of units to include entry doors, balconies, and general life safety of the site.
(e) Fire Department set up sites
(f) Normal and emergency lighting of all areas
14. Provide copies of all elevator certifications that are to be posted in the elevator cab.
15. Provide stair identification signage within the stair enclosures. The signage should indicate the story, the terminus of the top and bottom of the stair enclosure, and the identification of the stair enclosure. The signage shall also state the level of, and the direction to, exit discharge. The signage shall be inside the enclosure located approximately 5 ft above the floor in a position that is readily visible when the door is in the open or closed position in accordance with NFPA 101:7.2.2.5.4. Floor level designation shall be tactile in accordance w/ICC /ANSI
|
|