Inspection Result Comments

Saturday, June 7, 2025

Permit Number:  2015011603


Date:

9/21/2022 

Inspector:

Jose De Alfaraz (JOSEED) 

Type:

209 - FIRE FINAL

Status:

1 - APPROVED


Surf Club
Main Master Permit 2015011603
09/20/22


1. Final fire CO approved.
2. Fire alarm 2015065461 and Access control 2017038849 permits are approved pending fees.
3. BDA 2016042208 is approved.



Date:

9/8/2022 

Inspector:

Jose De Alfaraz (JOSEED) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


FOUR SEASONS SURF CLUB HOTEL
9011 COLLINS AVE
Main General permit #2015011603
09/07/22

1. TCO extension inspection is complete for 30 days. See the Fire Captain for the TCO extension approval.
2. Still pending the remaining Miami-Dade sub-permits that are tied to this project to be finaled.
3. Provide the BDA permit that hasn t been identified yet.
4. Item 4 from my previous list is completed. Regarding the concrete bumper in front of the exit door.



Date:

8/29/2022 

Inspector:

Sheran Johnson (SAJOHNS) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


On August 29, 2022, I spoke with customer/GC Mr. Cameron 239-641-5353 was advised that his current Temporary Certificate of Occupancy will expired on September 4, 2022.

TCO FOR B-1 SOUTH LOBBY, CORE #1 2ND -9TH FLOOR

In order to remain in compliance, he must schedule a Temporary Certificate of Occupancy Extension or Fire Final for his Certificate of Occupancy.

The TCO must be fully process and paid for, also the paperwork must be sign by the New Construction Bureau Office-in-Charge, before September 4, 2022 or a Notice of Violation (NOV) will be issued.

Lt. Johnson 8/29/2022



Date:

8/3/2022 

Inspector:

Jose De Alfaraz (JOSEED) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


FOUR SEASONS SURF CLUB HOTEL
9011 COLLINS AVE
Main General permit #2015011603
08/03/22

1. TCO extension inspection is complete for 30 days. See the Fire Captain for the TCO extension approval.
2. Still pending the remaining Miami-Dade sub-permits that are tied to this project to be finaled.
3. Provide the BDA permit that hasn t been identified yet.
4. Install a concrete parking bumper in front of the exterior Barton Room Stairwell exit door to prevent the valet vehicles from blocking the exit door.



Date:

8/1/2022 

Inspector:

Sheran Johnson (SAJOHNS) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


On August 1, 2022, I spoke with customer/GC Mr. Cameron 239-641-5353 was advised that his current Temporary Certificate of Occupancy will expired on August 7, 2022.

TCO FOUR SEASONS CLUB HOTEL

In order to remain in compliance, he must schedule a Temporary Certificate of Occupancy Extension or Fire Final for his Certificate of Occupancy.

The TCO must be fully process and paid for, also the paperwork must be sign by the New Construction Bureau Office-in-Charge, before August 7, 2022 or a Notice of Violation (NOV) will be issued.

Lt. Johnson 8/1/2022



Date:

7/7/2022 

Inspector:

Jose De Alfaraz (JOSEED) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


FOUR SEASONS SURF CLUB HOTEL
9011 COLLINS AVE
Main General permit #2015011603
07/06/22

1. TCO extension inspection is complete for 30 days. See the Fire Captain for the TCO extension approval.
2. Still pending the remaining Miami-Dade sub-permits that are tied to this project to be finaled.
3. Provide the BDA permit that hasn t been identified yet.
4. Install a concrete parking bumper in front of the exterior Barton Room Stairwell exit door to prevent the valet vehicles from blocking the exit door.



Date:

6/30/2022 

Inspector:

Sheran Johnson (SAJOHNS) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


On June 30, 2022, spoke with customer/GC Mr. Alex & Mr. Cameron 239-641-5353 & 786-348-4082 was advised that his current Temporary Certificate of Occupancy (TCO) will expired on July 8, 2022. (TCO for Surf Club Hotel).


In order to remain in compliance, he must schedule a Temporary Certificate of Occupancy Extension or Fire Final for his Certificate of Occupancy.

The TCO must be fully process and paid for, also the paperwork must be sign by the New Construction Bureau Office-in-Charge, before July 8, 2022 or a Notice of Violation (NOV) will be issued.

Lt. Johnson 6/30/2022



Date:

6/7/2022 

Inspector:

Jose De Alfaraz (JOSEED) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


FOUR SEASONS SURF CLUB HOTEL
9011 COLLINS AVE
Main General permit #2015011603
06/06/22

1. TCO extension inspection is complete for 30 days. See the Fire Captain for the TCO extension approval.
2. Still pending the remaining Miami-Dade sub-permits that are tied to this project to be finaled.
3. Provide the BDA permit that hasn t been identified yet.
4. Install a concrete parking bumper in front of the exterior Barton Room Stairwell exit door to prevent the valet vehicles from blocking the exit door.



Date:

5/26/2022 

Inspector:

Sheran Johnson (SAJOHNS) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


On May 26, 2022, Customer Mr. Cameron 239-641-5353 was advised that his client current Temporary Certificate of Occupancy will expired on June 9, 2022. (TCO Surf Club B-1 South Tower Lobby, #1,2nd-9 Floor area for TCO )

In order to remain in compliance, he must schedule a Temporary Certificate of Occupancy Extension or Fire Final for his Certificate of Occupancy.

The TCO must be fully process and paid for, also the paperwork must be sign by the New Construction Bureau Office-in-Charge, before June 9, 2022 or a Notice of Violation (NOV) will be issued.

Lt. Johnson 5/26/2022



Date:

4/19/2022 

Inspector:

Jose De Alfaraz (JOSEED) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


FOUR SEASONS SURF CLUB HOTEL
9011 COLLINS AVE
Main General permit #2015011603
04/18/22

1. TCO extension inspection is complete for 30 days. See the Fire Captain for the TCO extension approval.
2. Still pending the remaining Miami-Dade sub-permits that are tied to this project to be finaled.
3. Provide the BDA permit that hasn t been identified yet.
4. Install a concrete parking bumper in front of the exterior Barton Room Stairwell exit door to prevent the valet vehicles from blocking the exit door.



Date:

2/23/2022 

Inspector:

Jose De Alfaraz (JOSEED) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


FOUR SEASONS SURF CLUB HOTEL
9011 COLLINS AVE
Main General permit #2015011603
02/22/22

1. TCO extension inspection is complete for 30 days. See the Fire Captain for the TCO extension approval.
2. Still pending the remaining Miami-Dade sub-permits that are tied to this project to be finaled.
3. Provide the BDA permit that hasn t been identified yet.
4. Install a concrete parking bumper in front of the exterior Barton Room Stairwell exit door to prevent the valet vehicles from blocking the exit door.




Date:

2/23/2022 

Inspector:

Jose De Alfaraz (JOSEED) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


FOUR SEASONS SURF CLUB HOTEL
9011 COLLINS AVE
Main General permit #2015011603
02/22/22

1. TCO extension inspection is complete for 30 days. See the Fire Captain for the TCO extension approval.
2. Still pending the remaining Miami-Dade sub-permits that are tied to this project to be finaled.
4. Provide the BDA permit that hasn t been identified yet.
5. Install a concrete parking bumper in front of the exterior Barton Room Stairwell exit door to prevent the valet vehicles from blocking the exit door.





Date:

2/23/2022 

Inspector:

Jose De Alfaraz (JOSEED) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


FOUR SEASONS SURF CLUB HOTEL
9011 COLLINS AVE
Main General permit #2015011603

02/22/21

1. TCO extension inspection is complete for 30 days. See the Fire Captain for the TCO extension approval.
2. Still pending the remaining Miami-Dade sub-permits that are tied to this project to be finaled.
4. Provide the BDA permit that hasnt been identified yet.



Date:

2/22/2022 

Inspector:

Sheran Johnson (SAJOHNS) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


On February 22, 2022 Customer Mr. Don Cohen 770-695-9651 was advised that his current Temporary Certificate of Occupancy will expired on February 28, 2022.

In order to remain in compliance, he must schedule a Temporary Certificate of Occupancy Extension or Fire Final for his Certificate of Occupancy, before February 28, 2022.

The customer was given three days to comply, meaning the Temporary Certification of Occupancy Extension must be fully process and paid for within three (3) days, also paperwork must be sign by the NEW Construction Bureau Office in-Charge (OIC) or a Notice of Violation (NOV) will be issued.

Lt. Johnson 2/22/2022



Date:

2/15/2022 

Inspector:

Ricardo  Cruz (E32388) 

Type:

208 - FIRE TCO INSPECTION

Status:

4 - REJECTED PLAN & PERMIT MISSING


2015011603
9011 Collins Ave



Rejected plans and permit missing

No plans or permit were available for inspection.

Provide approved plans and Miami dade permit card for next inspection. NFPA 1:1.14

Lt. Cruz



Date:

12/22/2021 

Inspector:

Jose De Alfaraz (JOSEED) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


Surf Club
12/17/21

This Life safety inspection was replaced for a Access Control inspection under permit #2017038849.

The SRI fees were added to that permit.



Date:

11/29/2021 

Inspector:

Sheran Johnson (SAJOHNS) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


On November 29, 2021 Customer Mr. Don Cohen 770-695-9651 was advised that his current Temporary Certificate of Occupancy will expired on November 30, 2021.

In order to remain in compliance, he must schedule a Temporary Certificate of Occupancy Extension or Fire Final for his Certificate of Occupancy, before November 30, 2021.

The customer was given three days to comply, meaning the Temporary Certification of Occupancy Extension must be fully process and paid for within three (3) days, also paperwork must be sign by the NEW Construction Bureau Office in-Charge (OIC) or a Notice of Violation (NOV) will be issued.

Lt. Johnson 11/29/2021



Date:

11/10/2021 

Inspector:

John Molnar (MOLNAR) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY



PERMIT #2015011603 **M2014000010**
FOUR SEASONS SURF CLUB HOTEL
9011 COLLINS AVE
4/20/2021

SUBSIDIARY PERMITS
FIRE ALARM 2016042208
FIRE SPRINKLER 2015067872
WATER MAIN 2015001452
SITE PLAN 2014056456
BDA ?
ACCESS CONTROL ?


1- 90 DAY FIRE TCO EXTENSION IS RECOMMENDED WITH CAPTAINS APPROVAL, TO SCHEDULE APPOINTMENT CALL 786-315-2771 MON-FRI FROM 0730-1530. ONCE SCHEDULED, TAKE THE CITY OF SURFSIDE TCO FORM TO 11805 SW CORAL WAY FOR THE CAPTAIN APPROVAL SIGNATURE

2- REASON FOR TCO IS AWAITING TO CLOSE ALL SUBSIDIARY MIAMI DADE PERMITS INCLUDING THE BDA PERMIT


Prior to next inspection have GC on job site with what is pending to close this permit.
I advise to do this without project lead team.



Date:

9/9/2021 

Inspector:

Sheran Johnson (SAJOHNS) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


Permit: 2015011603
Name: The Surf Club Restaurant
Address: 9011 Collins Ave

Citation was issued on 9-9-2021 at 8:40 am. Citation # B253874 Section 14-39 Failure to obtain required permit or violation of condition of permit, or failure to obtain required fire department approval to use or occupancy. REF NO. 4401. CODE 14-39.

Occupying without Temporary Certificate of Occupancy Extension or Fire Final since 9-1-2021.

Please DO NOT CLOSE THIS PERMIT OUT.

LT. S. Johnson 9-9-2021



Date:

9/1/2021 

Inspector:

Jorge  Garcia (E33268) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


PERMIT #2015011603 **M2014000010**
FOUR SEASONS SURF CLUB HOTEL
9011 COLLINS AVE
4/20/2021

SUBSIDIARY PERMITS
FIRE ALARM 2016042208
FIRE SPRINKLER 2015067872
WATER MAIN 2015001452
SITE PLAN 2014056456
BDA ?
ACCESS CONTROL ?


1- 90 DAY FIRE TCO EXTENSION IS RECOMMENDED WITH CAPTAINS APPROVAL, TO SCHEDULE APPOINTMENT CALL 786-315-2771 MON-FRI FROM 0730-1530. ONCE SCHEDULED, TAKE THE CITY OF SURFSIDE TCO FORM TO 11805 SW CORAL WAY FOR THE CAPTAIN APPROVAL SIGNATURE

2- REASON FOR TCO IS AWAITING TO CLOSE ALL SUBSIDIARY MIAMI DADE PERMITS INCLUDING THE BDA PERMIT.

LT. JORGE GARCIA
09.01.2021



Date:

8/31/2021 

Inspector:

Sheran Johnson (SAJOHNS) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


On August 31, 2021 Customer Mr. Don Cohen 770-695-9651 was advised that his current Temporary Certificate of Occupancy will expired on September 1, 2021.

In order to remain in compliance, he must schedule a Temporary Certificate of Occupancy Extension or Fire Final for his Certificate of Occupancy, before September 1, 2021.

The customer was given three (3) days to comply, meaning the Temporary Certification of Occupancy Extension must be fully process and paid for within three (3) days, also paperwork must be sign by the NEW Construction Bureau Office in-Charge (OIC) or a Notice of Violation (NOV) will be issued.

Lt. Johnson 8/31/2021



Date:

7/27/2021 

Inspector:

Jose De Alfaraz (JOSEED) 

Type:

209 - FIRE FINAL

Status:

3 - REJECTED NOT TO CODE


FOUR SEASONS SURF CLUB HOTEL
9011 COLLINS AVE

MASTER PERMIT #2015011603
SPRINKLER PERMIT #2015067872
WATER MAIN EXTENSION PERMIT #2015001452
MAIN FIRE ALARM PERMIT #2016042208
ACCESS CONTROL PERMIT #2017038849
FIRE ALARM KITCHEN/RESTAURANT PERMIT # 2015065461
BDA PERMIT # UNKNOWN

07/26/2021

1. Final fire CO partial approved.
2. Today closed/finalized the site plan permit 2014056456.
3. Still pending the remaining Miami-Dade sub-permits that are tied to this project to be finaled.
4. Provide the BDA permit that hasn t been identified yet.



Date:

6/8/2021 

Inspector:

Sheran Johnson (SAJOHNS) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


On June 8, 2021, Customer/GC Ms. Randa Lao 808-559-6616 was advised that his current Temporary Certificate of Occupancy will expired on June 17, 2021.

In order to remain in compliance, he must schedule a Temporary Certificate of Occupancy Extension or Fire Final for his Certificate of Occupancy, on or before June 17, 2021.

Customer has three (3) days to comply after the expired date.

Comply means: The Temporary Certification of Occupancy Extension is fully process and paid for within three (3) days, after the expired date, also the paperwork must be sign by the New Construction Bureau Office in-Charge , or a Notice of Violation (NOV) will be issued.

Lt. Johnson 6-8-2021



Date:

6/3/2021 

Inspector:

John Molnar (MOLNAR) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY



PERMIT #2015011603 **M2014000010**
FOUR SEASONS SURF CLUB HOTEL
9011 COLLINS AVE
4/20/2021

SUBSIDIARY PERMITS
FIRE ALARM 2016042208
FIRE SPRINKLER 2015067872
WATER MAIN 2015001452
SITE PLAN 2014056456
BDA ?
ACCESS CONTROL ?


1- 90 DAY FIRE TCO EXTENSION IS RECOMMENDED WITH CAPTAINS APPROVAL, TO SCHEDULE APPOINTMENT CALL 786-315-2771 MON-FRI FROM 0730-1530. ONCE SCHEDULED, TAKE THE CITY OF SURFSIDE TCO FORM TO 11805 SW CORAL WAY FOR THE CAPTAIN APPROVAL SIGNATURE

2- REASON FOR TCO IS AWAITING TO CLOSE ALL SUBSIDIARY MIAMI DADE PERMITS INCLUDING THE BDA PERMIT.



Date:

4/21/2021 

Inspector:

Jose De Alfaraz (JOSEED) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


PERMIT #2015011603 **M2014000010**
FOUR SEASONS SURF CLUB HOTEL
9011 COLLINS AVE
4/20/2021

SUBSIDIARY PERMITS
FIRE ALARM 2016042208
FIRE SPRINKLER 2015067872
WATER MAIN 2015001452
SITE PLAN 2014056456
BDA ?
ACCESS CONTROL ?


1- 90 DAY FIRE TCO EXTENSION IS RECOMMENDED WITH CAPTAINS APPROVAL, TO SCHEDULE APPOINTMENT CALL 786-315-2771 MON-FRI FROM 0730-1530. ONCE SCHEDULED, TAKE THE CITY OF SURFSIDE TCO FORM TO 11805 SW CORAL WAY FOR THE CAPTAIN APPROVAL SIGNATURE

2- REASON FOR TCO IS AWAITING TO CLOSE ALL SUBSIDIARY MIAMI DADE PERMITS INCLUDING THE BDA PERMIT.

3- A LIFE SAFETY WALKTHROUGH OF THE ENTIRE PROJECT WAS PERFORMED TODAY TO ENSURE ALL LIFE SAFETY IS BEING MAINTAINED AND TO BE FAMILIARIZED WITH THIS PROJECT. THIS PROJECT ORGINALLY WAS ASSIGNED TO FF WOLFF AND WAS TRANSFERRED TO ME UPON HIS RETIREMENT.



Date:

3/8/2021 

Inspector:

Sheran Johnson (SAJOHNS) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


Permit: 2015011603
Name: The Surf Club Restaurant
Address: 9011 Collins Ave

Citation was issued on 3-8-2021 at 12:00 pm. Citation # B249853 Section 14-39 Failure to obtain required permit or violation of condition of permit, or failure to obtain required fire department approval to use or occupancy. REF NO. 4401. CODE 14-39.

Occupying without Temporary Certificate of Occupancy Extension or Fire Final since 3-1-2021.

Please DO NOT CLOSE THIS PERMIT OUT.

LT. S. Johnson 3-8-2021



Date:

2/25/2021 

Inspector:

Tina Guiler (TINAG) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


PERMIT #2015011603 **M2014000010**BLD13-727**
SURF CLUB
9011 COLLINS AVE
2/25/2021

SUBSIDIARY PERMITS
FIRE ALARM 2015065461
FIRE SPRINKLER 2018032631


1- 90 DAY FIRE TCO RECOMMENDED WITH CAPTAINS APPROVAL, TO SCHEDULE APPOINTMENT CALL 786-315-2771 MON-FRI FROM 0730-1530. ONCE SCHEDULED TAKE THIS FORM ALONG WITH THE CITY OF SURFSIDE TCO TO 11805 SW CORAL WAY FOR APPROVAL SIGNATURE

2- REASON FOR TCO IS AWAITING CONSTRUCTION TO BE COMPLETED

3- LIFESAFETY ITEMS OKAY.


LT. GUILER



Date:

2/22/2021 

Inspector:

Sheran Johnson (SAJOHNS) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


On February 22, 2021 Customer Mr. Don Cohen 770-695-9651 was advised that his current Temporary Certificate of Occupancy will expired on March 1, 2021.

In order to remain in compliance, he must schedule a Temporary Certificate of Occupancy Extension or Fire Final for his Certificate of Occupancy, before March 1, 2021.

The customer was given three days to comply, meaning the Temporary Certification of Occupancy Extension must be fully process and paid for within three (3) days, also paperwork must be sign by the NEW Construction Bureau Office in-Charge (OIC) or a Notice of Violation (NOV) will be issued.

Lt. Johnson 2/22/2021



Date:

11/10/2020 

Inspector:

Albert Carbonell  (ALCARBO) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


2015011603**M2014000010**BLD13-727**
SURF CLUB
9011 COLLINS AVE

90 DAY FIRE TCO RECOMMENDED WITH CAPTAINS APPROVAL, TO SCHEDULE APPOINTMENT CALL 786-315-2771 MON-FRI FROM 0730-1530. ONCE SCHEDULED TAKE THIS FORM ALONG WITH THE CITY OF SURFSIDE TCO TO 11805 SW CORAL WAY FOR APPROVAL SIGNATURE

REASON FOR TCO IS AWAITING CONSTRUCTION TO BE COMPLETED

SUBSIDIARY PERMITS
FIRE ALARM 2015065461
FIRE SPRINKLER 2018032631

1) LIFESAFETY ITEMS RE-INSPECTED, OKAY.

LT CARBONELL
11\10\2020



Date:

8/14/2020 

Inspector:

Steven  Clements (E164643) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


#2015011603
SURF CLUB
9011 COLLINS AVE.

1. TCO EXTENSION RECOMMENDED FOR 90 DAYS WITH THE CAPTAINS APPROVAL.

2. TO SCHEDULE AN APPOINTMENT CALL 786-315-2717, M-F, 0730-1500. GO TO 9300 NW 41 ST., DORAL TO HAVE CAPTAIN SIGN SURFSIDE TCO FORM.

3. REASON: NEED TO FINISH PROJECT TO CLOSE IT OUT.

4. REP: RANDA LAO @ 808-559-6616

5. NEED TO PAY ALL OUTSTANDING FEES BEFORE A TCO WILL BE RECOMMENDED.

LT S.CLEMENTS
8/14/2020



Date:

8/8/2020 

Inspector:

Sheran Johnson (SAJOHNS) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


On August 8, 2020, Customer Mr. Burak 305-343-5629, Mr Paul 786-792-9319 Commane & Tony Thompson 305-807-1031 was advised that his current Temporary Certificate of Occupancy (TCO) expire on August 06, 2020 and therefore, needs to schedule a TCO Extension or Fire Final for their Certificate of Occupancy (CO).

If the Temporary Certification of Occupancy Extension is not fully process and paid for within seven (7) days the customer is given to comply, before August 13, 2020, a Notice of Violation (NOV) will be issued.



Date:

5/6/2020 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


SURF CLUB
PERMIT 2015011603

1-TCO EXTENSION FOR 90 DAYS WITH THE CAPTAINS APPROVAL FOR THE ABOVE PERMIT
2-GO TO 9300 N.W. 41ST STREET AND HAVE THE CAPTAIN SIGN SURFSIDES TCO FORM
3-REASON: NEED TO FINISH PROJECT TO CLOSE IT OUT

REP: RANDO LAO 808 559-6616

NEED TO PAY ALL OUTSTANDING FEES BEFORE A TCO WILL BE RECOMMENDED

C.B.WOLFF -- 05/06/20



Date:

1/16/2020 

Inspector:

Albert Carbonell  (ALCARBO) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


2015011603**M2014000010***BLD13-727
SURF CLUB
9011 COLLINS AVE

3rd FIRE TCO EXTENSION RECOMMENDED FOR THE SURF CLUB BUILDING WITH CAPTAINS APPROVAL, TAKE THIS FORM ALONG WITH THE CITY OF SURFSIDE TCO FORM TO 11805 SW CORAL WAY FOR A PPROVAL SIGNATURE.

REASON FOR TCO IS AWAITING MUNICIPAL PERMITS TO BE FINALIZED

SUBSIDIARY PERMITS***
FIRE SPRINKLER 2018032631
FIRE ALARM 2015065461

1) ALL LIFE SAFETY ITEMS INSPECTED, OKAY.

2) ALL OUTSTANDING FEES PAID

LT CARBONELL
01\16\2020



Date:

9/21/2019 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMMENDED FOR 90 DAYS WITH THE CAPTAINS APPROVAL

1-REASON: NEED TO FINISH PROJECT AND CLOSE OUT ALL BUILDINGS
2-REP: BRAD COCHRAN 954 224-9066
3-BRAD IS FFAMILAR WITH THE TCO PROCESS

NOTE: NEED TO PAY ALL OUTSTANDING FEES BEFORE A TCO WILL BE RECOMMENDED

SRI FEES APPLY -- C.B.WOLFF -- 09/21/19



Date:

9/14/2019 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

2 - APPROVED PARTIAL


THIS INSPECTION WAS FOR THE BETALUX-E SERIES MODEL 171 (64G9) EXIT SIGNS TO PROVE THAT IT IS APPROVED UNDER NFPA 101 (UL924)

COASTAL PROVIDED ALL APPROVED DOCUMENTATION WHICH SUPPORTS NFPA 101 UL924

THEREFORE, THE SELF ILLUMINATED SIGNS ARE (APPROVED)

NOTE NEED TO PAY ALL OUTSTANDING FEES

SRI FEES APPLY -- C.B.WOLFF -- 09/14/19



Date:

7/24/2019 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


FIRE FINAL CO DENIED

1-THIS INSPECTION WAS FOR THE INSIDE EXIT SIGNS ONLY - THE CODE STATES THAT THE EXIT SIGNS SHALL BE UL924 NOT 64G9 - THE SIGNS ARE STILL 64G9 WHICH ARE NOT APPROVED BY NFPA 101 7.2

SRI FEES APPLY -- C.B.WOLFF -- 07/24/19



Date:

6/10/2019 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMMENDED FOR 90 DAYS WITH THE CAPTAINS APPROVAL FOR BLDG. 1 SPH4N ONLY

1-GO TO 11805 SW 26TH STREET AND HAVE THE CAPTAIN SIGN THE TCO FORM FROM SURFSIDE
2-REP: BRAD COCHRAN 954 224-0066
3-REASON: NEED TO FINISH THE PROJECT

NOTE: NEED TO PAY ALL FEES BEFORE A TCO WILL BE CONSIDERED

SRI FEES APPLY -- C.B.WOLFF -- 06/10/19



Date:

6/5/2019 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


WALKED WITH JOHN NEWSOME - VICE PRESIDENT OPERATIONS FOR COASTAL CONSTRUCTION SERVICES GROUP

1-DISCUSSED THE FOLLOWING ITEMS
-HANDRAILS BY THE FPL VAULT - ADVISED JOHN THAT IT IS NOT NECESSARY
-DISCUSSED THE TRITIUM EXIT SIGNS BEING USED IN THE PEACOCK AREA AND ADVISED JOHN THAT I WOULD DISCUSS THE SIGNS WITH FIRE ENG.
-DISCUSSED THE CANOPY OUTSIDE OF PEACOCK ALLEY - LOOKED AT THE APPROVED PLANS AND THEY STATE THAT THEY WILL HAVE TO PROVIDE SPRINKLER COVERAGE UNDER THE CANPOYS

SRI FEES APPLY -- C.B.WOLFF -- 06/05/19



Date:

3/7/2019 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

2 - APPROVED PARTIAL


SURF CLUB
9011 COLLINS AVE
PERMIT 2015011603

1-S.W. GROUND FL. AREA OF REFUGE -- OKAY
2-SPH4 BLDG. 1 CORE 3 -- BOH OKAY TO CLOSE CEILING

SRI FEES APPLY -- C.B.WOLFF -- 03/07/19



Date:

2/26/2019 

Inspector:

Anna Falco (AMFALCO) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


disregard in error per lt falco



Date:

2/1/2019 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMMENDED FOR (90) DAYS WITH THE CAPTAINS APPROVAL FOR UNIT 601 BUILDING 1 CORE 1

1-GO TO 11805 SW 26TH STREET AND HAVE THE CAPTAIN SIGN SURFSIDE TCO FORM
2-REP: BRAD COCHRAN 954 224-9066
3-REASON: NEED TO FINISH PROJECT
4-NEED NOTERIZED LETTER ON OWNERS LETTER HEAD FOR THE TCO AND REASON

NOTE: NEED TO PAY ALL OUTSTANDING FEES

SRI FEES APPLY -- C.B.WOLFF -- 02/01/19



Date:

12/17/2018 

Inspector:

James Hough (JGH) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


2015011603
9011 Collins Ave B1 SPH1
Process #M2019003866

TCO recommended with Captains approval. Contact is familiar with TCO process

For final:

1. Finish millwork and wall / ceiling finishes in unit

2. Provide proof of fire alarm and sprinkler finals approved

3. All items from FF Wolffs list from 12/11/18 OK

Sprinkler #2015067872
Fire alarm #2016042208

JG Hough
12/17/18



Date:

12/11/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


S/D S IN UNIT SPH 1 BUILDING 1 CORE ONE -- OKAY



Date:

12/11/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


TCO DENIED

1-SPH1 BUILDING 1 CORE 1
2-NEED TO FINISH SPRINKLERS IN THE UNIT - CAN NOT HAVE THE SPRINKLER HEADS UN-FINISHED PER NFPA 13 8.1.1
2-NEED TO ADD A SPRINKLER HEAD IN THE CLOSET UNDER THE STAIRS IN THE CLOSET PER NFPA 13 8.1.1
3-FIRE RATED DOORS SHALL CLOSE AND LATCH
4-NEED TO RELOCATE S/D BY THE SPIRAL STAIRCASE OR REMOVE DUE TO IT IS NOT NEEDED - SINCE THE WALL HEIGHT HAS BEEN LOWERED AND WILL NOT BE FUNCTIONAL PER NFPA 1 1.14.4

SRI FEES APPLY -- C.B.WOLFF -- 12/11/18



Date:

12/5/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMMENDED FOR 90 DAYS WITH THE CAPTAINS APPROVAL FOR UNIT (SPH4 SOUTH) ONLY BUILDING 1 CORE 2

1-REASON: NEED TO FINISH THE PROJECT
2-REP: BRAD COCHRAN 954 224-9066
3-NOTE: PAY ALL OUTSTANDING FEES

SRI FEES APPLY -- C.B.WOLFF -- 12/04/18



Date:

11/21/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO EXTENSION RECOMMENDED FOR 90 DAYS WITH THE CAPTAINS APPROVAL

1-FORTHE FOLLOWING ITEMS:
-10TH FLOOR,LOBBY,POOL,B2 MAIN ENTRANCE, EXTERIOR TERRACE POOL 1, POOL BATHROOM, HOTEL GYM, RETAIL SHOP, SPA FIDS CLUB, GENERAL MGR. OFFICE, SAFETY DEPOSIT ROOM, CONDO HOTEL LOBBY, MEETING ROOM, LOADING DOCK, POOL KITCHEN AND HISTORICAL BATHROOMS ONLY
2-REP: BRAD COCHRAN (954) 224-9066
3-BRAD IS FAMILAR WITH THE TCO PROCEDURE
4-REASON: NEED TO FINISH THE PROJECT

NOTE: NEED TO PAY ALL OUTSTANDING FEES

C.B.WOLFF -- 11/20/18



Date:

11/21/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


SURF CLUB BUILDING 1 CORE 1

1-UNITS 201,203 AND FLOORS 2-9 EXCEPT UNIT 601
2-REASON: NEED TO FINISH THE PROJECT
3-REP: BRAD COCHRAN (954) 224-9066
4-BRAD IS FAMILAR WITH THE TCO PROCEDURE

NEED TO PAY ALL OUTSTANDING FEES
NOTE: UNIT 201 AND 203 DELETED FROM HEADER

C.B.WOLFF -- 11/20/18



Date:

11/21/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO EXTENSION RECOMMEND FOR 90 DAYS FOR UNITS 1009,1011 ANS SPH6 ONLY WITH THE CAPTAINS APPROVAL

1-REASON: NEED TO FINISH THE PROJECT
2-REP: BRAD COCHRAN (954) 224-9066
3-BRAD IS FAMILAR WITH THE TCO PROCEDURE

NOTE: PAY ALL OUTSTANDING FEES

C.B.WOLFF -- 11/20/18



Date:

11/15/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMMENDED FOR 90 DAYS WITH THE CAPTAINS APPROVAL FOR SOUTH PH2 ONLY

1-REASON: NEED TO FINISH ENTIRE PROJECT
2-REP: BRAD COCHRAN 954 224-9066
3-BRAD IS FAMILAR WITH THE TCO PROCESS

NOTE: NEED TO PAY ALL OUTSTANDING FEES

SRI FEES APPLY -- C.B.WOLFF -- 11/15/18



Date:

11/9/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMENDED FOR 90 DAYS WITH THE CAPTAINS APPROVAL FOR SPH3 AND BASEMENT GARAGES AND PRIVATE GARAGES

1-REASON - NEED TO FINISH ALL OUTSTANDING PENDING ITEMS
2-REP: BRAD COCHRAN (954) 224-9066
3-BRAD IS FAMILAR WITH THE TCO PROCEDURE
4-NEED TO GO TO 11805 SW 26TH STREES AND HAVE THE CAPTAIN SIGN SURFSIDE TCO FORM

NOTE: NEED TO PAY ALL OUTSTANDING FEES

SRI FEES APPLY -- C.B.WOLFF -- 11/08/18



Date:

11/7/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


TCO DENIED

1-NEED TO CORRECT HANDRAILS SO THEY DO NOT EXTEND OUT BUT RETURN TO THE NUEL,FLOOR OR TO THE POST IN PH3 SOUTH BUILDING 1 PER NFPA 101 7.2.2.4.4.9
2-NEED TO REMOVE FENCING IN THE BASEMENT GARAGE AREA FOR TCO PURPOSES

C.B.WOLFF -- 11/07/18



Date:

10/27/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


TCO DENIED

1-BUILDING 1 SOUTH PH3
2-NEED TO CLEAN AND REMOVE ALL CONTRUCTION MATERIAL FROM THE UNIT
3-S/D S IN THE UNIT -- OKAY
4-SPRINKLERS IN THE UNIT OKAY
5-GARAGES IN THE BASEMENT AND CENTER MAIN GARAGE NOT READY
6-NEED TO REPLACE THE PAINTED SPRINKLER HEADS AND PROVIDE THE PAINTED HEADS FOR RE-INSPECTION
7-NEED TO TEST THE CO2 DETECTORS SINCE THEY HAD BEEN DAMAGED WITH MOLD AND MILDEW FRO HURRICANE IRMA

SRI FEES APPLY -- C.B.WOLFF -- 10/27/18



Date:

10/12/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMMENDED FOR 90 DAYS WITH THE CAPTAINS APPROVAL FOR SOUTH PH2 CORE 1 BUILDING 1

1-REASON: FINISH PROJECT
2-REP: BRAD COCHRAN 954 224-9066
3-BRAD IS FAMILAR WITH THE TCO PROCEDURE
4-PAY ALL OUTSTANDING FEES BEFORE A TCO WILL BE CONSIDERED
5-TAKE TCO FORM FROM SURF SIDE TO 11805 SW 26TH ST AND HAVE THE CAPTAIN SIGN THE FORM

SRI FEES APPLY -- C.B.WOLFF -- 10/12/18



Date:

9/7/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


WALKED WITH BRAD AND DENNIS FROM COASTAL CONTRUCTION AND ORLANDO FROM FORT PARTNERS

1-DISCUSSED THE EXIT SIGNS LOCATED AT PEACOCK ALLEY,THE GARAGE AREA,AREA OF REFUGE ON THE SOUTH SIE OF THE PROJECT AND ALSO THE CANOPYS FOR THE RESTAURANT AND TK KITCHEN
2-ALSO DISCUSSED THE CABANAS

SRI FEES APPLY -- C.B.WOLFF -- 09/07/18



Date:

8/10/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


THIS INSPECTION WAS TO DISCUSS THE AREAS THAT STILL NEED TO HAVE INSPECTIONS FROM THE BEGINNING OF THE INSPECTION PROCESS.

ALSO, TO HAVE THE LIFE SAFETY PLANS REVISED TO SHOW THE AREAS THAT ARE NOW GOING TO BE OUT OF THE SCOPE OF WORK FOR COASTAL CONSTRUCTION CORP AND ANOTHER CONSTRUCTION CO. WILL BE TAKING OVER THOSE AREAS

SRI FEES APPLY -- C.B.WOLFF -- 08/10/1



Date:

8/3/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO EXTENSION RECOMMENDED FOR90 DAYS WITH THE CAPTAINS APPROVAL

1- FOR BUILDING 1 FROM (LOBBY TO 10TH FLOOR -- EXCLUDING BASEMENT, CABANA S, PH S AND UNIT 601
2-REASON: NEED TO FINISH THE PROJECT
3-REP: DENNIS JARDINE 786 251-3133
4-DENNIS IS FAMILAR WITH THE TCO PROCEDURE

NEED TO PAY ALL OUTSTANDING FEES

SRI FEES APPLY -- C.B.WOLFF -- 08/02/18



Date:

7/27/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMMENDED FOR THE HOTEL ONLY FOR (90) DYS WITH THE CAPTAINS APPROVAL

1-REASON: FINISH PROJECT AND NEED APPROVED PLANS FOR THE AWNING ON THE EAST SIDE OF THE HOTEL
2-REP: DENNIS JARDINE 786 251-3133

SRI FEES APPLY -- C.B.WOLFF -- 07/26/18



Date:

7/5/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMMENDED FOR BUILDING 2 CORE 1 NORTH PH6 "ONLY" WITH THE CAPTAINS APPROVAL

1-REASON: NEED TO FINISH THE BUILDING
2-REP: JEFF SUTHERLAND 305 308-3694
3-JEFF IS FAMILAR WITH THE TCO PROCEDURE

NOTE: PAY ALL OUTSTANDING FEES

SRI FEES APPLY -- C.B.WOLFF -- 07/05/18



Date:

7/5/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMMENDED FOR BUILDING 2 CORE 1 NORTH PH6 "ONLY" WITH THE CAPTAINS APPROVAL

1-REASON: NEED TO FINISH THE BUILDING
2-REP: JEFF SUTHERLAND 305 308-3694
3-JEFF IS FAMILAR WITH THE TCO PROCEDURE

NOTE: PAY ALL OUTSTANDING FEES

SRI FEES APPLY -- C.B.WOLFF -- 07/05/18



Date:

7/5/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMMENDED FOR BUILDING 2 CORE 1 NORTH PH6 "ONLY" WITH THE CAPTAINS APPROVAL

1-REASON: NEED TO FINISH THE BUILDING
2-REP: JEFF SUTHERLAND 305 308-3694
3-JEFF IS FAMILAR WITH THE TCO PROCEDURE

NOTE: PAY ALL OUTSTANDING FEES

SRI FEES APPLY -- C.B.WOLFF -- 07/05/18



Date:

7/5/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMMENDED FOR BUILDING 2 CORE 1 NORTH PH6 "ONLY" WITH THE CAPTAINS APPROVAL

1-REASON: NEED TO FINISH THE BUILDING
2-REP: JEFF SUTHERLAND 305 308-3694
3-JEFF IS FAMILAR WITH THE TCO PROCEDURE

NOTE: PAY ALL OUTSTANDING FEES

SRI FEES APPLY -- C.B.WOLFF -- 07/05/18



Date:

7/5/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMMENDED FOR BUILDING 2 CORE 1 NORTH PH6 "ONLY" WITH THE CAPTAINS APPROVAL

1-REASON: NEED TO FINISH THE BUILDING
2-REP: JEFF SUTHERLAND 305 308-3694
3-JEFF IS FAMILAR WITH THE TCO PROCEDURE

NOTE: PAY ALL OUTSTANDING FEES

SRI FEES APPLY -- C.B.WOLFF -- 07/05/18



Date:

6/29/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMMENDED FOR 90 DAYS FOR BUILDING 1 CORE 1 UNITS 201 AND 301 ONLY WITH THE CAPTAINS APPROVAL

1-REASON - NEED TO FINISH THE PROJECT
2-REP - JEFF SUTHERLAND 305 308-3694
JEFF IS FAMILAR WITH THE TCO PROCEDURE

NOTE - PAY ALL OUTSTANDING FEES

STI FEES APPLY -- C.B.WOLFF -- 06/28/18



Date:

6/22/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMMENDED FOR PH7 AND BUILDING 1 BASEMENT @ PRIVATE GARAGES ONLY FOR 90 DAYS WITH THE CAPTAINS APPROVAL

1-REASON: NEED TO FINISH POJECT
2-REP: JEFF SUTHERLANS 305 308-3694
3-JEFF IS FAMILAR WITH THE TCO PROCEDURE
4-NEED TO PAY ALL OUTSTANDING FEES

SRI FEES APPLY -- C.B.WOLFF -- 06/22/18



Date:

6/19/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


TCO DENIED -- PH7
BUILDING 1 CORE 3

1-NEED TO REMOVE EXIT LIGHT IN ELEVATOR LOBBY IN THE BASEMENT LEADING TO THE GARAGE PER NFPA 1 1.14.4
2-NEED TO REMOVE ACCESS CONTOL OR PROVIDE PLANS AND PERMIT IN ELEVATOR LOBBY CORE 3 BUILDING 1
3-CORE SHALL BE IN TACK FOR ALL BUILD OUTS

C.B.WOLFF -- 06/19/18



Date:

6/7/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMMENDED FOR BUILDING 1 CORE 3 SOUTH PH5 FOR 90 DAYS "ONLY"

1-NEED THE CAPTAINS APPROVAL FOR THE TCO RECOMMENDATION
2-GO TO 11805 SW 26TH STREET AND HAVE THE CAPTAIN SIGN THE SURFSIDE TCO FORM

REASON: FINISH THE BUILDING

REP: JEFF SUTHERLAND 305 308-3694

NOTE: PAY ALL OUTSTANDING FEES -- SRI FEES APPLY -- C.B.WOLFF -- 06/07/18



Date:

5/31/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


TCO DENIED

1-TCO DENIED FOR BUILDING 1 BASEMENT DUE TO ON GOING CONSTRUCTION FOR TK KITCHEN IN THE BASEMENT PER NFPA 1 1.14.4

BUILDING 1 CORE 1

1-UNITS 201 AND 301 UNIT S/D S - OKAY
2-UNITS 201 AND 301 FIRE ALARM SPEAKERS - OKAY

SRI FEES APPLY -- C.B.WOLFF -- 05/31/18



Date:

5/10/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


TCO DENIED FOR BUILDING 1 GARAGE BASEMENT

1-AUTOMATIC GATES ARE NOT INSTALLED AT THIS TIME AND THE GATES ARE MANUAL - FIRE DEPARTMENT PERSONNEL NEEDS ACCESS TO THE GARAGE AREA
2-NEED CLEARANCE SIGNS FOR ALL GARAGE ENTRANCES
3-ALL CORES AS PREVIOUSLY DISCUSSED NEED TO BE COMPLETE UP TO THE ROOF
4-THERE IS STILL GOING TO BE CONSTRUCTION PERSONNEL MIXING WITH UNIT OWNERS

SRI FEES APPLY -- C.B.WOLFF -- 05/10/18



Date:

5/3/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


STAIR TABLE FOR NEW STAIRS NFPA 101 7.2.2.2.2.1.1 -- 4 TO 7 INCHES BY 11 WHEN STAIRS ARE GREATER THAN 21 INCHES



Date:

5/3/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


TCO DENIED BUILDING 1 CORE 3 SOUTH PH7

1-NEED TO HAVE STAIRS UNIFORM NFPA101 7.2.2.3.6
2-HANDRAILS SHALL BE 34 TO 38 INCHES PER NFPA 101 7.2.2.4.4
3-NEED TO HAVE GUARDRAILS ON CIRCULAR STAIRS IN THE UNIT DUE TO THE FACT THAT THEY ARE GREATER THAN 30 INCHES FROM THE GROUND ON THE OUTSIDE PER NFPA 101 7.2.2.4.5
4-PICKETS CAN NOT BE MOR THAN 4 INCHES PER NFPA 101 7.2.2.4.5.3
5-NEED TO PROVIDE HANDRAILS ON THE POOL DECK PER NFPA 101 7.2.2.4.4


SRI FEES APPLY -- C.B.WOLFF -- 05/03/18



Date:

5/3/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


TCO DENIED BUILDING 1 CORE 3 SOUTH PH7

1-NEED TO HAVE STAIRS UNIFORM NFPA101 7.2.2.3.6
2-HANDRAILS SHALL BE 34 TO 38 INCHES PER NFPA 101 7.2.2.4.4
3-NEED TO HAVE GUARDRAILS ON CIRCULAR STAIRS IN THE UNIT DUE TO THE FACT THAT THEY ARE GREATER THAN 30 INCHES FROM THE GROUND ON THE OUTSIDE PER NFPA 101 7.2.2.4.5
4-PICKETS CAN NOT BE MOR THAN 4 INCHES PER NFPA 101 7.2.2.4.5.3
5-NEED TO PROVIDE HANDRAILS ON THE POOL DECK PER NFPA 101 7.2.2.4.4


SRI FEES APPLY -- C.B.WOLFF -- 05/03/18



Date:

4/27/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMMENDED FOR BUILDING 2 CORE 1 NORTH PH4 FOR 90 DAYS WITH THE CAPTAINS APPROVAL

1-REASON - NEED TO FINISH THE PROJECT
2-REP -- JEFF SUTHERLAND 305 308-3694
3-JEFF IS FAMILAR WITH THE TCO PROCEDURE

NOTE - PAY ALL OUTSTANDING FEES

SRI FEES APPLY -- C.B.WOLFF -- 04/27/18



Date:

4/19/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


TCO DENIED
FOR PH6 BUILDING 2

1-NEED TO HAVE STAIRS UNIFORM - CAN NOT HAVE A STEP GREATER THAN 7 INCHES - THE LAST STEP IS 9 INCHES PER NFPA 101 7.2.2
2-NEED TO HAVE AT LEAST ONE HAND HANDRAIL ON STEPS FOR DWELLING UNITS PER NFPA 101 7.2.2.4.4
3-HANDRAILS SHALL BE FROM 34 TO 38 INCHES PER NFPA 101 7.2.2

SRI FEES APPLY -- C.B.WOLFF -- 04/19/18



Date:

4/12/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


TCO DENIED

1-POOL ACCESS DOOR FROM POOL KITCHEN - IN-OP NEED TO BE REPAIRED AND MUST STAY CLOSED PER NFPA 1 1.14.4
2-NEED TO REPLACE RUSTY SPRINKLER HEADS AT CABANA S AND POOL ACCESS
3-NO TCO DUE TO CORES BUILDING 1 NOT FINISHED
4-NEED AUTOMATIC KEY SWITCH FOR AUTOMATIC GATES TO GARAGE
5-NORTH CONSTRUCTION AREA NEEDS BARRICADE BACK IN PLACE
6-NEED TO PROVIDE HEIGHT SIGNS FOR GARAGE - MUST BE LOCATED OUTSIDE GARAGE NOT INSIDE
7-PH4 AND PH6 - S/D S -- OKAY - BUILDING 2 CORE 1
8-PH4 AND PH6 - SPEAKERS - OKAY - BUILDING 2 CORE 1

SRI FEES APPLY -- C.B.WOLFF -- 04/12/18



Date:

4/5/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


NEED TO HAVE 18 INCHES FROM A SPRINKLER HEAD IN THE CLOSETS PER NFPA 13



Date:

4/5/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


TCO DENIED
BUILDING 2 CORE 1 PH 4
PERMIT 2015011603
SURF CLUB

1-NEED TO ADD SPRINKLER HEAD IN A/C CLOSET PER NFPA 13
2-NEED TO FINISH POOL DECK PER NFPA 1 1.14.4
3-NEED TO TEST S/D S IN THE UNIT PER NFPA 1 1.14.4
4-NEED TO TEST SPEAKERS IN THE UNIT PER NFPA 72
5-HANDRAILS SHALL BE 34 TO 38 INC
6-HANDRAILS SHALL BE CONTINOUSLY GRASPABLE PER NFPA 101 7.2.2.4.4.8
7-NEED TO ADD SPRINKLER COVERAGE IN MENS SPA AREA PER NFPA 13 8.1.1
8-NEED TO REMOVE SPRINKLER CAPS IN ALL A/C CLOSETS PER NFPA 13
9-NEED TO CAULKING FROM SPRNKLER ESCUTCHEON PLATES PER NFPA 13

SRI FEES APPLY -- C.B.WOLFF -- 04/05/18



Date:

3/29/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMMENDED WITH THE CAPTAINS APPROVAL FOR 90 DAYS FOR BUILDING 2 NORTH TOWER CORE3 PH1 ONLY

1-MUST MAINTAIN CORE 3 FROM LOBBY TO ROOF -- IF FOR ANY REASON THE CORE IS COMPRISED THE TCO IS "VOID"
2-PAY ALL OUTSTANDING FEES
3-REP: JEFF SUTHERLAND 305 308-3694
4-REASON : FINISH THE NORTH TOWER AND SOUTH TOWERS,CABANA S AND GARAGE

SRI FEES APPLY -- C.B.WOLFF -- 03/29/18



Date:

3/29/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMMENDED WITH THE CAPTAINS APPROVAL FOR 90 DAYS FOR BUILDING 2 NORTH TOWER CORE3 PH1 ONLY

1-MUST MAINTAIN CORE 3 FROM LOBBY TO ROOF -- IF FOR ANY REASON THE CORE IS COMPRISED THE TCO IS "VOID"
2-PAY ALL OUTSTANDING FEES
3-REP: JEFF SUTHERLAND 305 308-3694
4-REASON : FINISH THE NORTH TOWER AND SOUTH TOWERS,CABANA S AND GARAGE

SRI FEES APPLY -- C.B.WOLFF -- 03/29/18



Date:

3/23/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


TCO DENIED

1-PH 1 ROOF CORE DOOR - DOOR DOES NOT CLOSE AND LATCH
2-HANDRAIL IN STAIR SHALL BE CONTINOUS
3-PH 5 ELEVATOR VESTIBULE NOT FINISHED
4-ELEVATOR VESTIBULE NEEDS SCREWS FOR DOOR
5-OKAY TO PROGRAM DRAPES AND SOFT GOODS - NO OCCUPANCY AT THIS TIME

SRI FEES APPLY -- C.B.WOLFF -- 03/2/18



Date:

3/14/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


TCO DENIED

1-MEET WITH ORLANDO CARRILLO FROM FORT PARTNERS
2-MEET WITH JOHN NEWSOME COASTAL
3-JEFF SUTHERLAND COASTAL
4-BILL FORD COASTAL
5-SPOKE ABOUT TCO PROCEDURES FOR BUILDING 1 AND 2

NOTE: EXPLAINED TO ORLANDO THAT HE NEEDS TO KEEP ALL LIFE SAFETY ITEMS UP TO CODE AND CAN NOT COMPRISE THE INTEGRITY OF THE CORRIDORS OR THE SMOKE CONTROL - ADVISED THE OWNERS REP (ORLAND) THAT THE POOL DECK MUST BE PUT BACK TOGETHER SINCE HE DID NOT HIRE A CHANGE OF CONTRACTOR FOR THE BUILDOUTS

SRI FEES APPLY -- C.BWOLFF -- 03/13/18



Date:

3/14/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


TCO DENIED

1-MEET WITH ORLANDO CARRILLO FROM FORT PARTNERS
2-MEET WITH JOHN NEWSOME COASTAL
3-JEFF SUTHERLAND COASTAL
4-BILL FORD COASTAL
5-SPOKE ABOUT TCO PROCEDURES FOR BUILDING 1 AND 2

NOTE: EXPLAINED TO ORLANDO THAT HE NEEDS TO KEEP ALL LIFE SAFETY ITEMS UP TO CODE AND CAN NOT COMPRISE THE INTEGRITY OF THE CORRIDORS OR THE SMOKE CONTROL - ADVISED THE OWNERS REP (ORLAND) THAT THE POOL DECK MUST BE PUT BACK TOGETHER SINCE HE DID NOT HIRE A CHANGE OF CONTRACTOR FOR THE BUILDOUTS

SRI FEES APPLY -- C.BWOLFF -- 03/13/18



Date:

2/27/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


CONTINUED WALKING BUILDING 1 AND 2 TO DISCUSS TCO PROCEDURES

1-ADVISED COSTAL PERSONNELL THAT NO MORE TCO S OR EXTENSIONS WILL BE GIVEN UNTIL CONSTRUCTION OF THE PH UNITS,CABANAS,ROOF POOL DECKS,PERSONAL GARAGES AND BUILDING 1 AND 2 BEGIN CONSTRUCTION TO FINISH THE PROJECT
2-NEED TO CLOSE OUT THE BDA SYSTEM PERMIT 040 CAT.
3-DISCUSSED LOADING DOCK GUARD RAILS - OKAY TO USE CHAIN (REMOVABLE) FOR 5 FOOT DROP OFF - PLANS TO SOW THE LOADING DOCK AS IS

SRI FEES APPLY -- C.B.WOLFF -- 02/27/18



Date:

2/7/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


TCO INSPECTION DENIED

1-SECURITY PERSONNEL CAN NOT OPERATE THE FACP UNTIL THE CONSTRUCTION IS DON IN THE BUILDING AND THE BASEMENT ( GARAGE LEVEL) IS COMPLETED AND APPROVED PER NFPA 1 1.14.4
2-NEED RUNNERS AND MONITOR AGGREEMENT ALON WITH FIRE ALARM PERMIT BEING CLOSED OUT
3-THERE WILL NOT BE ANYMORE TCO S OR TCO EXTENSIONS UNTIL THE ABOVE HAS BEEN CORRECTED

SRI FEES APPLY -- C.B.WOLFF -- 02/06/18



Date:

1/31/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


DISCUSSED TCO EXTENSION PROCEDURES FOR BUILDING 2

1-ONCE BARRIERS ARE UP IN THE NORTH CABANA AREA BOTH TOP AND BOTTOM,BASEMENT GARAGE AT CORES 1,2 & 3 AND NEED TO INSTALL BARRIER FOR NO ACCESS FROM FLOOR 10 THROUGH THE POOL ROOF
2-THEN A TCO EXTENSION WILL BE RECOMMENDED WITH THE CAPTAINS APPROVAL
3-NEED GUARDS IN ALL (3) CORES AT LEVEL 10 STAIRWELL

SRI FEES APPLY -- C.B.WOLFF -- 01/30/18



Date:

1/24/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


TCO DENIED

1-NEED TO PROVIDE CONES AT THE ENTRANCE TO THE NORTH GARAGE TO PREVENT CARS FROM USING THE GARAGE PER NFPA 1 1.14.4
2-NEED TO LOCK PRIVATE GARAGES AT THE END OF THE DAY SO FOUR SEASONS PERSONELL ARE UNABLE TO PASS INTO THE CONSTRUCTION AREA PER NFPA 1 1.14.4
3-NEED TO PROVID A BARRIER FROM THE GARAGES TO PREVENT FOUR SEASONS PERSONELL FROM THE GARAGE AREA - THIS AREA DOES NOT HAVE A TCO
4-NEED TO UPDATE THE FIRE ALARM LOG BOOK IN THE FIRE COMMAND ROOM
5-NEED TO PROVIDE AN ADDRESS ON THE FIRE ALARM BOOK
6-NEED TO PROVIDE A COMPLETE FIRE ALARM BOOK PER NFPA 72

SRI FEES APPLY -- C.B.WOLFF -- 01/23/18



Date:

1/18/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMMENDED FOR UNITS 1001,1003,1005 AND 1007 BUILDING 1 CORES 1 AND 2 ONLY FOR 90 DAYS

1-REASON: NEED TO FINISH BUILDING 1
2-REP: JEFF SUTHERLAND 305 308-3694
3-NEED TO BRING SURFISDE TCO FORM TO FIRE ENG. AND HAVE THE APTAIN SIGN THE TCO FORM

NOTE: NEED TO PAY ALL OUTSTANDING FEES

SRI FEES APPLY -- C.B.WOLFF -- 01/18/18



Date:

1/11/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO EXTENSION RECOMMENDED FOR THE HOTEL FROM THE BASEMENT OFFICES,BASEMENT KITCHEN AND LOBBY TO THE ROOF ONLY

1-THIS TCO IS RECOMMENDED FOR(90) DAYS ONLY
2-REASON: ON GOING CONSTRUCTION FROM THE T.K.TERRACE
3-JEFF SUTHERLAND IS FAMILAR WITH THE TCO PROCESS

REP: JEFF SUTHERLAND 305 308-3694

NOTE: PAY ALL OUTSTANDING FEES BEFORE A TCO WILL BE CONSIDERED
NOTE: BRING TCO FORM FROM THE TOWN OF SURFSIDE

SRI FEES APPLY -- C.B.WOLFF -- 01/11/18



Date:

1/11/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO EXTENSION RECOMMENDED FOR THE HOTEL FROM THE BASEMENT OFFICES,BASEMENT KITCHEN AND LOBBY TO THE ROOF ONLY

1-THIS TCO IS RECOMMENDED FOR(90) DAYS ONLY
2-REASON: ON GOING CONSTRUCTION FROM THE T.K.TERRACE
3-JEFF SUTHERLAND IS FAMILAR WITH THE TCO PROCESS

REP: JEFF SUTHERLAND 305 308-3694

NOTE: PAY ALL OUTSTANDING FEES BEFORE A TCO WILL BE CONSIDERED
NOTE: BRING TCO FORM FROM THE TOWN OF SURFSIDE

SRI FEES APPLY -- C.B.WOLFF -- 01/11/18



Date:

1/4/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


DISCUSSED WITH JEFF SUTHERLAND THE PROCEDURE TO MOVE FORWARD FOR GETING A TCO EXTENSION AND REMOVING AREAS THAT ARE NOW UNDER CONSTRUCTION AND WILL NOT BE GRANTED A TCO EXTENSION. ALSO, DISCUSSED WRITING A HARDSHIP LETTER FOR AREAS THAT HAV NOT BEEN COMPLETED FROM THE ORGINAL TCO S

SRI FEES APPLY -- C.B.WOLFF -- 01/04/17



Date:

1/3/2018 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

2 - APPROVED PARTIAL


SURF CLUB
PERMIT 2015011603 LIFE SAFETY

1-PARTIAL APPROVAL
2-HOTEL SERVICE ELEVATOR - OKAY
3-NEED TO ADJUST DOOR CLOSER ELECTRIAL ROOM IN THE HOTEL SERVICE ELEVATOR
4-HOTEL EAST SIDE SIGNAGE STAIR 8 - OKAY

SRI FEES APPLY -- C.B.WOLFF -- 01/02/18



Date:

12/27/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


TCO DENIED

1-AREAS IDENTIFIED ON 12/19/17 STILL HAVE NOT BEEN CORRECTED
2-AREAS CORRECTED
BUILDING 2 CORE 1 FLOORS 10-LOBBY - FIRE RATED LABELS AND UNIT SIGNAGE - OKAY
BUILDING 2 CORE 2 FLOORS 10-LOBBY - FIRE RATED LABELS AND UNIT SIGNAGE - OKAY
BUILDING 2 CORE 3 FLOORS 10-LOBBY - FIRE RATED LABELS AND UNIT SIGNAGE - OKAY
HOTEL - AREA OF REFUGE SIGNAGE - OKAY

SRI FEES APPLY -- C.B.WOLFF -- 12/26/17



Date:

12/20/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


TCO EXTENSION DENIED1

BUILDING 2 CORE 1 AND PEACOCK ALLEY HOTEL

1-NEED TO FINISH STAIRS BY THE NORTH STAIRS BY FIRE PUMP ROOM
2-NEED DOOR CLOSER ELECTRIC ROOM BY SERVICE ELEVATOR CORE 1
3-HAVE CERT. FOR ELEVATOR VISIBLE
4-REMOVE STORAGE FROM ALL ELECTRIC AND MECHANIAL ROOMS
5-BUILDING 2 BOH NEED SIGNAGE FOR UNITS AND STAIRWELLS
6-NEED ESCUTCHEON PLATES FOR BOH THROUGHOUT
7-NEED TO HAVE ALL PH UNITS FOR BUILDING 2 COMPLETE
8-NEED TO REMOVE STORAGE FROM STAIRWELLS
9-NEED TO REMOVE OFFICE IN CONDO HOTEL UNDER SPA STAIR
10-NEED TO PATCH SERVICE ELEVATOR 10 SPRINKLER IT CLOSET
11-NEED TO FINISH ROOF IT CLOSET SPRINKLER HEAD FINISH
12-ROOF ELECTRIC NEED DOOR CLOSER AND FIRE CAULK
13-12TH FL B2 8A TAG AND SERVICE FIRE EXTINGUISHER
14-NEED TO RELOCATE AREA OF REFUGE SIGN IN OTEL
15-GYM PANIC HARDWARE NORTH STAIR 7 CHANGE TO FIRE EXIT HARDWARE
16-NEED TO PROVIDE A OCCUPANT LOAD SIGN FOR THE GYM
17-NEED TO REPAIR PRIVATE GARAGES IN BASEMENT DUE TO CONSTRUCTION
18-TCO FOR BASEMENT - DENIED
19-NEED TO REMOVE STORAGE IN NORTH CABANA S MECHANIAL ROOM
20-NEED HANDRAIL BOTH SIDES NORTH CABANA
21-NEED EXIT SIGNAGE FOR THE NORTH CABANA 2ND LEVEL
22-NEED TO RAISE AWNING NORTH CABANA ABOVE THE SPRINKLER SYSTEM FOR SPRINKLER COVERAGE

SRI FEES APPLY -- C.B.WOLFF -- 12/19/17



Date:

12/16/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


DISCUSSED WITH JEFF SUTHERLAND THE SCHEDULE FOR THE REMIANING UNITS TO TCO AND THE TIME FRAME FOR THEM.

SRI FEES APPLY -- C.B.WOLFF -- 12/16/17



Date:

12/14/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

2 - APPROVED PARTIAL


SURF CLUB
PERMIT 2015011603 LIFE SAFETY

1-THIS INSPECTION WAS FOR HAND RAILS AND GURAD RAILS ONLY
2-BUILDING 1 CORE 1
-UNITS 1001 AND 1003 - OKAY

BUILDING 1 CORE 2
1-UNITS 1005 AND 1007 - OKAY

SRI FEES APPLY -- C.B.WOLFF -- 12/14/17



Date:

12/9/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMMENDED FOR BUILDING 1 CORE 1 FLOORS 2-9 ONLY FOR 90 DAYS WITH THE CAPTAINS APPROVAL

1-NEED TO FINISH THE BUILDNG FIRE FINALS AND SPRINKLERS
2-REP: JEFF SUTHERLAND 305 308-3694
3-JEFF IS FAMILAR WITH THE TCO PROCESS

NOTE: NEED TO PAY ALL OUTSTANDING FEES BEFORE A RECOMMENDATION WILL BE CONSIDERED

C.B.WOLFF -- 12/09/17



Date:

12/1/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


TCO IS FOR THE FOLLOWING ITEMS ONLY


BUILDING 1 CORE 3
1-PH7,PH6,PH5,PH4,1009,1010 AND 1011 ONLY
3-THIS TCO IS GOOD FOR 90 DAYS ONLY

C.B.WOLFF -- 11/30/17



Date:

12/1/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


TCO IS FOR THE FOLLOWING ITEMS ONLY


BUILDING 1 CORE 3
1-PH7,PH6,PH5,PH4,1009,1010 AND 1011 ONLY
3-THIS TCO IS GOOD FOR 90 DAYS ONLY

C.B.WOLFF -- 11/30/17



Date:

12/1/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMMENDED

1-TCO RECOMMENDED FOR 90 DAYS WITH THE CAPTAINS APPROVAL
2-REASON FOR THE TCO - NEED TO FINISH PROJECT AND CLOSE OUT PERMITS
3-REP: JEFF SUTHERLAND (305) 308-3694

NOTE: NEED TO PAY ALL OUTSTANDING FEES
NOTE: JEFF SUTHERLAND IS FAMILAR WITH THE TCO PROCEDURE

SRI FEES APPLY -- C.B.WOLFF -- 11/30/17



Date:

11/29/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

2 - APPROVED PARTIAL


SURF CLUB
LIFE SAFETY 2015011603

BUILDING 1 CORE 3

1-UNITS PH5,PH7,PH6,PH4,1011,1010 AND 1009 - SPEAKERS AND S/D S - OKAY

BUILDING 1 CORE 2

1-UNITS 908 - S/D S - OKAY

C.B.WOLFF -- 11/28/17



Date:

11/18/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

2 - APPROVED PARTIAL


SURF CLUB
PERMIT 2015011603 LIFE SAFETY

1-INSPECTION WAS FOR RE-INSPECTION OF THE INSPECTION CONDUCTED ON 11/15/17 -- ALL ITEMS OKAY
2-PH5 DOOR CLOSED AND LATCHES -- OKAY
3-FLOOR 5 AND 9 SPRINKLER PIPE IN STAIRWELL - OKAY
BUILDING 1

1-UNIT 905 AND 906 SPRINKLERS OKAY

SRI FEES APPLY -- C.B.WOLFF -- 11/18/17



Date:

11/16/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMMENDED FOR BUILDING 1 CORE 3 FLOORS 2-9 ONLY

1-TCO RECOMMENDED FOR 90 DAYS ONLY
2-GO TO 11805 SW 24TH STREET AND HAVE CAPTAIN SIGN THE TCO CARD FROM SURFSIDE
3-REASON IS TO FINISH THE PROJECT
REP: JEFF SUTHERLAND 305 308-3694

C.B.WOLFF -- 11/16/17



Date:

11/15/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


SURF CLUB
BUILDING 1 CORE 2
2015011603 LIFE SAFETY

1-DOORS IN THE BOH ROOF TO FLOOR 2
2-FLOORS 12,11,8,7,6,5,4,3 AND 2 -- OKAY
3-ROOF NO LABELS
4-FLOOR 10 TRASH CHUTE
5-FLOOR 9 STAIR B1-S03

C.B.WOLFF -- 11/14/17



Date:

11/15/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

2 - APPROVED PARTIAL


SURF CLUB
2015011603 LIFE SAFETY

BUILDING 1 CORE 2 UNIT SMOKE DETECTORS

1-UNIT 905,906,907,805,806,810/811,708,505 AND 407 -- OKAY

SRI FEES APPLY -- C.B.WOLFF -- 11/14/17



Date:

11/14/2017 

Inspector:

John Molnar (MOLNAR) 

Type:

209 - FIRE FINAL

Status:

2 - APPROVED PARTIAL


2015011603
Surf Club
1) Unit 711 all smoke/CO alarms installed per plans and tested OK
2) Unit 811 all smoke/CO alarms installed per plans and tested ok



Date:

11/3/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

2 - APPROVED PARTIAL


SURF CLUB
BUILDING 1 CORE 2
HANDRAILS/GUARDRAILS FOR FLOORS 9-3

1-HANDRAILS 9-3 - OKAY
2-GUARDRAILS 9-3 - OKAY

SRI FEES APPLY -- C.B.WOLFF -- 11/02/17



Date:

11/1/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

2 - APPROVED PARTIAL


SURF CLUB
BUILDING 1 CORE 2
PERMIT 2015011603

BUILDING 1 CORE 2 SMOKE DETECTORS

1-UNITS 807,705,706,707,605,606,506,507,405,406,307 -- OKAY
2-UNIT 305 - BAD

BUILDING 1 CORE 2 SPEAKERS

1-UNITS 807,705,706,707,605,606,506,507,405,406,305 AND 307 - OKAY

SRI FEES APPLY -- C.B.WOLFF -- 11/01/17



Date:

10/26/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

2 - APPROVED PARTIAL


NOTE:COMMENTS ON 10/16/17 ITEM (4) CORRECTION

-THE 1ST TCO FOR BUILDING 1 CORE 1 WAS FROM THE LOBBY TO THE 9TH FLOOR AND APPROVED PER THE AGREEMENT WITH OWNERSHIP AND MDFR


SURF CLUB
BUILDING 1 CORE 3

1-UNIT 910,809,709 AND 710 - S/D S - OKAY

BUILDING 1 CORE 2

1- UNIT 205 AND 207 - S/D S - OKAY

SRI FEES APPLY -- C.B.WOLGG -- 10/26/17



Date:

10/26/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

2 - APPROVED PARTIAL


NOTE:COMMENTS ON 10/16/17 ITEM (4) CORRECTION

-THE 1ST TCO FOR BUILDING 1 CORE 1 WAS FROM THE LOBBY TO THE 9TH FLOOR AND APPROVED PER THE AGREEMENT WITH OWNERSHIP AND MDFR


SURF CLUB
BUILDING 1 CORE 3

1-UNIT 910,809,709 AND 710 - S/D S - OKAY

BUILDING 1 CORE 2

1- UNIT 205 AND 207 - S/D S - OKAY

SRI FEES APPLY -- C.B.WOLGG -- 10/26/17



Date:

10/16/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


DENIAL
2-THERE WAS A MEETING WITH SURF CLUB OWNERSHIP AND (MDFR) CONCERNING BUILDING 1 AND HOW TO PROCEDE WITH SAID BUILDING.
2-OWNERSHIP AND MDFR CAME TO AN AGREEMENT THAT WOULD ALLOW BUILDING (1) TO BE BUILT TO THE 9TH FLOOR ONLY FOR TCO PURPOSES.
3-FLOORS 10-12 HAVE HAD THE SPRINKLER SYSTEM AND THE FIRE ALARM DEVICES REMOVED PER THE AGREEMENT .
4-THE 1ST TCO FOR BUILDING (1) WAS TCO DENIED

1-REASON FOR CORE 1 WAS TO THE 9TH FLOOR AS AGREED UPON.
5-OWNERSHIP HAS NOW DECIDED TO ONLY FOR BUILDING 1 CORE 3 TO BUILD ONLY TO THE 6TH FLOOR WHICH IS NOT PART OF THE AGREEMENT.
6-IT IS THIS INSPECTORS RECOMMENDATION THAT THE TCO BE DENIED DUE TO OWNERSHIP HAS NOT HONORED THE AGREMENT BETWEEN MDFR AND THEMSELVES.



Date:

10/12/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

2 - APPROVED PARTIAL


SURF CLUB
PERMIT # 2015011603

BUILDING 1 CORE 3 FLOORS 12-2

1-DOORS CLOSE AND LATCH
2-TRASH CHUTE DOORS CLOSE AND LATCH
3-STAIRWELL DOORS CLOSE AND LATCH
4-UNIT DOORS CLOSE AND LATCH
5-FIRE EXTINGUISHERS ARE ON FLOORS 12-2
6-STAIRWELL STANDPIPE FLOORS 8-12 DO NOT HAVE PRESSURE OIN THEM
7-BOH SPRINKLERS 12-2 - OKAY
8-GUARD RAIL AT WATER FEATURE AT (TK TERRACE) NEEDS TO HAVE A GUARDRAIL BUILT TO CODE WITH PICKETS ALSO TO CODE PER NFPA 1 1.14.4

SRI FEES APPLY -- C.B.WOLFF -- 10/12/17



Date:

10/11/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

2 - APPROVED PARTIAL


THIS INSPECTION WAS TO CONTINUE WALKING BUILDING 1 CORE 3 FOR TCO PURPOSES

SRI FEES APPLY -- C.B.WOLFF -- 10/10/17



Date:

10/7/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


SURF CLUB
PERMIT #2015011603
BUILDING 1 CORE 3 BOH

1-NEED DOOR LABELS ON ROOF
2-STAIRS ON ROOF THAT ARE LESS THAN 21 INCHES TREAD MUST BE 13 INCHES
3-NEED TO HAVE A 2 INCH CONTRASTING STRIPE ON NOSE OF TREAD FOR STAIR LESS THATN 21 INCHES
4-NEED TO HAVE SPRINKLER CAPS FOR HOSE VALVES
5-12TH FLOOR FAILS
6-NEED FIRE EXTINGUISHERS THROUGHOUT
7-STAIR B1-SO2 NEED LABEL 12TH FLOOR
8-PH 5 - DOES NOT CLOSE AND LATCH
9-FLOR 11 NEED TO REPAIR EXIT LIGHT
10-FLOOR 11 TRASH CHUTE NEEDS LABEL
11-PH4 NEEDS TO HAVE A DOOR LABEL
12-B1-SO1 STAIR 10TH FLOOR DOES NOT CLOSE AND LATCH
13-FLOOR 9 B1-SO2 NEEDS DOOR LABEL
14-FLOOR 9 B1-SO1 NEEDS DOOR LABEL
15-UNIT 911 AND 910 NEEDS DOOR LABEL
16-8TH FLOOR NEED DOOR LABELS
17-7TH FLOOR NEED DOOR LABELS
18-STAIR B1-SO1 7TH FLOOR DOES NOT CLOSE AND LATCH
19-6TH FLOOR NEEDS UNIT NUMBERS
20-UNIT 309 DOES NOT CLOSE AND LATCH
21-B1-SO1 3RD AND 2ND FLOORS DO NOT CLOSE AND LATCH

SRI FEES APPLY -- C.B.WOLFF -- 10/07/17



Date:

10/7/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


SURF CLUB
PERMIT #2015011603
BUILDING 1 CORE 3 BOH

1-NEED DOOR LABELS ON ROOF
2-STAIRS ON ROOF THAT ARE LESS THAN 21 INCHES TREAD MUST BE 13 INCHES
3-NEED TO HAVE A 2 INCH CONTRASTING STRIPE ON NOSE OF TREAD FOR STAIR LESS THATN 21 INCHES
4-NEED TO HAVE SPRINKLER CAPS FOR HOSE VALVES
5-12TH FLOOR FAILS
6-NEED FIRE EXTINGUISHERS THROUGHOUT
7-STAIR B1-SO2 NEED LABEL 12TH FLOOR
8-PH 5 - DOES NOT CLOSE AND LATCH
9-FLOR 11 NEED TO REPAIR EXIT LIGHT
10-FLOOR 11 TRASH CHUTE NEEDS LABEL
11-PH4 NEEDS TO HAVE A DOOR LABEL
12-B1-SO1 STAIR 10TH FLOOR DOES NOT CLOSE AND LATCH
13-FLOOR 9 B1-SO2 NEEDS DOOR LABEL
14-FLOOR 9 B1-SO1 NEEDS DOOR LABEL
15-UNIT 911 AND 910 NEEDS DOOR LABEL
16-8TH FLOOR NEED DOOR LABELS
17-7TH FLOOR NEED DOOR LABELS
18-STAIR B1-SO1 7TH FLOOR DOES NOT CLOSE AND LATCH
19-6TH FLOOR NEEDS UNIT NUMBERS
20-UNIT 309 DOES NOT CLOSE AND LATCH
21-B1-SO1 3RD AND 2ND FLOORS DO NOT CLOSE AND LATCH

SRI FEES APPLY -- C.B.WOLFF -- 10/07/17



Date:

10/4/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


SURF CLUB
PERMIT #2015011603
BUILDING 1 CORE 3

HAND/GUARD RAIL FLOORS 10-2 ON BALCONY
1-FLOORS 10-2 - OKAY
EXCEPT: UNIT 1009 - BROKEN GLASS ON BALCONY

SRI FEES APPLY -- C.B.WOLFF -- 10/03/17



Date:

9/27/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


SURF CLUB

BUILDING 1 CORE 3

1-UNITS 709,609,611,612 AND 610 - F/A SPEAKERS OKAY
2-UNITS 709,710,610,612,609,611 AND 511 S/D S - OKAY

BUILDING 1 CORE 2

1-UNITS 406 AND 305 S/D S - OKAY

SRI FEES APPLY -- C.B.WOLFF -- 09/27/17



Date:

9/23/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMMENDED

1-TCO RECOMMENDED WITH THE CAPTAINS APPROVAL FOR THE SOUTH CABANA S ONLY
2-THIS IS A 90 DAY TCO - THE CAPTAIN MUST SIGN THE TCO FORM FROM SURFSIDE BEFORE A TCO WILL BE RECOMMENDED
3-ALL FEE MUST BE PAID BEFORE A TCO WILL BE RECOMMENDED
4-NEED HOLD HARMLESS LETTER ON CO. LETTER HEAD AND MUST BE NOTERIZED

REASON FOR TCO: NEED TO FINISH THE PROJECT

REP: PETE BERTOT 305 588-6232

SRI FEES APPLY -- C.B.WOLFF -- 09/23/17



Date:

9/23/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMMENDED

1-TCO RECOMMENDED WITH THE CAPTAINS APPROVAL FOR THE SOUTH CABANA S ONLY
2-THIS IS A 90 DAY TCO - THE CAPTAIN MUST SIGN THE TCO FORM FROM SURFSIDE BEFORE A TCO WILL BE RECOMMENDED
3-ALL FEE MUST BE PAID BEFORE A TCO WILL BE RECOMMENDED
4-NEED HOLD HARMLESS LETTER ON CO. LETTER HEAD AND MUST BE NOTERIZED

REASON FOR TCO: NEED TO FINISH THE PROJECT

REP: PETE BERTOT 305 588-6232

SRI FEES APPLY -- C.B.WOLFF -- 09/23/17



Date:

9/23/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMMENDED

1-TCO RECOMMENDED WITH THE CAPTAINS APPROVAL FOR THE SOUTH CABANA S ONLY
2-THIS IS A 90 DAY TCO - THE CAPTAIN MUST SIGN THE TCO FORM FROM SURFSIDE BEFORE A TCO WILL BE RECOMMENDED
3-ALL FEE MUST BE PAID BEFORE A TCO WILL BE RECOMMENDED
4-NEED HOLD HARMLESS LETTER ON CO. LETTER HEAD AND MUST BE NOTERIZED

REASON FOR TCO: NEED TO FINISH THE PROJECT

REP: PETE BERTOT 305 588-6232

SRI FEES APPLY -- C.B.WOLFF -- 09/23/17



Date:

9/21/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

2 - APPROVED PARTIAL


THIS INSPECTION WAS FOR BUILDING 1 SOURTH CABANA S

1-SITE EGRESS EMERGENCY LIGHTNING - OKAY

SRI FEES APPLY -- C.B.WOLFF -- 09/21/17



Date:

8/26/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


SURF CLUB BUILDING 1 CORE 3

1-FIRE DEPARTMENT SET UP SITE IS APPROVED AND MUST KEEP ALL SIGNAGE PER THE SET UP SITES PER CAPT. IGLESIAS
2-UNIT 512 - SPRINKLERS, HAND AND GUARDRAILS - OKAY
3-UNIT 510 - SPRINKLERS, HAND AND GUARDRAILS - OKAY
4-UNIT 509 - SPRINKLERS, HAND AND GUARDRAILS - OKAY
5-UNIT 511 - NOT READY
6-UNIT 409 - SPRINKLERS, HAND AND GUARDRAILS - OKAY
7-UNIT 410 - SPRINKLERS, HAND AND GUARDRAILS - OKAY
8-UNIT 412 - SPRINKLERS, HAND AND GUARDRAILS - OKAY
9-UNIT 411 - HAND AND GUARDRAILS - OKAY
10-UNIT 309 - HAND AND GUARDRAILS - OKAY
11-UNIT 209 - HAND AND GUARDRAILS - OKAY

SRI FEES APPLY -- C.B.WOLFF -- 08/26/17



Date:

8/15/2017 

Inspector:

Casandra Pough (POUGHC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


8/15/2017
Pough
Permit #2015011603
9001 Collins Avenue
Surfside ,FL 33154
Surf Club
Surfside# 13-727


1. TCO inspection performed, however will need the Bureau Captain s signature for the final recommendation of approval.

2. Contractor is requesting a TCO to occupy Building#1, Core#1, South Tower Floors 2-9 and lobby. The Core #1, 10th thru the roof, cabanas, Core #2 and #3 is excluded from the TCO.

3. Reason: The remaining upper floors, and cores are still under construction . One permit.

4. Pending items from the previous list
-BOH - BRASS CAPST NOT INSTALLED IN STAIRWELLS
-NEED TO I.D. PULL 4TH FLOOR BOH
-3RD FLOOR STAIR 5 SPRINKLER PIPE
-STAIR 5 EXIT DOOR NEEDS EXIT TACTILE SIGNAGE
- pending items from Lt. McCook List is still outstanding.

5. Life safety items for requested areas verified okay.

6. Sprinkler # 2015-067872, f/a # 2016-042208 are on a partial approval.

7. Tom Evans @ 571-206-2377

8. All documents will need to be submitted to both departments for a signed approval.

9. Do not occupy w/o a CO or TCO signed approved on site.

10. Still need a final fire, f/a and sprinkler final approval inspections.

11. Fees applies.



Date:

8/15/2017 

Inspector:

Michele McCook (MMW) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


INSP 8-11-17MMW

SURF CLUB
LIFE SAFETY INSPECTIONS CONTINUE.
ITEMS COMPLETED:

1. BUILDING 1, GENERATOR #1 - POWER TRANSFER. VARIFIED EMERGENCY/EXIT LIGHTS.

NOTE: AT TIME INSPECTION, GENERATOR RUNNING DID NOT REPORT TO FACP. ALSO UNABLE TO CONFIRM STATUS OF GENERATOR 1 ON ANNUNCIATOR. AT TIME ANNUNCIATOR REPORTING TROUBLE.



Date:

8/9/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


BUILDING 1 CORE 1

1-UNIT 901 - 120V AND SPRINKLERS - OKAY
2-UNIT 903 - 120V, SPRINKLERS AND HAND/GUARDRAILS - OKAY
3-UNIT 803 - 120V - OKAY
4-BOH - BRASS CAPST NOT INSTALLED IN STAIRWELLS
5-2ND FLOOR BALCONIES NEED HAND/GUARDRAILS
6-NEED SIGNAGE IN THE LOBBY
7-BOH - 5TH FLOOR NOT READY
8-NEED TO I.D. PULL 4TH FLOOR BOH
9-3RD FLOOR STAIR 5 SPRINKLER PIPE
10-STAIR 5 EXIT DOOR NEEDS EXIT TACTILE SIGNAGE
11-NEED FIRE EXTINGUISHERS THROUGHOUT THE LOBBY AREA PER NFPA 10

SRI FEES APPLY -- C.B.WOLFF -- 08/08/17



Date:

8/5/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

2 - APPROVED PARTIAL


BUILDING 1 CORE 1

1-AREA OF REFUGE FOR FLOORS - ROOF TO 1ST FLOOR - OKAY
2-NOT READY FOR OUTSIDE LIGHTING AT THIS TIME
3-STILL NEED APPROVED PLANS FOR FIRE DEPARTMENT SET UP,ACCESS CONTROL AND LIFE SAFETY FOR BUILDING 1
4-NEED TO INSTALL HANDRAILS IN THE CABANA AREA BUILDING 1
5-NEED EXIT SIGNS ON THE EAST SIDE OUTSIDE TO THE PUBLIC WAY
6-NEED TO FINISH THE SITE WORK ON THE EAST SIDE OF BUILDING 1
7-NEED OCCUPANT LOADE SIGNAGE FOR ASSEMBLIES GREATER THAN 50
8-NEED TO FINISH FIRE DEPARTMENT SET UP SITE ON THE EAST SIDE OF BUILDING 1

SRI FEES APPLY -- C.B.WOLFF -- 08/05/17



Date:

8/3/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

2 - APPROVED PARTIAL


BUILDING 1 CORE 1

1-BOH FLOORS ROOF TO FLOOR 2 DOORS CLOSE AND LATCH,FIRE RATED LABELS OKAY ALL DOOR HARDWARE OKAY, FIRE RATED LABELS OKAY

SRI FEES APPLY -- C.B.WOLFF -- 08/03/17



Date:

7/29/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

2 - APPROVED PARTIAL


BUILDING 1 CORE 1

SPRINKLERS
1-UNITS 402,501,502,602,603 AND 703 - OKAY

UNIT SMOKE ALARMS
1-601,602,603 AND 801 - OKAY

FIRE ALARM
1-UNITS 601,602,603,703 AND 801 - OKAY

BOH FIRE ALARM
1-5TH,4TH,3RD AND 2ND FLOORS - OKAY

SRI FEES APPLY -- C.B.WOLFF -- 07/29/17



Date:

7/26/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


BUILDING 1 CORE 1

1-NEED ADA FROM BUILDING 1
2-REMOVING SIDE WALK AND GOING TO ONLY HAVE DRIVE WAY

SPRINKLER FINALS - 602,603,503,403,303 - APPROVED

BUILDING 1 CORE 3

1-SPRINKLER FINALS -409,309,209 - APPROVED

SRI FEES APPLY -- C.B.WOLFF -- 07/25/17



Date:

7/22/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

2 - APPROVED PARTIAL


SURF CLUB
BUILDING 1 CORE 1

1-NEED TO REPLACE ALL SPRINKLER HEADS IN UNIT 903
2-UINIT HANDRAILS/GUARDRAILS THAT ARE APPROVED - 1001,1003,901,801,803,701,703,602,603,50`,502,401,402 AND 301
3-UNIT 801 GUARDRAILS ONLY OKAY
4-11TH FLOOR AND PH ARE NOT READY FOR INSPRCETION

SRI FEES APPLY -- C.B.WOLFF -- 07/22/17



Date:

7/21/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


MEET WITH JOHN NEWSOME (VP OPERATIONS COASTAL), FRANK HENRY (PROJECT MGR), AND JEFF SUTHERLAND (SUPERVISOR)

DISCUSSED TCO PROCEDURE FOR BUILDING 1 CORE 1,2 AND 3.

THEY HAVE BEEN ADVISED BY OWNERSHIP TO REMOVE SPRINKLER COVERAGE IN THE PH UNITS FOR ALL THE CORES. THE QUESTION WAS ASKED HOW DOES THIS EFFEC THE TCO.

I EXPLAINED THEY WILL NOT GET A TCO WITH OUT THE PROPER SPRINKLER COVERAGE FOR THE BUILDING IN ALL THE CORES,LOBBY AND THEY NEED TO HAVE THE PROPER MEANS OF EGRESS UNOBSTRUCTED

SRI FEES APPLY -- C.B.WOLFF -- 0721/17



Date:

7/15/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


SURF CLUB - BUILDING 1 CORE 3

1-WALKED FLOORS 6-9 UNITS TO DETERMINE IF READY FOR FINAL - THESE UNITS ARE STILL UNDER CONSTRUCTION PER NFPA 1 1.14.4

BUILDING 1 CORE 3 - 2 UNITS ONLY

1-UNIT 309 - S/D S, DOORS AND SPRINKLERS - OKAY
2-UNIT 208 - S/D S AND DOORS - OKAY
-UNIT 209 - NEED TO ADD SPRINKLER HEAD BEHIND STRUCTUAL COLUN EAST LIVING ROOM PER DRAWINGS

SRI FEES APPLY -- C.B.WOLFF -- 07/15/17



Date:

7/9/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


THIS INSPECTION WAS FOR THE FIRE DEPARTMENT SET UP SITE FOR THE SURF CLUB LOCATED AT 9011 COLLINS AVE.

WALKED WITH LT. SIMMONS,JOHN NEWSOME (VP COASTAL CONSTRUCTION),ORLANDO CARRILLO (OWNERS REP.),JEFF SOUTHERLAND (PROJECT SUPERVISOR) AND A REP. FROM KOBI CARP.

1-IT WAS DETERMINED THAT THERE IS WORK TO BE DONE IN ORDER FOR THE SET UP SITES TO BE APPROVED
2-ORLANDO CARRILLO WILL RE-SUBMIT THE SET UP SITE PLANS WITH THE NECESSARY ADJUSTMENT FOR APPROVAL
3-IT ALSO, WAS DETERMINED THAT BUILDING 1 SIDEWALK FROM THE BUILDING IS GREATER THAN 1 IN 12 AND NEEDS TO BE LOOKED AT FOR PROPER EGRESS TO THE PUBLIC WAY AND POSSIBLE HANDRAILS OR STEPS TO SATISFY THE REQUIREMENTS FOR EGRESS FROM A BUILDING TO THE PUBLIC WAY

SRI FEES APPLY -- C.B.WOLFF -- -07/08/17



Date:

7/7/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


BUILDING 1 CORE 1 FLOORS 2-5

1-UNIT SMOKE ALARMS FLOORS 2-5 - OKAY
2-UNIT F/A SPEAKERS FLOORS 2-5 - OKAY

BUILDING 1 SOUTH CABANA S 1ST & 2ND FLOOR

1-S/D S SOUNDER BASE 1ST & 2ND FLOOR - OKAY
2-F/A SPEAKERS IN CABANA S 1ST & 2ND FLOOR - OKAY
3-OUTSIDE STROBES IN CABANA AREA - OKAY

S/D S SOUNDER BASE 2ND FLOOR OKAY EXCEPT UNIT 16

NOTE: NEED TO REPROGRAM S/D S SOUNDERBASE TO SAY 1ST FLOOR AND 2ND FLOOR "NOT" BASEMENT AND 1ST FLOOR

SRI FEES APPLY --C.B.WOLFF -- 07/06/17



Date:

7/1/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


SURF CLUB
BUILDING 1 CORE 1

1-MISSING ROOF ELECTRIAL ROOM DOOR
2-ELECTRIAL ROOM ROOF NEEDS FIRE CAULKING
3-NEED HANDRAILS FOR ROOF STAIRS IN THE CORE
4-NEED TO FINISH THE ROOF HANDRAILS AND GUARDRAILS FOR THE POOL AREAS
5-NEED TO PROVIDE SPRINKLER CAPS FOR THE CONCEALED SPRINKLER HEADS
6-NEED TO REPLACE SPRINKLER HEAD BY KITCHEN 501 AND BEDROOM 2 BATHROOM

7-DID NOT WALK THE ENTIRE BUILDING 1 CORE 1 JUST DID A SPOT CHECK PER CONSTRUCTION COMPANY

SRI FEES APPLY -- C.B.WOLFF -- 07/01/17



Date:

6/29/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


PRELIMARY INSPECTION FOR BUILDING 1

1-NEED TO RAISE SPRINKLER HEAD IN STGORAGE ROOM LOWER LOBBY
2-NEED TO ADD EXIT LIGHTS IN LOWER LOBBY CORRIDOR
3-LOWER LOBBY NEEDS TO ADD SPRINKLER COVER PLATES
4-NEED TO REMOVE EXIT LIGHTS THAT LEAD TO THE GARAGE
5-NEED SPRINKLER CAPS FOR PRV S IN BUILDING 1
6-ALL THRESHOLDS NEED TO BE SECURE IN BASEMENT THROUGHOUT
7-NEED TO FINISH ELEVATOR LOBBY STAIR B1-SO4
8-NEED EXIT TACTILE SIGNAGE THROUGHOUT
9-NEED TO FINISH B1 LOBBY AND EXTERIOR FOR A CLEAR MEANS OF EGRESS
10-NEED TO INSTALL HANDRAILS FOR SIDEWALK FOR BUILDING 1 WEST SIDE OF BUILDING 1

SRI FEES APPLY -- C.B.WOLFF -- 06/29/17



Date:

6/27/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


THIS INSPECTION WAS FOR BUILDING 1 -WALKED WITH JEFF SUTHERLAND AND PETE BERTOT CONCERNING THE PROGRESS THAT HAS BEEN MADE IN THE LAST 2 WEEKS.

BUILDING IS STILL UNDER CONSTRUCTION - TALKED ABOUT A TCO IN THE NEXT 3 TO 4 WEEKS.

BUILDING STILL DOES NOT HAVE A SPRINKLER FINAL IN ANY OF THE CORES 1,2 OR 3 NOR THE LOBBY OR BASEMENT OR GARAGE AND LOADING DOCK

BUILDINNG STILL NEEDS TO BE TESTED FOR THE FIRE ALARM

BUILDING STILL NEEDS THE OUTSIDE TO BE FINISHED BEFORE A TCO WILL BE CONSIDERED.

ALSO, STILL NEED FIRE DEPARTMENT SETUP SITES TO BE FINISHED TO BRING OUT THE ARIEAL FOR SET UP.

SRI FEES APPLY -- C.B.WOLFF -- 06/27/17



Date:

6/15/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


THIS INSPECTION WAS FOR THE EXTENSION FOR THE TCO FOR BUILDING 2 - WALKED THE ENTIRE BUILDING WITH FRANK HENRY THE PROJECT MGR. - AT THIS TIME FRANK WANTED TO KNOW HOW TO FINAL BUILDING 2 - EXPLAINED THAT THE ENTIRE PROJECT NEEDS TO BE COMPLETED BEFORE A FIRE FINAL CO CAN BE GIVEN. DUE TO THE ENTIRE PROJECT IS UNDER ONE PERMIT

SRI FEES APPLY -- C.B.WOLFF -- 06/15/17



Date:

6/14/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


WALKED BUILDING 1 CORES 1,2 AND 3 WITH COASTAL CONSTRUCTION PERSONNEL TO SEE HOW FAR ALONG THEY ARE IN GETTING A TCO FOR THIS BUILDING. THIS BUILDING IS STILL UNDER CONSTRUCTION AND NOT EVEN BEING CLOSE TO BEING COMPLETED

SRI FEES APPY -- C.B.WOLFF -- 06/13/17



Date:

6/14/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


WALKED BUILDING 1 CORES 1,2 AND 3 WITH COASTAL CONSTRUCTION PERSONNEL TO SEE HOW FAR ALONG THEY ARE IN GETTING A TCO FOR THIS BUILDING. THIS BUILDING IS STILL UNDER CONSTRUCTION AND NOT EVEN BEING CLOSE TO BEING COMPLETED

SRI FEES APPY -- C.B.WOLFF -- 06/13/17



Date:

6/11/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


INSPECTION WAS FOR BUILDING 1 CORE 1 HANDRAILS ONLY

1-WALKED FLOORS 2-12
2-THE ONLY HANDRAILS THAT WERE GOOD ARE IN UNITS 303,402,403,503,603,701,703,901 AND 1003
3-ALL OTHER HANDRAILSW WERE NOT ACCEPTABLE

SRI FEES APPLY -- C.B.WOLFF -- 06/10/17



Date:

6/9/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


THIS INSPECTION WAS A PRE-TEST FOR THE SMOKE CONTROL TEST AND BALANCE INSPECTION

BUILDING 1 CORE 2 - SMOKE CONTROL FLOORS 10,6 & 2 CHECKED - OKAY
BUILDING 1 CORE 3 - SMOKE CONTROL FLOORS 10,6 & 2 CHECKED - OKAY
BUILDING 1 STAIR B1-S02 SMOOKE CONTROL DAMPER DID NOT OPEN WHEN ON THE 2ND FLOOR

1-WHEN ALL THE PAPER WORK IS IN AND THE REPORTS HAVE BEEN SUBMITTED THEN WE WILL CONDUCT THE FINAL SMOKE CONTROL TEST FOR ALL CORES IN BUILDING 1
2-LOBBY IS NOT READY FOR THE TEST
3- NEED TO RELOCATE TRUST MARKING SIGN AT PEACOCK ALLEY - NOT VISIBLE DUE TO FOLLAGE IN FRONT OF IT.
4-6TH FLOOR STAIR 1 LEADING TO THE 7TH FLOOR STEPS ARE NOT UNIFORM
5-NEED TO RELOCATE ALL STAIRWELL SIGNAGE CLOSER TO THE DOOR

SRI FEES APPLY -- C.B.WOLFF -- 06/08/17




Date:

6/7/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


WENT TO THE SURF CLUB TO WITNESS THE SMOKE TEST FOR BUILDING 1 CORES 2 AND 3 - HOWEVER , JEFF FROM SLS CONDUCTING THE SMOKE TEST - THE SMOKE MACHINE BROKE AND HE DID NOT HAVE ANOTHER MACHINE NOR DID HE HAVE SMOKE BOMBS THAT WOULD WORKD FOR THE SMOKE TEST

SRI FEES APPLY -- C.B.WOLFF -- 06/06/17



Date:

6/6/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


THIS INSPECTION WAS FOR BUILDING 1 CORE 1

1-UNITS 401,402 AND 403 SPRINKLER FINAL - DENIED
2-IT ELECTRIAL ROOM B1-121 BUILDING 1 CORE 1 SPRINKLER HEAD - OKAY
3-NEED TO PAINT RED ALL FDC S AT COLLINS AVE. PER WASA D-8

SRI FEES APPLY -- C.B.WOLFF -- 06/05/17



Date:

6/3/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


WALKED BUILDING 1 CORE 1 BOH

1-FROM THE 11TH FLOOR TO THE 2ND FLOOR
2-FLOORS 2-7 TRASH CHUTE HOOPER DOORS DO NOT CLOSE AND LATCH
3-BOH - UNITS,BOTH STAIRWELL DOORS FOR FLOORS 2-11 OKAY - FOR CLOSING,LATCHING,FIRE RATED LABELS AND ASSEMBLY

C.B.WOLFF -- 06/03/17



Date:

6/3/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMMENDED FOR 90 DAYS WITH THE CAPTAINS APPROVAL FOR T.K. KITCHEN AND BUILDING 2 BASEMENT/GARAGE "ONLY

1-ORLANDO IS FAMILAR WITH THE TCO PROCEDURE
2-NEED TO PAY ALL OUTSTANDING FEES BEFORE A TCO WILL BE RECOMMENDED

REP: ORLANDO CARRILLO 305 632-7921

SRI FEES APPLY -- C.B.WOLFF -- 06/03/17



Date:

6/2/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


TCO DENIED FOR THE FOLLOWING AREAS

1-T.K. KITCHEN - FIRE ALARM PLANS DO NOT MATCH APPROVED PLANS
2-FIRE ALARM PLANS SHOW WALLS - NO WALLS INSTALLED
3-NEED TO REVISE FIRE ALARM PLANS TO SHOW A SHELL INSTEAD OF WALLS OR INSTALL WALLS PER NFPA 1 1.14.4
4-BASEMENT GARAGE - NEED TO INSTALL EXIT TACTILE SIGNAGE FOR THE BUILDING (2)
5-NEED TO INSTALL THE PROPER FIRE RATED DOOR BY THE POOL KITCHEN

SRI FEES APPLY -- C.B.WOLFF -- 06/01/17



Date:

5/31/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


TCO DENIED

1-NEED AN APPROVED SET OF FIRE ALARM PLANS FOR T.K. KITCHEN PER NFPA 1 1.14.4
2-NEED APPROVED SIGNAGE FOR THE BASEMENT/GARAGE IN BUILDING 2
3-FIRE RATED DOORS SHALL CLOSE AND LATCH PER NFPA 1 1.14.4
4-NEED TO HAVE AN APPROVED ELEVATOR IN T.K. KITCHEN

SRI FEES APPLY -- C.B.WOLFF -- 05/31/17



Date:

5/25/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


INSPECTION WAS FOR THE T.K. KITCHEN

1-NEED TO ADD EXIT LIGHT ON THE 1ST AND 2ND LEVEL FLOOR LOBBY
2-NEED YELLOW STRIPPING ON STAIRS LESS THAN 21 INCHES
3-NEED SPRINKLER HEAD UNDER A/C 2ND FLOR
4-NEED FIRE RATED LABEL ON 2ND FLLOR T.K. KITCHEN
5-NORTH T.K.KITCHEN REVISE PLANS TO SHOW CORRECT EOL
6-FIRE ALARM FOR THE T.K. KITCHEN IS OKAY
7-NEED A COMPLETE AND APPROVED SET OF PLANS FROM MDFR
8-NEED SIGNAGE FOR THE BASEMENT AND T.KT.KITCHEN AREAS

C.B.WOLFF -- 05/25/17



Date:

5/25/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMMENDED FOR 90 DAYS FOR BUILDING 2 PENTHOUSES 1-6 AND ROOF WITH THE CAPTAINS APPROVAL

1-NEED TCO LETTER ON CO. LETTER HEAD AND MUST BE NOTERIZED AND STATE REASON FOR THE TCO
2-OWNERS REP: ORLANDO CARRILLO 305 632-7921
3-ORLANDO IS FAMILAR WITH THE TCO PROCEDURES
4-NEED TO PAY ALL OUTSTANDING FEES BEFORE A TCO WILL BE CONSIDERED

SRI FEES APPLY -- C.B.WOLFF -- 05/25/17



Date:

5/24/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


BUILDING 1 CORE 1

1-CORE 1 T & B, DOOR PULLS AND DIFFENTRAL PRESSURE - OKAY
2-NEED CENTER HANDRAIL IN THE LOBBY GRANDSTAIR IN BUILDING 1

SRI FEES APPLY -- C.B.WOLFF -- 05/23/17



Date:

5/20/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


WALKED TK KITCHEN WITH JEFF SUTHERLAND TO DETERMIN WHAT NEEDS TO BE DONE FOR A TCO IN THIS AREA.THERE ARE MANY ITEMS THAT NEED TO BE DONE - NEED EXIT SIGNS,EMERGENCY LIGHTS,UNIFORMIT IN THE STAIRS,FIRE EXTINGUISHERS,DOOR HARDWARE,FIRE RATED WALLS SHALL GO ALOTHE WAY T0 CEILING AND MUST BE FIRE CAULKED. ALSO, WALKED THE PENTHOUSE AREA WHICH STILL THE HAND/GUARD RAILS THAT NEED TO BE FINISHED

ALSO, WALKED THE AREAS FOR SMOKE CONTROL AND ARE NOT READY FOR TESTING AT THIS TIME, THEY ARE STILL IN THE TEST AND BALANCING STAGE OF THIS PROCEDURE

SRI FEES APPLY -- C.B.WOLFF -- 05/20/17



Date:

5/19/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

2 - APPROVED PARTIAL


SURF CLUB

1-BUILDING 1 CORE 1 SMOKE ALARMS
2-UNIT 203 SMOKE ALARM - OKAY
3-UNIT 303 SMOKE ALARM - OKAY
4-UNITS 401,402 AND 403 SMOKE ALARMS - OKAY
5-UNITS 501,502 AND 503 SMOKE ALARMS - OKAY
6-UNITS 602 AND 603 SMOKE ALARMS - OKAY

SRI FEES APPLY -- C.B.WOLFF -- 05/18/17



Date:

5/17/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


WALKED WITH FRANK HENRY THE PROJECT MANAGER AND JEFF SUTHERLAND THE SUPERVISOR - FOR THE NORTH CABANA S,BUILDING 1 LOBBY, T.K. KITCHEN,BUILDIING 2 ROOF AND POOLS FOR THE PENTHOUSE,BUILDING 1 LOBBY AND SOUTH CABANA S

NOTE: THIS INSPECTION WAS FOR TCO PROCEDURES

SRI FEES APPLY -- C.B.WOLFF -- 05/16/17



Date:

5/13/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMMENDED FOR 90 DAYS WITH THE CAPTAINS APPROVAL FOR (NORTH CABANA S ONLY)

1-PETE BERTOT IS FAMILAR WITH THE TCO PROCEDURE
2-NEED NEW TCO LETTER ON CO. LETTER HEAD AND NOTERIZED
3-NEED TO PAY ALL OUTSTANDING FEES BEFORE THE TCO WILL BE GIVEN

REP: PETE BERTOT 305 588-6232

SRI FEES APPLY -- C.B.WOLFF -- 05/13/17



Date:

5/11/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


SURF CLUB CABANA S
2015011603

1-FENCE ON THE BOTTOM HAS GREATER THAN 4"
2-NO HANDRAILS ON THE NORTH SIDE OF THE CABANA S
3-NO GUARDRAILS ON THE NORTH SIDE OF THE CABANA S
4-NEED TO REMOVE THE TRIPPING HAZARD AT THE LIFT STATIION
5-BOILER EXHAUST NEEDS A 90
6-NEED CLEAN OUT AND COVER
7-SPRINKLER ESCUTCHEONS NEED TO BE FLUSH
8-NEED UNIT NUMBERS ON THE BACK OF THE CABANA S
9-NEED TO MOVE POOL SIGN AND GIVE SPECIFIC TIMES OF POOL OPERATIONS

SRI FEES APPLY -- C.B.WOLFF -- 05/11/17



Date:

5/10/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


WALKED THE PH UNITS 3,4 AND 6 TO DETERMINE WHEN THEY SHOULD BE ABLE TO GET A TCO.

DISCUSSED THE GARAGE AREA,TK KITCHEN,NORTH CABANA S AND THE ROOF AND POOL AREAS FOR ALL THE PENTHOUSES

WALKED WITH THE PROJECT MANAGER FROM COASTAL AND ONE OF THE SUPERVISERS.

ALSO, ASKED IF THERE WAS ANYTHING ELSE THAT THEY WOULD LIKE TO LOOK AT OR INSPECT.

SRI FEES APPLY -- C.B.WOLFF -- 05/09/17



Date:

5/6/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


SURF CLUB 2015011603

1-PH 5 S/D S - OKAY
2-PH 2 S/D S - OKAY
3-CHECKED OUT T.K. KITCHEN FOR PROGRESS
4-WALKED BUILDING 1 CORE 1 FOR PROGRESS

SRI FEES APPLY -- C.B.WOLFF -- 05/06/17



Date:

5/5/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMMENDED WITH THE CAPTAINS APPROVAL FOR 90 DAYS

1-THIS TCO IS FOR UNITS PH1,PH2 AND PH5 ONLY
2-ROOF AND POOL DECK ARE EXCLUDED FROM THIS TCO
3-PETE BERTOT IS FAMILAR WITH THE TCO PROCEDURE

REASON: CONTINUE PHASE 2 AND COMPLETE BUILDING 1

REP: PETE BERTOT 305 588-6232

SRI FEES APPLY -- C.B.WOLFF -- 05/04/17



Date:

5/4/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


INSPECTION FOR PENTHOUSES

1-PH 5 SPEAKERS - OKAY
2-PH 5 S/D S IN-OP
3-NEED PANEL SCHEDULE ALL ELECTRIC PANELS PH LEVEL
4-PH 2 S/D S IN-OP
5-PH 2 SPEAKERS - OKAY
6-PH 1 S/D S - OKAY
7-PH 1 SPEAKERS - OKAY

SRI FEES APPLY -- C.B.WOLFF -- 05/03/17



Date:

5/3/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


THIS INSPECTION WAS FOR THE PENTHOUSES IN BUILDINNG 2

1-HANDRAILS TO SPA FROM LOBBY - OKAY
2-PH 1,2 AND 5 BUILDING 2
3-PH 1 AND 5 ROOF STAIR ACCESS TO DECK NEED TO BE CHECKED OUT
4-NEE TO CLOSE TK KITCHEN STAIRS

SRI FEES APPLY -- C.B.WOLFF -- 05/02/17



Date:

4/29/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


WALKED WITH FRANK HENRY AND JEFF SUTHERLAND FROM COASTAL CONSTRUCTION CO.

1-WALKED THE PH UNITS IN BUILDING 2 WHICH ARE ON THE 11TH AND 12TH FLOORS TO DETERMINE WHAT NEEDS TO BE DONE TO GET A TCO
2-WALKED THE NORTH CABANA S TO DETERMINE THE SAME
3-WALKED THE GARAGE TO DETERMINE ALSO THE SAME

NOTE: I ADVISED THE COASTAL/OWNERS THAT THE FIRE DEPARTMENT WILL NOT BRING OUT THE FIRE TRUCK FOR FIRE DEPARTMENT SET UP SITE UNTIL THE AREAS FOR THE SET UP SITE ARE FULLY CONSTRUCTED. ONCE, THIS IS DONE WE WILL BRING OUT THE TRUCK AND VERIFY THE SET UP SITES ARE OKAY AND THEN WE WILL APPROVED THEM BUT NOT UNTIL ALL SET UP SITES ARE READY FOR INSPECTION. IF THEY ARE NOT APPROVED THE SET UP SITE PLANS WILL HAVE TO BE REVISED SO THEY CAN BE APPROVED BY VERIFICATION OF TH ETRUCK COMING OUT ONCE AGAIN UNLESS IT IS ON SOLID GROUND AND NOT MORE THAN A 5% SLOPE

C.B.WOLFF -- 04/29/17



Date:

4/28/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMMENDED WITH THE CAPTAINS APPROVAL (90) DAYS

1-AREAS FOR TCO INCLUDE CORES 1,2 AND 3 FROM THE LOBBY TO 10TH FLOOR "ONLY"
2-ORLANDO CARRILLO IS FAMILAR WITH THE TCO PROCEDURE
3-REASON: FINISH BUILDING 1 PHASE 3 AND REVISE PLANS

OWNERS REP: ORLANDO CARRILLO 305 632-7921

SRI FEES APPLY -- C.B.WOLFF -- 04/27/17



Date:

4/26/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


WALK BUILDING 2 CORE 3

1-S/D S IN THE MECHANIAL ROOM 3RD FLOOR GYM - OKAY
2-D/D IN THE MECHANIAL ROOM 3RD FLOOR GYM - OKAY
3-3RD FLOOR GYM LIFE SAFETY - OKAY
4-UNITS 315 AND 415 - OKAY
5-UNIT 913 - OKAY

BUILDING 2 CORE 2

1-ACCESS CONTROL/ELECTRIC STRIKES - FOR ACCESS CONTROL/ELECTRIC STRIKES TO BE REMOVED OR ADDED SEE PLANS
2-STILL NEED TO TEST THE ACCESS CONTROL/ELECTRIC STRIKES FOR BUILDING 2 CORE 2

C.B.WOLFF -- SRI FEES APPLY -- 04/25/17



Date:

4/25/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


THIS INSPECTION WAS FOR THE FOLLOWING

1-BUILDING 2 CORE 3 GYM
A)NEED DIRECTIONAL EXIT SIGNS X2
B-NEED (1) 2A-10BC FIRE EXTINGUISHER - MUST BE TAGGED AND SERVICED BY A STATE CERTIFIED CO. AND HANG NO HIGHER THAN 5 AFF.

2-NEED SPRINKLER HEADS IN THE MASTER BEDROOM A/C CLOSET FOR UNITS 315 AND 415.

3-BUILDING 2 CORE 3 UNITS 1014,1013,1012,1011,911,912,914,811,812,813,814,711,712,713,714,611,511 AND 513 - OKAY

4-BUILDING 2 CORE 2 UNITS -915,917,919,921,1015,1017,1019 AND 1021 - OKAY

SRI FEES APPLY -- C.B.WOLFF -- 04/24/17



Date:

4/22/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


THIS IS A PRILIMARY INSPECTION FOR BUILDING 2 CORE 3

1-UNITS 512,514,612,613 AND 614 ARE - OKAY
2-7TH FLOOR NEEDS SIGNAGE
3-3RD AND 4TH FLOORS ARE NOT READY
4-ALL BALCONIES STILL NEED STONE ON THEM
5-UNITS 915 AND 917 NEED STONE
6-T.K. KITCHEN NEEDS TO HAVE S/D S RAISED TO THE CEILING,PULL STATIONS ADDED,STAIRS TO CONFORM TO CODE,FIRE EXTINGUISHERS THROUGHOUT,NEED TO ADD EXIT SIGNS,NEED EMERGENCY LIGHTS,NEED TO ADD A SECOND MEANS OF EGRESS,ALL STAIRS SHALL BE OF A PERMANENT NATURE AND TO CODE,HANDRAILS SHALL CONFORM TO THE CODE,GUARDRAILS SHALL CONFORM TO CODE,NEED TO TEST ALL FIRE ALARM DEVICES,CAN NOT HAVE GREATER THAN 1/2" ELEVATION CHANGE AND THERE SHALL NOT BE ANY TRIPPING HAZARDS,NEED EXIT TACTILE SIGNAGE FOR EXITS THAT LEAD TO THE OUTSIDE,ALL CONSTRUCTION DEBRIS SHALL BE REMOVED AND LAST BUT NOT LEAST YOU MUST HAVE AN APPROVED SET OF PLANS FOR THE T.K. KITCHEN

SRI FEES APPLY -- C.B.WOLFF -- 04/22/17



Date:

4/21/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


ONCE AGAIN, WALKED THE UNITS ON THE 3RD AND 4TH FLOORS FOR TCO PURPOSES IN BUILDING 2 CORE 3. AGAIN, THEY WERE NOT READY. LOOKED AT UNITS IN BUILDING 2 CORE 2 ON THE 8TH AND 9TH FLOORS AND AGAIN THOSE UNITS ALSO ARE NOT READY.

ALSO, THEY STILL DO NOT AN APPROVED SET OF PLANS FOR THE ACCESS CONTROL AND ELECTRIC STRIKES WHICH I ADVISED THEM 4 MONTHS AGO. I ALSO HAVE ADVISED THEM THEY NEED TO REMOVE THE POWER TO THEM UNTIL THEY GET AN APPROVED SET OF PLANS.

IT HAS BEEN BROUGHT TO MY ATTENTION THAT THEY DO NOT SEEM TO CARE ABOUT THE ACCESS CONTROL AND THAT THEY WILL CONTINUE TO USE IT WITHOUT APPROVAL OR PLANS.

SRI FEES APPLY -- C.B.WOLFF -- 04/20/17



Date:

4/20/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


this inspection was a walk through for the owner and the general contractor

sri fees apply -- c.b.wolff -- 04/20/17



Date:

4/19/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


AGAIN, THIS INSPECTION WAS FOR THE TCO PROCEDURRE FOR BUILDING 2 CORE 3 UNITS ON THE 3RD AND 4TH FLOORS. ALSO, THE PH UNITS IN ALL CORES FOR BUILDING 2

SRI FEES APPLY -- C.B.WOLFF -- 04/18/17



Date:

4/18/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


THIS INSPECTION WAS TO WALK THROUGH BUILDING 2 CORE 3 TO SEE THE PROGRESS THAT IS BEING MADE IN ORDER TO GET A TCO. WALKED WITH JOHN NEWSOME - V.P. FIELD OPERATIONS,FRANK HENRY AND JEFF SUTHERLAND

SRI FEES APPLY -- C.B.WOLFF -- 04/17/17



Date:

4/14/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


THIS INSPECTION WAS TO DETERMIN WHEN BUILDING 2 CORE 3 WILL BE ABLE TO GET A TCO.

WALKED WITH JOHN NEWSOME - VP FIELD OPERATIONS, MICHAEL AUAUD AND JEFF SUTHERLAND. IT WAS DETERMINED THAT THE UNITS ON THE 3RD AND 4TH FLOORS NEED TO BE BUILT AS PER THE PLANS OR THE PLANS NEED TO BE REVISE TO REFLECT THE CHANGES AND APPROVED BY THE FIRE DEPARTMENT.

OTHER AREAS OF CONCERN WERE THE CABANA S WHICH THEY ALSO WANT A TCO FOR - IT ALSO WAS DETERMINED THAT THESE AREA S WILL NEED TO COMPLY WITH ALL LIFE SAFETY AND A PLAN WILL NEED TO BE IN PLACE FOR THE EXITING OF CUSTOMERS

SRI FEES APPLY -- C.B.WOLFF -- 04/13/17



Date:

4/13/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


THIS INSPECTION WAS FOR CLEANING UP AND ORGANIZING PAPER WORK TO MOVE FORWARD ON HAVING THE SURF CLUB OBTAIN A TCO IN ADDITIONAL AREAS IN BUILDING 2 CORE 1,2 AND 3

SRI FEES APPLY -- C.B.WOLFF -- 04/12/17



Date:

4/7/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


THIS INSOECTION IS FOR SPECIFIC UNITS

1-UNIT 309 - SPRINKLERS,SPEAKERS AND S/D S - OKAY - CORE 3
2-UNIT 209 - SPRINKLERS,SPEAKERS AND S/D S - OKAY - CORE 3
3-UNIT 305 - SPEAKERS AND S/D S - OKAY
4-UNIT 205 - SPEAKERS,S/D S CORE 2 - OKAY
5-UNIT 303 - SPEAKERS AND S/D S - OKAY
6-UNIT 203 - SPEAKERS AND S/D S - OKAY

NOTE: WALKED WITH OWNERSHIP FOR THE NORTH CABANA S TO SEE WHEN THEY CAN GET A TCO

SRI FEES APPLY -- C.B.WOLFF -- 04/06/17



Date:

4/7/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


THIS INSOECTION IS FOR SPECIFIC UNITS

1-UNIT 309 - SPRINKLERS,SPEAKERS AND S/D S - OKAY - CORE 3
2-UNIT 209 - SPRINKLERS,SPEAKERS AND S/D S - OKAY - CORE 3
3-UNIT 305 - SPEAKERS AND S/D S - OKAY
4-UNIT 205 - SPEAKERS,S/D S CORE 2 - OKAY
5-UNIT 303 - SPEAKERS AND S/D S - OKAY
6-UNIT 203 - SPEAKERS AND S/D S - OKAY

NOTE: WALKED WITH OWNERSHIP FOR THE NORTH CABANA S TO SEE WHEN THEY CAN GET A TCO

SRI FEES APPLY -- C.B.WOLFF -- 04/06/17



Date:

4/4/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO EXTENSION RECOMMENDED WITH THE CAPTAINS APPROVAL FOR 90 DAYS FOR PHASE 1 ONLY

NOTE: THOSE AREAS INCLUDE FLOORS 5-12,PEACOCK ALLEY,LOUNGE BAR,RESTAURANT LOBBY, SHOW KITCHEN, 4 SEASONS KITCHEN AND BOH OFFICES ONLY

1-NEED TO PROVIDE FIRE EXIT HARDWARE FOR 3RD FLOOR GYM FIRE RATED DOOR PER NFPA 1 1.14.4 AND APPROVED PLANS
2-NEED TO REMOVE LADDER STAIR 3 - 3RD FLOOR
3-NEED TO REMOVE CABINET LOBBY B2-S07
4-NEED TO REMOVE ALL STORAGE BY THE ELECTRIAL ROOM IN THE HOTEL BOH CORRIDORS - THEY DO NOT MAINTAIN 36" OF CLEAR WITH PER NFPA 1 1.14.4
5-NEED TO REMOVE ALL STORAGE IN THE ELECTRIAL ROOMS IN THE HOTEL BOH PER NFPA 1 1.14.4

REP- ORLANDO CARRILLO

ORLANDO IS FAMILAR WITH THE TCO PROCEDURED

C.B.WOLFF -- 04/04/17



Date:

3/24/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


HAD A MEETING WITH OWNERSHIP AND COASTAL CONSTRUCTION CONCERNING THE PROCEDURE TO TCO THE NORTH GARAGE AREA AND THE TESTING OF THE FIRE ALARM FOR BUILDING 1. AND HOW TO BY-PASS THE AREAS THAT ARE ALREADY TCO.

C.B.WOLFF -- 03/23/17



Date:

3/17/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


BUILDING 1 CORE 3

INSPECTED FIRE RATED DOOR LABELS AND TRASH CHUTE DOOR HOOPERS
1-ROOF WEST SIDE DOOR MISSING SCREWS
2-IN-OP HOOPER 10TH FLOOR
3-2 THRU ROOF FIRE RATED LABELS - OKAY
4-2-12 TRASH CHUTE HOOPER DOORS OKAY EXCEPT ON FLOOR 10
5-BASEMENT FIRE RATED DOOR LABEL OKAY

BUILDING 1 COTE 2
1-ROOF WEST SIDE DOOR MISSING SCREWS
2-12TH FLOOR TRASH CHUTE HOOPER DOOR IN-OP
3-2 THRU ROOL FIRE RATED LABELS - OKAY
4-2 THRU 11 HOOPERS OKAY

MEET WITH OWNERSHIP CONCERNING TCO FOR BUILDING 1 - (1) HOUR

SRI FEES APPLY -- C.B.WOLFF -- 03/16/17



Date:

3/17/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


BUILDING 1 CORE 3

INSPECTED FIRE RATED DOOR LABELS AND TRASH CHUTE DOOR HOOPERS
1-ROOF WEST SIDE DOOR MISSING SCREWS
2-IN-OP HOOPER 10TH FLOOR
3-2 THRU ROOF FIRE RATED LABELS - OKAY
4-2-12 TRASH CHUTE HOOPER DOORS OKAY EXCEPT ON FLOOR 10
5-BASEMENT FIRE RATED DOOR LABEL OKAY

BUILDING 1 COTE 2
1-ROOF WEST SIDE DOOR MISSING SCREWS
2-12TH FLOOR TRASH CHUTE HOOPER DOOR IN-OP
3-2 THRU ROOL FIRE RATED LABELS - OKAY
4-2 THRU 11 HOOPERS OKAY

MEET WITH OWNERSHIP CONCERNING TCO FOR BUILDING 1 - (1) HOUR

SRI FEES APPLY -- C.B.WOLFF -- 03/16/17



Date:

3/10/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


FIRE FINAL CO DENIED

1-NEED DOOR BELL FOR NORTH CABANA S FOR THE ADA UNITS
2-SPEAKERS AND S/D S OKAY FOR THE NORTH CABANA S

3-BUILDING 1 CORE 3 FLOORS 902

A)-FLOORS 7,6,5 AND 4 NEED SCREWS IN THE CORNER NE SIDE
B)-4TH FLOOR NEEDS GLASS ON THE NW SIDE
C)-4TH FLOOR E UNIT NOT FINISHED
D)-2ND FLOOR E UNIT MISSING HANDRAIL

BUILDING 1 CORE 2

FLOORS 8-3 OKAY
A)2ND FLOOR MISSING HANDRAIL WEST SIDE

WALKED WITH OWNERSHIP FOR 2 HOURS

SRI FEES APPLY 6 HOURS -- C.B.WOLFF -- 03/10/17



Date:

3/8/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMMENDED FOR 90 DAYS WITH THE CAPTAINS APPROVAL FOR THE FOLLOWING AREAS ONLY PHASE 2

1-SURF CLUB BUILDING 2 NORTH TOWER CORES 1 AND 2 ONLY FLOORS LOBBY THRU 8TH FLOOR, LOBBY AND 2ND FLOOR CORE 3, POOL #1, B2 MAIN ENTRANCE EXTERIOR TERRACE,POOL #1 BATHROOMS,TK COURTYARD,LE SIRENUSE DECK,HOTEL GYM,PRIVATE DINING,RETAIL SHOP 2,SPA,KIDS CLUB, GM OFFICE,SAFETY DEPOSIT ROOM,CONDO HOTEL LOBBY, MEETING ROOM, LOADING DOCE,POOL KITCHEN AND HISTORICAL BATHROOMS
2-OWNERS REP: ORLANDO CARRILLO 305632-7921
3-GO TO 11805 SW 24TH STREET AND HAVE CAPTAIN SIGN SURFSIDE TCO FORM AND MUST BE NOTERIZED ON CO LETTER HEAD

SRI FEES APPLY -- C.B.WOLFF -- 03/07/17



Date:

3/4/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PRILIMARY INSPECTION FOR BUILDING 2 TCO

1-ADVISED OWNERSHIP OF THE FOLLOWING ITEMS FOR BUILDING TO BE ABLE TO GET A TCO
A)POOL APPROVAL BY HRS
B)ELEVATOR CERTIFICATION
C)FIRE DEPARTMENT SITE SETUP FOR SUPPRESSION UNITS - CURRENTLY SITE SETUP IS NOT APPROVED BY THE FIRE DEPARTMENT
D)PLANS THAT THEY HAVE FOR THE SITE SETUP AND WHAT OWNERSHIP HAS DONE IS TWO DIFFERENT THINGS EX. PLANS TO NOT SHOW CANOPIES AND THE HAVE PLANTED PLANTS WHERE FIRE DEPARTMENT UNITS ARE SUPPOSE TO SET UP - BIG PROBLEM

C.B.WOLFF -- 03/04/17



Date:

3/2/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


AREA OF REFUGE FOR THE SPA 3RD FLOOR HOTEL -- OKAY

SPA 3RD FLOOR HOTEL FITNESS -- OKAY

C.B.WOLFF -- 03/01/17



Date:

3/1/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


WALKED WITH OWNERSHIP FOR 2 HOURS

1-SPA SPRINKLERS FINAL - OKAY
2-POOL KITCHEN - OKAY
3-S/D IN GYM 3RD FLOOR - OKAY
4- MECHANIAL ROOM SOUTH SPRINKLER HEAD HAS BEEN ADDED - OKAY
5-B2 CORE 2 TO 3 BRIDGE SPRINKLERS - OKAY
6-B2 CORE 3 SMOKE TEST - OKAY

SRI FEES APPLY -- 02/28/17



Date:

2/25/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


ONCE AGAIN WALKED WITH OWNERSHIP AND VP OF OPERATIONS FOR COASTAL CONSTRUCTION GROUP JOHN NEWSOME. THIS WALK THROUGH WAS FOR BUILDING 2 CORES 1 AND 2.

THE OWNERSHIP GROUP STATED THAT THEY WERE READY FOR THE TCO.

AS WE STARTED TO WALK THE BUILDING FROM THE 12TH FLOOR. FLOORS 12,11,10,9 AND 8 FOR BOTH CORES WERE NOT READY.

CORE 1 FLOORS 7-3 - OKAY

HOWEVER, IN CORE 2 ON FLOORS 3 AND 4 THEY HAVE CONVERTED THE CONDO TO A HOTEL/CONDO AND ARE STILL IN THE CONSTRUCTION STAGES.

THEY FINISH BOTH THE 3RD AND 4TH FLOORS FOR CORE 2 WHICH CONNECTS TO CORE 3 THEN I TOLD THE OWNERSHIP GROUP WE WOULD ENTERTANE THE IDEA OF A TCO, BUT UNTIL THAT TIME THEY NEEDED TO FINISH THE UNITS AS PREVIOUS DISCUSSED

SRI FEES APPLY (7) HOURS -- C.B.WOLFF -- 02/25/17



Date:

2/24/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


CONTINUED WALKING BUILDING 2 DOORS

1-BUILDING 2 CORE 1 FROM ROOF TO 4TH FLOOR - CLOSE,LATCH AND RATED LABELS OKAY
2-BUILDING 2 CORE - 2ND FLOOR STAIRWELL B2 S01 - OKAY
3-BUILDING 2 CORE 1 BASEMENT DOOR MISSING

BUILDING 2 CORE 2

1-B2-S03 ROOF AND ELECTRIAL ROOM DOORS MISSING SCREWS
2-FLOORS 12-3 CLOSE,LATCH AND LABEL - OKAY
3-DOOR 617 MISSING SCREWS
4-REMOVE KEY LOCK STORE FRONT DOOR B2 S04
5-B2-SO3 BASEMENT OKAY

BUILDING 2 CORE 3

1-ROOF TO 5TH FLOOR - OKAY
2-B2-S06 3RD FLOOR MISSING SCREWS
3-B2 3RD FLOOR TO CONDO FITNESS CENTER MISSING LABEL
4-B2 DOOR 245 MISSING SCREWS
5-B2 DOORS 255 AB AND C MISSING LABELS
6-SPA OKAY

SMOKE CONTROL

1-BUILDING 2 CORE 1 AND 2 -- SMOKE CONTROL BOH - PASS PENDING ALL ELEVATOR LOBBIES ONLY
2-STILL NEED TO TEST THE REST OF THE AREA FOR CORES 1 AND 2
3-DID NOT TEST BUILDING 2 CORE 3

SRI FEES APPLY 5 HOURS -- C.B.WOLFF -- 02/23/17



Date:

2/22/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


CONTINUED TESTING OF THE FIRE ALARM AND LIFE SAFETY ITEMS

1-PERSONAL GARAGE - CO DETECTOR - OKAY
2-PERSONAL GARAGE - CO DETECTOR - OKAY
3-B2 CORE 3 SOUNDER BASE CO/SMOKE DETECTORS DID NOT OPERATE PROPERLY - NEED TO RE-TEST
4-B2 CORE 2 - 11TH FLOOR TRASH CHUTE DOOR - OKAY
5-LABELS ON TRASH CHUTE DOORS - OKAY
6-B2 CORE 3 TRASH CHUTE DOORS 12-3 FLOORS
-NEED TO REPAIR 12TH FLOOR WASH DOWN DOOR
-NEED TO REPAIR 11TH FLOOR TRASH CHUTE DOOR
-3RD,4TH,9TH AND 10TH FLOOR HOOPER DOORS DO NOT CLOSE AND LATCH

NOTE: LOADING DOCK OKAY FOR 4 SEASONS TO USE AS ONLG AS CONSTRUCTION PERSONNEL DOES NOT USE IT - ONCE CONSTRUCTION PERSONNEL USSES IT THEN 4 SEASONS WILL NOT BE ALLOWED TO USE IT UNTIL THEY GET A TCO IN THAT AREA

SRI FEES APPLY -- C.B.WOLFF -- 02/22/17



Date:

2/22/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


BUILDING 2 CORE 1

1-TRASH CHUTE DOORS FLOORS 11-3
-FLOORS 5,9 AND 10 NEED LABELS ON THE DOORS
-FLOORS 3,4,6,7,8 AND 11 - OKAY

BUILDING 2 CORE 2

1-TRASH CHUTE DOORS FLOORS 12-3
-FLOORS 10 AND 11 IN-OP
-FLOORS 5,6,8,9 AND 12 NEED LABELS ON THE DOORS
-FLOORS 3,4 AND 7 - OKAY

2-LOADING DOCK - ENGINEERING OFFICE NEEDS TO ADD STROBE
3-LOADING DOCK BACKOFFICE HALLWAY NEEDS TO BE FIRE CAULKED
4-MECHANIAL ACCESS DOOR DOES NOT CLOSE AND LATCH
5-NEED TO COVER ALL EXPOSED WIRES IN THE CARPENTRY SHOP
6-NEED TO HAVE A FIRE RATED LABEL FOR THE CARPENTRY SHOP DOOR
7-STAIRS ARE NOT UNIFORM BY THE CARPENTRY SHOP
8-MECHANIAL ROOM LOADING DOCK NEED TO CHANGE THE SPRINKLER HEAD UNDER A/C DUCT
9-CO DETECTORS FOR INDIVIDUAL GARAGES - OKAY
EXCEPT: PG 9 AND 11 IN-OP
10- KSF-4 DUCT DETECTOR - OKAY
11-NEED DOOR LABELS ON DOORS B2001E AND B2009
12-NEED LATEST APPROVED SET OF PLANS

SRI FEES APPLY -- C.B.WOLFF -- 02/21/17



Date:

2/18/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


FIRE FINAL CO DENIED

1-NEED TO FINISH WALL AT DUCT DETECTORS B1 - 15 & 16
2-NEED TO REMOVE ALL STORAGE FROM ALL MECHANIAL ROOM PER NFPA 1 1.14.4
3-NEED SIGNAGE FOR ALL ELECTRIAL AND MECHANIAL ROOMS PER NFPA 1.14.4
4-NORTH ENTRY TO GARAGE B2-S01 GREATER THAN 1/2" ELEVATION CHANGE
5-CO DETECTORS IN THE BASEMENT 1-14 - OKAY STILL NEED APPROVED PLANS AND NEED TO INSPECT THE OWNERS GARAGES

C.B.WOLFF -- 02/18/17



Date:

2/17/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


WALKED WITH OWNERSHIP FOR 1 HOUR TO DISCUSS VARIOUS ITEMS FOR PHASE 2 TCO

1-NEED SILCONE FOR HOOD IN THE POOL KITCHEN
2-NEED TO FIRE CAULK PCU ROOM
3-NEED SIGNAGE ABOVE CEILING ( 2 HOUR RATED WALL/NO PENTRATIONS)
4-NEED TO HAVE FIRE RATED LABELS ON ALL FIRE RATED DOORS

C.B.WOLFF -- 02/17/17



Date:

2/14/2017 

Inspector:

Kelvin Thompson (KET) 

Type:

209 - FIRE FINAL

Status:

2 - APPROVED PARTIAL


Item completed on list dated 2/4/17, buiding #2 core #1: Door #921, and #319
checked, okay.

Items completed 2/4/17 building #2 core #2. Item #8 okay, unit #617 okay. All other on list still pending.

Inspected Guard and hand rails on the unit balconies in Building #1 core #3 12th thru 3rd floors. All are okay except as mention on this report.

1. Floors 12th and 11th not ready for inspection. (recheck)
2. All E1 units need to close off an 8 inch opening, between the last sphere
and glass guardrail/wall. Located on the NW coner of balcony. 12th thru 3rd floors.
3. Missing a section of handrail in unit E-1 7th floor.
4. Units on 2nd thru 10th floor is missing a small section of handrail.
Per NFPA 101:7.2.2.4.4.7 New handrails shall be continuously graspable
along their entire length. Located on the NE corners of balcony.
5. Unit F1 4th floor has a broken glass guard rail, replace.
6. Unit E 2nd floor mssing handrail, westside balcony.



Date:

2/14/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


THIS INSPECTION WAS FOR A WALK WITH THE OWNERS REP,VP FROM COASTAL CONSTRUCTION AND THE BUILDING OFFICIAL FROM THE TOWN OF SURFSIDE.

WE WALKED THE BUILDING FOR 2 HOURS - IN ORDER TO MOVE FORWARD FOR PHASE 2.

1-NEED EMERGENCY LIGHTS IN ELECTRIC ROOM LOBBY B2 LEVEL PER NFPA 1 1.14.4
2-BUILDING 2 CORE 1
A)EXIT LIEHGT ON BATTERY BACK-UP - OKAY
3-STAIR 1 CORE 1 MISSING EXIT LIGHT PER PLANS
4-SPA EXIT LIGHT ARE NOT READY AT THIS TIME
5-BASEMENT CORE 2 - MISSING EXIT LIGHT
6-BUILDING 2 CORE 2
A)-STAIR 3 B 2 11TH FLOOR NEED TO REPAIR HANDRAIL GOING UP TO THE 12TH FLOOR
7-B2 CORE 2 - EXIT LIGHT/BATTERY BACK UP - OKAY
8-B2 CORE 3 - EXIT LIGHT/BATTERY BACK UP - OKAY

SRI FEES APPLY -- C.B.WOLFF -- 02/13/17



Date:

2/8/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


WALKED BUILDING 2 WITH THE CONSTRUCTION COMPANY AND OWNERSHIP FOR THE TCO AND WHAT IS NEEDED TO ACHIEVE THE TCO

C.B.WOLFF -- 02/07/17



Date:

2/6/2017 

Inspector:

Kelvin Thompson (KET) 

Type:

209 - FIRE FINAL

Status:

2 - APPROVED PARTIAL


1. Correction pertaining to item #6 2/6/17 Label breakers to read "S/A" not
EM.


This is the results of Saturday 4, 2017 inspection.

1. Building #2 Core #1 Fire alarm audibility speakers in the units, and smoke
alarms in the units. All testing is completed except, as mention in this
report.
2. 11th floor penhouse unit #3, speakers, not ready for testing.
3. Unit DSV10 smoke alarms not ready for testing.
4. Unit 9E smoke alarms not ready for testing.
5. Unit 721H smoke alarms not ready for testing.
6. Label all breakers in the electrical panels that control the Smoke alarms
"EM"
Building #2 Core #2 Fire alarm audibility speakers, and smoke alarm testing
in the units. All testing is completed except, as mention in this report.
7. 12th floor smoke alarms not ready for testing.
8. 11th floor smoke alarms and fire alarm speakers are not ready fortesting.
9. 10th floor smoke alarms not ready for testing.
10. Unit 915C smoke alarms not ready for testing.
11. 4th floor smoke alarms not ready for testing.
12. 3rd floor unitC not ready for speaker and smoke alarms.
13. 3rd floor unit #317 one speaker not working located in the corridor next to the laundry room.

This inspection was done on Monday 2/6/17

Building #2 Core #1 Inspection checking all fire rated doors for closing and
and latching properly. All testing completed except, as mention on this report

1. Recheck door penhouse north.
2. Recheck unit B2 ph3c 11th floor.
3. Recheck 10th floor stair #1 door.
4. Unit DSV10 recheck
5. 9th floor stair #2 door
6. Units 919, 921,821,721,719 back,622,619,422, and 421. Recheck these doors.
7. Trash room door 8th floor recheck.
8. Stair #1 6th floor door, recheck.
9. Stair #1 spa level door unable to access.

Building #2 Core #1 This inspection tested all Area of refuge two-way communication, speaker system. (only) from roof level to basement. All testing
completed except, as mention on this report.
1. Roof level speaker, is showing the location as the ground floor per the
monitored personnel. Reprogram showing the correct location as roof level.
(Retest)
2. 11th floor speaker is not working.
3. 3rd floor speaker shut off after the 1st recording. (retest)



Date:

2/4/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


CONTINUED INSPECTIONS FOR BUILDING 2 *** TENTATIVE LIST ***

1-NEED TO REMOVE TEMP. POWER SOURCE B2 S03 2ND FLOOR
2-NEED TO REPAIR DOOR AND REMOVE PVC B2 SO3 BASEMENT
3-NEED TO REMOVE PVC FROM LOBBY B2 S05
4-NEED TO REMOVE FOB @ LOADING DOCK TO ENTRANCE OF BUILDING
5-NEED TO FIRE CAULK SPRINKLER PIPE IN B2 S06 10TH FLOOR
6-NEED TO BLOCK UP STAIRWELL B2 S06 5TH FLOOR
7-NEED TO COVER PLUMBING PIPE IN 2 HOUR SOFFIT IN B2 S06 4TH FLOOR
8-NEED TO REMOVE HATCH DOOR B2 S06 4TH FLOOR
9-NEED TO COVER PLUMBING PIPE IN 2 HOUR SOFFIT IN B2 S06 3RD FLOOR
10-NEED TO PROVIDE A STAIRWELL DOOR B2 S06 2ND FLOOR

C.B.WOLFF -- 02/04/17



Date:

2/3/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


INSPECTIONS CONTINUED

1-NEED TO FIRE CAULK ALL DOORS IN BUILDING 2 S02 DUE TO TEMPORARY ELECTRIC BEING REMOVED PER NFPA 1 1.14.4

C.B.WOLFF -- 02/03/17



Date:

2/1/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


THE FOLLOWING ITEMS NEED TO BE CORRECTED

1-CLOSE STIRWELL B2-SO6 FLOOR 5 - OPENING
2-NEED TO REPAIR STAIR B2-SO6 FLOOR 5 2ND STEP
3-NEED TO REMOVE PLUMBING PIPE B2-SO6 FLOOR 4
4-NEED TO REMOVE PVC PIPE STAIR B2-SO5 FLOOR
5-NEED TO REMOVE FOB STAIR B2-SO5 - BASEMENT

C.B.WOLFF -- 01/31/17



Date:

1/30/2017 

Inspector:

Kelvin Thompson (KET) 

Type:

211 - PRELIMINARY

Status:

2 - APPROVED PARTIAL


Fire final partial inspection, checking fire rated labels on all fire doors
From the 12th to the 3rd floors.

Building #2 core #1
All fire rated door labels checked okay except, as mention on this report.
1. missing labels on all roof level (3)
2. Unable to open door at the 12th floor door B2 PH 4D. (recheck)
3. Paint on 10th floor trash chute door, fire rated label. (Recheck)
4. Unable to open the following doors: 921H,919E,821H,619B, and 319. (Recheck)

Building #2 core #2 12th to 3rd floors.
5. all Roof level fire doors missing labels.
6. Stair door at roof level missing label.
7. Unit 915C missing label
8. unable to open trash chute door on the 8th floor. (recheck)
9. Unit #617 unable to open door.

Building #2 core #3 12th to 3rd floor.
10. Missing label on door at the upper roof level elevator lobby door.
11. Stairwell #6 door on the 3rd floor missing label.



Date:

1/26/2017 

Inspector:

Kelvin Thompson (KET) 

Type:

209 - FIRE FINAL

Status:

2 - APPROVED PARTIAL


Fire alarm final partial inspection.
1. Location and candelas checked, okay in building #2 core #2 floors 12th thru
1st except as mention on this report.
2. The 12th and 11th floor apt units speakers need to be inspected, walls were
not installed yet.
3. Apt 4c elevator #6 lobby strobe, need to be replaced with a ceiling mount
device.
4. Apt 3c speakers not installed, no walls. Recheck.
5. All condo units in this core from the 12th to 2nd floor, have duct work
that penetrate the the units from the elevator lobbies. Each duct have a
mechanical fire damper attach to them, need to verify if they are part of
the smoke control system. If not that need to be tied to the FACP.



Date:

1/25/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


THIS NOTE IS FOR THE PROJECT AT SURF CLUB PER NFPA 101 7.1.3.2.1 (10)

1- THERE SHALL NOT BE ANY PENTRATIONS IN THE STAIRWELL EXCEPT THE FOLLOWING ITEMS IN PERIN (10) UNDER NFPA 101 7.1.3.2.1

C.B.WOLFF -- 01/24/17



Date:

1/14/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


FINAL CO DENIED **** B2 CORE 1 ****

1-AS STATED BEFORE ALL HANDRAILS SHALL CONFORM TO NFPA 1 1.14.4 AND NFPA 101
2-ALL STAIRS SHALL BE UNIFORM AS STATED BEFORE
3-NEED FIRE RATED LABELS ON ALL FIRE RATED DOORS
4-NEED SIGNAGE FOR ALL ELECGTRICAL/MECHANIAL ROOM DOORS
5-ROOF VFD ROOM - NEEDS DOOR
6-B2 STAIR 2 HANDRAIL AT TOP NEEDS TO BE RELOCATED - DO NOT HAVE 44"
7-SPRINKLER SIGNAGE FOR SPRINKLER SYSTEM IN STAIRWELLS
8-FIRE ALARM HAS NOT BEEN STESTED
9-NEED TO TEST THE PRV S IN B2
10-STAIR B2-S03 7TH AND 8TH FLOORS ARE UNEVEN - NOT UNIFORM
11-HANDRAILS/GUARDRAILS FOR BALCONY UNITS IN B2 - OKAY
12-B2 STAIR 2ND FLOOR LAST STEP 8 1/4" - CAN NOT BE MORE THAN 7" - ONCE AGIN UNIFORMITY
13-B2 STAIR 2 2ND FL - HOLE IN WALL BY STANDPIPE
14-B2-SO4 FL 2 NEED TO CORRECT THE LAST STEP
15-B2-S06 FL 3 WIDTH 32" - MUST BE MIN. 44"
16-B2-S06 FL 4 - NEED TO REPAIR HOLE IN WALL AND REPAIR HANDRAILS
17-FITNESS ROOM NOT READY - INCOMPLETE STILL UNDER CONSTRUCTION

SRI FEES APPLY -- C.B.WOLFF -- 01/14/17



Date:

1/11/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


TCO RECOMMENDED FOR PHASE 1 AREAS

1-FLOORS 5-12 HOTEL ONLY,PEACOCK ALLEY,LOUNGE BAR,RESTAURNT LOBBY,SHOW KITCHEN, 4 SEASONS KITCHEN AND BACK OF HOUSE OFFICES
2-RECOMMENDED FOR 90 DAYS
3-GO TO 11805 SW 26TH STREET AND HAVE CAPTAIN SIGN SURFSIDE TCO FORM
4-NEED HOLD HARMLESS LETTER ON OWNERS LETTER HEAD AND MUST BE NOTERIZED

NOTE: ALL FEES MUST BE PAID BEFORE TCO WILL BE CONSIDERED
OWNERS REP: ORLANDO CARRILLO 305 632-7921

SRI FEES APPLY -- C.B.WOLFF -- 01/10/17



Date:

1/7/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


TCO DENIED

1- NEED TO CORRECT THE AREA OF REFUGE AND IT MUST WORK PROPERLY IN ORDER TO GET THE TCO FOR THE FIRST PHASE OF THE HOTEL BUILDING 2
2-ALL OTHER AREAS HAVE BEEN SATISIFIED

SRI FEES APPLY -- C.B.WOLFF -- 01/07/17



Date:

1/6/2017 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


WALKED WITH THE OWNERS REP,PROJECT MANGER AND THE CONSULTANT CONCERNING TCO FOR THE HOTEL ONLY

1-EXPLAINED THAT HAND/GUARD RAILS MUST BE INSTALLED
2-EXPLAINED THAT ALL TRIPPING HAZARDS MUST BE CORRECTED
3-EXPLAINED THAT ALL FIRE EXTINGUISHERS MUST BE IN PLACE
4-EXPLAINED THAT ALL BARRIERS SHALL BE IN PLACE FOR TCO
5-EXPLAINED THAT ALL DOORS THAT ARE NOT EXITS SHALL HAVE SIGNAGE STATING SUCH

SRI FEES APPLY -- C.B.WOLFF -- 01/06/17



Date:

1/5/2017 

Inspector:

Kelvin Thompson (KET) 

Type:

209 - FIRE FINAL

Status:

2 - APPROVED PARTIAL


Witnessed the stair B2-s08 pressurization fan fault signal cleared within 24
seconds. Item on LT. Wolff list. Tested, okay.



Date:

12/29/2016 

Inspector:

Kelvin Thompson (KET) 

Type:

211 - PRELIMINARY

Status:

2 - APPROVED PARTIAL


1. Life safety partial inspection.
Stairs, in the peacock alley, and hotel building:
2. Main entrance in peacock alley, stairs missing handrails.
3. Provide handrails on bothsides of ramp on the westside of peacock alley.
(Ground floor level.)
4. Missing handrails on the Grand stairs to beach. (south set)
5. Grand stairs (North) are still under contruction.
6. Missing one handrails on steps in peacock alley. (steps to mezzaine)
7. Stair #8 3rd floor exit door need an exit light above door. per NFPA 101:
7.10.1
8. Stair #1 B-5 2nd floor two doors need a sign that read NOT AN EXIT. This
will prevent confusion to exit.
9. Missing EM light (Not working) in stair #7 half landing between floors 3
and 1.
10. All other handrails checked, okay.



Date:

12/28/2016 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


FIRE FINAL DENIED

1-BASEMENT KITCHEN OKAY - NEED PERMIT NUMBER TO FINAL
2-DOORS THAT STILL HAVE PROBLEMS
DOOR 1203 LABEL
SERVICE LOBBY DOORS - 11R,10R,9R,8R,7R AND 5R
DOOR 1006 NEED HARDWARE
DOOR 705,605 AND 506 FOYER DOORS DO NOT CLOSE AND LATCH
DOOR B2 4TH FLOOR STAIR DOES NOT CLOSE AND LATCH
DOOR 7 FITNESS STAIR DOES NOT CLOSE AND LATCH
DOOR B5 SO1 STAIR DOES NOT CLOSE AND LATCH
3-STAIR UNIFORMITY
4-PAGE B2-A3.04 NEEDS TO BE REVISED

SRI FEES APPLY -- C.B.WOLFF -- 12/28/16



Date:

12/23/2016 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


FIRE FINAL CO DENIED

**** ITEMS CORRECTED FROM PREVIOUS LISTS ****

1-EXIT LIGHTS IN STIRWELLS AT GROUND LEVEL
2-F/A DEVICES IN HOTEL ROOF MECHANICAL ROOM
3-MECHANICAL ROOM NEEDS TO BE 2 HOUR RATED ENCLOSER
4-PULL STATION IN FACP ROOM - NEEDS TO BE TESTED
5-CONDUIT IN HOTEL HAS BEEN MOVED
6-REPEATER ROOM NOW HAS A S/D ON ROOF LEVEL
7-SCUPPERS ON ROOF AND SPACE BEHIND UPTURNED BEAM IS OKAY
8-F/A SPEAKERS HAVE BEEN INSTALLED ON FLOOR 9-12
9-EXIT LIGHTS BOH ON FLOORS 5-12 HAVE BEEN RAISED
10-BOH FIRE RATED WALLS HAVE BEEN FIRE CAULKED 5-12
11-BOH NOW HAS FLOORING ON FLOORS 5-8

SRI FEES APPLY -- C.B.WOLFF -- 12/23/16



Date:

12/22/2016 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


FIRE FINAL CO DENIED

1-GENERATOR TRANSFERED WITH IN 10 SEC. - OKAY
2-DOORS ON FLOORS THAT DO NOT WORK PROPERLY
3-5-7 & 9 ALL IN-OP
4-DOORS THAT DO NOT CLOSE AND LATCH - 1201,1109,1106,1105,1005,1006,1008,806,801,802,804,805 & 807
5-DOORS WITH NO LABELS - 1203 AND 8TH FLOOR ELECTRIAL BOH

SPRINKLERS - OPEN PARKING AREA BASEMENT ONLY

1-ZONE 4 SPRINKLER ROUGH AND PRESSURE - OKAY
2-NEED TO ADD SPRINKLER HEADS IN PEACOCK ALLEY BASEMENT
3-NEED TO REVISE PLANS IN PARKING GARAGE
4-NEED TO FIRE CAULK POOL EQUIPMENT ROOM
5-NEED TO RAISE SPRINKLER HEAD IN TRASH ROOM B1 CORE 3
6-SITE LIGHTING DIMMER CLOSET NEED TO ADD SPRINKLER HEAD IN BASEMENT

SRI FEES APPLY -- C.B.WOLFF -- 12/21/16



Date:

12/21/2016 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


FIRE FINAL CO DENIED

1-SMOKE CONTROL OKAY FOR FLOORS 5-12
2-STAIR B2-S08 -- SPH-H-L FAULT - NO POWER
3-AREA OF REFUGE FAILED
4-NEED TO FIRE CAULK STAIRWELLS
5-NEED TO RAISE TEST ORFICE IN STAIRWELLS
6-SMOKE DOORS DO NOT CLOSE AND LATCH ON FLOORS 5-12

SRI FEES PPLY -- C.B.WOLFF -- 12/20/16



Date:

12/14/2016 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


THIS INSPECTION WAS FOR TCO HOTEL AREAS ONLY

1-NEED STEPS AND RAILS AT BUILDING 2 LOADING DOCK
2-NEED TO INSTALL CADDIE BARS FOR ALL S/D S IN THE BASEMENT
3-NEED TO DO A SPRINKLER FINAL FOR ALL AREAS FOR THE HOTEL
4-NEED TO DO A LIFE SAFETY INSPECTION BEFORE A TCO WILL BE CONSIDERED
5-NEED RAILINGS FOR HANDICAP RAMP AT THE HOTEL
6-NEED LATEST SET OF APPROVED LIFE SAFETY PLANS
7-NEED LIGHTING FOR THE OUTSIDE
8-NEED TO MOVE EXIT LIGHTS THROUGHOUT IF NOT SEEN DUE TO OBSTRUCTIONS - NEED VISIBILITY FOR THE EXIT LIGHTS

SRI FEES APPLY -- C.B.WOLFF -- 12/14/16



Date:

12/9/2016 

Inspector:

Kelvin Thompson (KET) 

Type:

209 - FIRE FINAL

Status:

2 - APPROVED PARTIAL


1. Life safety partial inspection completed.
2. All units doors fire rated labels checked, OKAY on the 12,10,9,8, and 7th
floors.
3. All smoke detectors, were relocated to permanant ceiling per LT wolff s
list dated 11/10/16 on floors:12,10,9,8, and 7th OKAY.
4. Units 809 and 709 strobes were relocated away from the S/D OKAY. Per List
dated 11/10/16.



Date:

11/17/2016 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


CONTINUED WALKING THROUGH THE B2 HOTEL

1-EXIT LIGHTS SHALL BE HAVE BATTERY BACK-UP PER NFPA 101 7.9.2.3
2-LIGHTS IN THE FOYER/VESTIBULE SHALL BE ON 2 LIGHTING CIRCCUITS PER NFPA 101 7.9.2.3
3-UNIT DOORS 502,601 AND 602 DO NOT HAVE FIRE RATED DOOR TAGS FOR FLOORS 5-9 ONLY

SRI FEES APPLY -- C.B.WOLFF -- 11/16/16



Date:

11/10/2016 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


CONTINUED TO KEEP WALKING THE BUILDING 2 HOTEL

1-SPRINKLER FINAL APPROVED FOR FLOORS 5-9 ONLY FOR THE UNITS AND COMMON AREAS ONLY
2-NEED TO RELOCATE STROBE IN UNITS 709 AND 809 DUE TO SPRINKLER HEAD IS BEING UBSTRUCTED PER NFPA 13 8.1.1
3-NEED TO SECURE ALL S/D S ON FLOORS 5-12 IN THE VESTIBULE/FOYER IN BUILDING B2 HOTEL
3-NEED TO HAVE EXIT LIGHTS WITH BATTERY BACK-UP PER NEC 70
4-NEED TO HAVE VESTIBULES/FOYERS ON 2 LIGHTING CIRCUITS - ONE ON NORMAL LIGHTING AND THE OTHER ON EMERGENCY LIGHTING

SRI FEES APPLY -- C.B.WOLFF -- 11/10/16



Date:

11/8/2016 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


BELOW COMMENTS ON INSPECTION DATE 11/07/16 BELONG UNDER THE FIRE ALARM PERMIT 2016042208

C.B.WOLFF -- 11/08/16



Date:

11/8/2016 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


FIRE ALARM DENIED

1-NEED TO INSTALL CORRECT SIZE BATTERIES FOR THE FACP PER TNE PLANS
2-NEED TO HAVE PHONE LINES INSTALLED TO FINISH TESTING OF THE FIRE ALARM
3-NEED TO HAVE CENTRAL STATION CONNECTED TO THE PHONE LINES
4-NEED TO REVISE PLANS TO SHOW WHERE THE NEW EOL S ARE - THEY HAVE BEEN MARKED ON THE PLANS
5-STILL NEED TO INSTALL SPEAKERS IN UNITS 1006,1109 AND 1201
6-ALL SPEAKERS ON FLOORS 5-12 SOUNDER BASE OKAY EXCEPT THOSE IN ITEM 5
7-POWER BOOSTERS 37,38,39 AND 40 WERE CHECKED FOR GROUND FAULT,BATTERIES AND BREAKER ALL OKAY
8-NEED TO ADD S/D IN REPEATER ROOM ON THE ROOF
9-CHECKED NAC CIRCUITS ON FLOORS 5-12 -> OKAY
10-NEED TO SECURE S/D S IN ALL CORNER VESTIBULES PER NFPA 72 4.4.4.2

SRI FEES APPLY -- C.B.WOLFF -- 11/07/16



Date:

11/3/2016 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


FIRE FINAL CO DENIED

1-BUILDING 2 HOTEL - STAIRWELL DOORS
A-12TH FLOOR STAIR 7 AND 8 FAILED
B-11TH FLOOR STAIR 7 AND 8 OKAY
C-10TH FLOOR STAIR 7 OKAY STAIR 8 FAILED
D-9TH FLOOR STAIR 7 AND 8 FAILED
E-8TH FLOOR STAIR 7 AND 8 OKAY
F-7TH FLOOR STAIR 7 AND 8 OKAY
F-6TH FLOOR STAIR 7 AND 8 OKAY
G-5TH FLOOR STAIR 7 OKAY STAIR 8 FAILED

ALL DOORS FLOORS 5-12 STAIRWELLS HAD FIRE RATED LABELS

2-NEED TO SECURE ALL S/D S ON ALL FLOORS IN THE CORNER VESTIBULES
3-11TH AND 12TH FLOOR S/D S IN VESTIBULES WORK OKAY

SRI FEES APPLY -- C.B.WOLFF -- 11/02/16



Date:

10/18/2016 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


WALKED THE ROOF WITH PETE,JOSE AND JEFF

1-THEY HAD CONCERNS OVER THE FIRE ALARM PLACEMENT OF THE H/S S AND EXIT LIGHTING
2-THERE WERE VARIOUS AREAS IN WHICH WE ADDED EXIT LIGHTS PER NFPA 101 7.10.1.2
3-THERE ARE ALSO CONCERNS OVER THE DISTANCE OF THE GUARDRAILS FROM THE STRUCTURE - PER NFPA 101 7.2.2.4.5.3 YOU CAN NOT HAVE MORE THAN 4" FROM THE STRUCTURE - THERE ARE MANY PLACES WHICH EXCEEDS 6 1/2" - NEED TO CORRECT
4-THERE ARE VARIOUS AREAS ALSO ON THE ROOF WHICH HAS 12" X 12" OPENINGS BY THE GUARDRAILS WHICH NEED TO BE CORRECTED SINCE THE ROOF IS FOR OWNERS OF THE PENTHOUSES PER NFPA 101 7.2.2.4.5.3

SRI FEES APPLY -- C.B.WOLFF -- 10/17/16



Date:

10/4/2016 

Inspector:

Kelvin Thompson (KET) 

Type:

211 - PRELIMINARY

Status:

2 - APPROVED PARTIAL


1. Witnessed the generator load bank test on the south side of the building
600 KW generator, okay.
2. Provide the following signage per NFPA 110:
(A) No smoking
(B) 704 placard identifying fuel type.
(C) Directing signage showing the location of the generator remote shut
off switch.
(D) KW capacity (600) on the outside of
3. Still need to test the generator remote shut off switch, it was not ready
for testing.



Date:

10/1/2016 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


WALKED THE (B2-HOTEL) WITH PETE BERTOT

1-WALKED THE 11TH AND 12TH FLOOR BALCONIES ALL BALCINIES OKAY
EXCEPT: UNIT 1104 - HAD GREATER THAN 4" SEPERATION ON THE NORTH SIDE PER NFPA 101 7.2.2.4.5.3
2-9TH FLOOR SPRINKLERS IN ELEVATOR LOBBY - THE CEILING HAS BEEN CHANGED FROM A SOLID CEILING TO A CRIS CROSS CEILING - NEED TO CHECK ON THE OBSTRUCTION PER NFPA 13 8.1.1
3-TRASH ROOM B2035 HAS A ROLL UP DOOR THE ROOM IS 2HOUR FIRE RATED AND DOES NOT HAVE A FUSIBLE LINK TO PROTECT THE CORRIDOR PER NFPA 1 1.14.4

SRI FEES APPLY -- C.B.WOLFF -- 10/01/16



Date:

9/20/2016 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


WALKED BUILDING 2 WITH THE PROJECT MGR - PETE BERTOT

1-ZONE 5 SPRINKLER ROUGH AND PRESSURE APPROVED
2-OKAY TO CLOSE UP THE CEILING FOR ZONE 5 ONLY
3-PEACOCK ALLEY (2) SPRINKLER ROUGH DENIED
4-NEED TO ADD SURGE PROTECTORS TO THE SPRINKLER SYSTEM OR BRING THE ALL-THREAD RODS TO THE SPRINKLER PIPE PER NFPA 13 8.1.1

SRI FEES APPLY -- C.B.WOLFF -- 09/19/16



Date:

9/17/2016 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


1-WALKED THE B2 BUILDING - HOTEL/CONDOHOTEL AND (2) CONDO BUILDINGS
2-NEED TO INSTALL ROOF MANIFOLDS ON EAST SIDE OF BUILDING AS PER PLANS NFPA 13 AND NFPA 1 1.14.4
3-NEED TO INSPECT SPRINKLER SYSTEM ON ROOF UNDER WOOD DECKING PER NFPA 13 8.1.1
4-NORTH SIDE ZONE 5 ROUGH OKAY FOR 1ST 3 LINES ON THE NORTH SIDE ONLY
5-BUILDING 1 3RD FLOOR UNIT (C) ROUGH AND PRESSURE - OKAY
6-NEED TO CHECK ON THE GENERATOR INSTALLATION PLANS TO SEE IF IT HAS BEEN INSTALLED CORRECTLY
7-NEED TO COVER EXHAUST PIPE FOR THE GENERATOR
8-NEED TO INSTALL (2) WAY COMMUNICATION PROPERLY - IT SHALL NOT IMPEDE THE MEANS OF EGRESS FOR ADA PURPOSES AND IF INSTALLED YOU NEED TO INCREASE THE LANDING OR MUST BE REMOVED PER NFPA 1 1.14.4

SRI FEES APPLY -- C.B.WOLFF -- 09/17/16



Date:

8/25/2016 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


WALKED BUILDING WITH PETE BERTOT - HE VARIOUS QUESTINS ABOUT ROLL UP OVERHEAD DOORS AND WANTED TO DO A SPRINKLER ROUGH ON VARIOUS FLOORS BUT ALL THE FLOORS WERE ALREADY ROCKED.

SRI FEES APPLY -- C.B.WOLFF -- 08/25/16



Date:

8/22/2016 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


PRILIMARY INSPECTION FOR HOTEL AND CONDO

1-HOTEL FLOORS 6 AND 7 DISCUSS (2) EXIT LIGHTS IN THE VESTIBULE FOR UNITS 601 AND 701 APPROVED DUE TO THE AREA THAT THEY ARE ON - ON THE PLANS MOVED TO ANOTHER WALL PER LEAD INSPECTOR
2-CONDO CORE 1 AND 2 -> FLOORS 2-7 HANDRAILS AND GUARDRAILS OKAY
3=TK - ZONE2 BASEMENT AND 1ST FLOOR - GREY BOX AREA OKAY TO CLOSE AND NOT INCLUDE IN THE ORGINAL TCO WHEN APPROVED

SRI FEES APPLY -- C.B.WOLFF -- 08/22/16



Date:

8/19/2016 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


WALKED WITH THE OWNERS REP AND THE PROJECT MGR FOR THE SPA AREA (B2)

1-NEED TO DISCUSS 2 WAY COMMUNICATION/AREA OF REFUGE FOR STAIRWELLS -THEY HAVE AREA OF REFUGE ON EVERY 5 FLOOR OF THE CROSS OVER IN THE STAIRWELLS ?
2-NEED TO ADD SPRINKLER HEADS AROUND THE GLASS IN THESPA OR ADD WALLS FOR NO ACCESS
3-NEED TO MOVE SPRINKLER HEAD IN PHONE ROOM (IT) IN SPA
4-NDD TO ADD (1) SPRINKLER HEAD IN A/C ROOM IN SPA
5-PRESSURE TEST FOR SPA AREA OKAY
6-CHECKED ON PLACEMENT OF EXIT LIGHTS IN THE SPA

SRI FEES APPLY -- C.B.WOLFF -- 08/18/16



Date:

8/17/2016 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


NEED TO ADDRESS THE PIPING FOR THE AREA OF REFUGE AND THE HANDRAILS IN THE STAIRWELLS FOR CLEARANCE

C.B.WOLFF -- 08/16/16



Date:

8/16/2016 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


DID AN INSPECTION ON THE CONDO HOTEL -CORE 3 SOUTH

1-FLOORS 4-7 GUARD/HANDRAILS ON BALCONIES
2-NEED TO CHECK ON GLASS WIDTH ABOVE HANDRAILS - GLASS WIDTH MEASURES FROM 4 TO 6 INCHES ABOVE THE HANDRAILS
3-NEED TO CHECK IN THE STAIRWELLS FOR LIGHTING THAT HAS PVC PIPING INSTEAD OF (EMT) THE PVC PIPING DOES NOT HAVE A 2 HOUR RATING
4-GUARD/HANDRAILS BELOW THE HANDRAILS ARE WITHIN THE 4 INCH SPHERE

SRI FEES APPLY -- C.B.WOLFF -- 08/16/16



Date:

8/5/2016 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


walked the arch lounge and various areas with michael awaud and jorge from rodel sprinkler co.

1-arch lounge zone 5 sprinklers are - okay
2-need water curtin for 3rd floor means of egress east side hotel for all windows per nfpa 13 8.1.1
3-need to install all roof manifolds per approved sprinkler plans - nfpa 13 8.1.1
4-also discussed area of refuge piping in the stairwells - per the approved plans the area of refuge piping is okay

c.b.wolff -- 08/05/16



Date:

7/28/2016 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


walked with both project mgr. to discuss many issues concerning the stairwells, mechanial rooms and openings in the stairwells and sprinklers in the historical areas

c.b.wolff -- 07/28/16



Date:

7/23/2016 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


THIS WALK THROUGH WAS FOR THE ROOF MANIFOLDS AND HOSE CONNECTIONS FROM THE ROOF

1-NEED TO MOVE HOSE CONNECTIONS IN THE STAIRWELLS ON THE ROOF IN THE 3 CORES PER NFPA 13 8.1.1
2-NEED TO REMOVE ALL PLUMBING IN THE STAIRWELLS PER NFPA 1 1.14.4
3-STAIRWELLS 1-4 BUILDING 2 - OKAY
4-SOUTH BUILDING STILL NEEDS TO ADD SPRINKLER HEADS ON THE 1ST FLOOR OVERHANG
5-SPRINKLER HEADS IN THE CONDO HOTEL MUST HAVE 18" OF CLEARANCE AND YOU CANNOT HAVE SOLID SHELVING PER NFPA 13 8.1.1


SRI FEES APPLY -- C.B.WOLFF -- 07/23/16



Date:

7/19/2016 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


INSPECTION FOR THE STAIRWELLS CONTINUED

1-WALKED BUILDING 2
2-WALKED STAIRWELL 5 AND 6 -> MINOR ISSUES
3-WALKED STAIRWELL 1-4 FOR ITEMS FOUND ON PREVIOUS INSPECTIONS AND ALL ITEMS WERE CORRECTED
4-STILL NEED TO WALK STAIREWLLS FOR GUARDRAILS AND HANDRAILS

SRI FEES APPLY -- C.B.WOLFF -- 07/19/16



Date:

7/14/2016 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


THIS INSPECTION WAS FOR THE STAIRWELLS 7 AND 8 WITH THE PROJECT MGR.

ALSO, WALKED THE HOTEL LOBBY AREAS TO SEE IF THE F/A DEVICES ARE OKAY

WALKED THE BASEMENT AREA AND ADVISED THE PROJECT MGR. THAT THEY NEED TO INSTALL SPRINKLERS (ASAP) DUE TO THE STORAGE OF CONST. MATERIAL WHICH IS FLAMMABLE

SRI FEES APPLY -- C.B.WOLFF -- 07/14/16



Date:

5/20/2016 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


Reults from Partial Stair Riser inspection with Inspector Wolff, MDFD. 5/20/16


Floors Stair B2-S1 Stair B2-S2 Stair B2-S3 Stair B2-S4

Roof-12 Stair to roof deck-needs 2" Nosing in yellow No landing Stair to roof deck-needs 2" Nosing in yellow No Landing
12-11 No issue No Issue Adjust treads No Issue
11-10 No issue No Issue No Issue No Issue
10-9 Float landing and mid-landing Float Landing Adjust risers Float Landing
9-8 Float landing Float Landing No Issue Float Landing
8-7 Float landing Float Landing No Issue Float Landing and Nosings
7-6 Float landing Float Landing No Issue Float Landing
6-5 Float landing Float Landing No Issue Float Landing
5-4 Float landing Float Landing No Issue Float Landing
4-3 Float landing and repair nosing where chipped Float landing No Issue
3-2 Float landing Float Landing Float landing No Issue
2-1 2nd tread pitches, needs floating to level out Lowest step is 8-3/4" for Tile? Float landing and chipped nosings Float landing has Dip
1-Basement Clean low nosing No Issue Float landing and chipped nosings No Issue

sri fees apply -- c.b.wolff -- 05/20/16









Date:

10/16/2015 

Inspector:

Curtis Wolff (WOLFFC) 

Type:

211 - PRELIMINARY

Status:

3 - REJECTED NOT TO CODE


PRIMILARY WALK THRU WITH THE PROJECT MANAGER AND OWNERS REP FOR BUILDING 2

SEE MASTER REPORT ON FILE

SRI FEES APPLY -- C.B.WOLFF -- 10/16/15