Inspection Result Comments

Wednesday, October 28, 2026

Permit Number:  2020056405


Date:

10/28/2025 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

208 - FIRE TCO INSPECTION

Status:

2 - APPROVED PARTIAL


Remaining items for code reference for elevator machine room

(4) no materials, unrelated to elevator equipment our permit to be stored in elevator machine rooms, machinery spaces, control rooms, control spaces or hoistway of traction elevators



(5) the elevator machinery is not of the hydraulic type


***ENTERED UNDER 208 TCO DUE TO FEES BEING OWED UNABLE TO ENTER UNDER 209 FINAL***

PERMIT 2020056405
17975 COLLINS AVE
THE ESTATES OF ACQUALINA NORTH TOWER


1. SPRINKLER FINAL PARTIAL APPROVAL

2. NEED TO UPDATE THE PERMIT FOR FINAL TO REFLECT THE CORRECT ADDRESS

3. NEED TO PROVIDE ORIGINAL APPROVED PLANS, LOG BOOK AND THE MOST RECENT SET OF REVISED PLANS THAT HAVE BEEN APPROVED BY FIRE FOR REVIEW

4. VERIFIED THE FOLLOWING ITEMS AND UNITS FROM THE PREVIOUS LIST DATED 8/5/24

UNITS 901,1001,2401,3501,3001,4001,4102, ARE ALL APPROVED FOR FINALS

THE FOLLOWING UNITS ARE CUSTOM UNITS THAT ARE OK FOR FINAL DUE TO HAVING SEPARATE BUILDOUT PERMITS

-3201 PENDING BUILDOOUT PERMIT

-3501 REVISION OF PLANS

-FLOOR 47 SPRINKLER PERMIT 2024045248 (APPROVED)

-FLOOR 49 SPRINKLER PERMIT 2024045268 (APPROVED PENDING FEES)

5. THE FOLLOWING ARE STILL PENDING FROM 8/5/24

-1501, 2501,2702,3001, 4202

6. UNIT 3801 DUE TO CUSTOM CLOSETS IN ALL CLOSETS, SPRINKLERS ARE BEING OBSTRUCTED.

7. FL 55 PENDING ELEVATOR MACHINE ROOM
NEED TO PROVIDE PROOF THAT THE MACHINE ROOM COMPLIES WITH NFPA 13:8.15.5.3

AUTOMATIC SPRINKLERS SHALL NOT BE REQUIRED IN ELEVATOR MACHINE ROOMS, EELEVATOR MACHINERY SPACES, CONTROL SPACES, OR HOISTWAYS OF TRACTION ELEVATORS INSTALLED IN ACCORDANCE WITH THE APPLICABLE PROVISIONS IN NFPA 101, OR THE APPLICABLE BUILDING CODE, WHERE ALL OF THE FOLLOWING CONDITIONS ARE MET:
(1) THE ELEVATOR MACHINE ROOM, MACHINERY SPACE, CONTROL ROOM, CONTROL SPACE, OR HOISTWAY OF TRACTION ELEVATOR IS DEDICATED TO ELEVATOR EQUIPMENT ONLY.

(2) THE ELEVATOR MACHINE ROOM, MACHINE ROOM, MACHINERY SPACE, CONTROL ROOM, CONTROL SPACE, OR HOISTWAY TRACTION ELEVATORS ARE PROTECTED BY SMOKE DETECTORS, OR OTHER AUTOMATIC FIRE DETECTION, INSTALLED IN ACCORDANCE WITH NFPA 72

(3) THE ELEVATOR MACHINERY SPACE, CXONTROL ROOM, CONTRIL SPACE, OR HOISTWAY OF TRACTION ELEVATORS SEPARATED FROM THE REMAINDER OF THE BUILDING BY WALLS AND FLOOR/CEILING ASSEMBLIES HAVING A FIRE RESISTANCE RATING OF NOT LESS THAN THAT SPECIFIED BY THE APPLICABLE CODE

WILL NEED TO PROVIDE PROOF AND THIS SHALL BE NOTED ON THE PLANS

8. ALL SIGNAGE FROM THE PENDING LIST SHALL BE VERIFIED

9. NEED TO VERIFY ALL OTHER PENDING ITEMS

10. SRI FEES APPLY
T. JABALI
10/27/25





Date:

8/5/2024 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


**ENTERED UNDER COMMENTS ONLY DUE TO REINSPECTION FEES BEING OWED**

PERMIT 2020056405
17901 COLLINS AVE
THE ESTATES OF ACQUALINA
NORTH TOWER ONLY

1. INSPECTION TO GO THROUGH ALL INSPECTIONS TO VERIFY ALL FINALS

2. ALL SPRINKLER FINALS HAVE BEEN VERIFIED AND COMPLETED EXCEPT FOR THE FOLLOWING:

901
1001
1501
2401
2501
FLOOR 27
FLOOR 30
3201
3501 REVISION OF PLANS
3801
4001
4102 PARTIAL RELOCAATE HEAD IN SMALL MB CLOSET 4" FROM WALL, REPLACE PAINTED HEAD IN MASTER SHOWER
4202 PARTIAL FIX GAP AROUNG ESC PLATE IN MASTER SHOWER
FLOOR 47
FLOOR 49
FL 55 PENDING ELEVATOR MACHINE ROOM

2. SRI FEES APPLY



Date:

1/11/2024 

Inspector:

John Molnar (MOLNAR) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


2020056405

Sprk final approved for 48th floor build out
Log book signed

Inspection entered as comments only due to fees being owed



Date:

1/10/2024 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

209 - FIRE FINAL

Status:

2 - APPROVED PARTIAL


Permit 2020056405
17901 Collins Ave
The Estates of Acqualina North Tower

1. Sprinkler final approved for unit 4501 and elevator lobby

2. Verified sprinkler rough, pressure and fire caulking approvals all areas

3. Unit 4502, elevator lobby and BOH was approved 4/26/23




Date:

1/9/2024 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

209 - FIRE FINAL

Status:

2 - APPROVED PARTIAL


Permit 2020056405
17901 Collins Ave
The estates of Acqualina
North Tower

1. Sprinkler final partial approval

2. Sprinkler final approved for floor 46 North Tower

3. Verified all rough, pressure and fire caulking for all areas



Date:

1/8/2024 

Inspector:

John Molnar (MOLNAR) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
17901 COLLINS AVE , Sunny Isles Beach

Level 47 rough pressure fire caulking ok
Log book signed

Pending issue unit 401 shadow area in kitchen has been eliminated
Plans log book signed



Date:

12/19/2023 

Inspector:

John Molnar (MOLNAR) 

Type:

209 - FIRE FINAL

Status:

2 - APPROVED PARTIAL


2020056405
17901 COLLINS AVE , Sunny Isles Beach

Disregard previous entry
This was a Sprk final approved for unit 37 combo
Jabali gave it a partial final on 12/14/23



Date:

12/19/2023 

Inspector:

John Molnar (MOLNAR) 

Type:

209 - FIRE FINAL

Status:

2 - APPROVED PARTIAL


2020056405
17901 COLLINS AVE , Sunny Isles Beach

Sprk rough approved



Date:

12/14/2023 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

209 - FIRE FINAL

Status:

2 - APPROVED PARTIAL


PERMIT 2020056405
17901 COLLINS AVE , Sunny Isles Beach
THE ESTATED OF ACQUALINA NORTH TOWER


1. SPRINKLER FINAL PARTIAL APPROVAL FOR FLOOR 37 COMBO UNIT

2. ALL AREAS OK EXCEPT FOR THE 2 ELECTRICAL ROOMS AND 2 LAUNDRY ROOMS
NEED TO INSTALL ALL ACOUSTICAL CEILING TILE

3. VERIFIED PRESSURE ON THE SYSTEM OK

4. VERIFIED ROUGH, PRESSURE AND FIRE CAULKING APPROVAL. APPROVED BY LT. MOLNAR 5/8/21



Date:

11/28/2023 

Inspector:

John Molnar (MOLNAR) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
17901 COLLINS AVE , Sunny Isles Beach

Sprk rough inspection was done on 11/14/23 by Jabalie
The pending items from that inspection has been completed and ok



Date:

10/13/2023 

Inspector:

Javier Ginoris (E160215) 

Type:

209 - FIRE FINAL

Status:

2 - APPROVED PARTIAL


Permit #2020056405
17901 COLLINS AVE
Unit #3602

*** Fire Sprinkler Final-Partial Approval ***

1. Final for Unit #3602 verified done OK.

10-13-23
Lt. Ginoris



Date:

9/27/2023 

Inspector:

Marc Harrison (E88884) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


2020056405
17901 COLLINS AVE , Sunny Isles Beach
ACQUALINA NORTH TOWER
CARLOS JARQUIN
786-357-2817

Sprinkler final approved for both full units on 21st and 22nd floors including the back-of-the-house only.

Lt. Harrison
9.27.23



Date:

9/26/2023 

Inspector:

Steven  Clements (E164643) 

Type:

209 - FIRE FINAL

Status:

2 - APPROVED PARTIAL


2020056405
ACQUALINA NORTH TOWER
17901 COLLINS AVE , Sunny Isles Beach

***North Tower***
***Floors 51 & 52 Only***

1. Sprinkler final approved for shell conditions for floors 51 & 52. Revised plans is approved and verified.

Lt. B. Stark
Lt. S. Clements



Date:

9/22/2023 

Inspector:

Byron Kappes (E153438) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


2020056405

Acqualina North Tower
17901 COLLINS AVE
Sunny Isles Beach

Sprinkler final not approved.

1. Per request of the contractor performed inspections on both floors 21 and 22. Multiple sprinklers had gaps around escutcheon plates. Seal gaps and reschedule inspection.

Lt B. Kappes



Date:

6/14/2023 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2020056405
177901 COLLINS AVE

1. SPRINKLER FINAL PARTIAL APPROVAL

2. SPRINKLER FINAL APPROVED FOR UNIT 4301 ONLY

3. VERIFIED PRESSURE ON THE SYSTEM

4. VERIFIED ALL SPRINKLER ROUGH AND PRESSURE APPROVALS FOR FLOOR 43

5. SRI FEES APPLY



Date:

5/15/2023 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

209 - FIRE FINAL

Status:

2 - APPROVED PARTIAL


PERMIT 2020056405
17901 COLLINS AVE
THE ESTATES OF ACQUALINA
NORTH TOWER

1. SPRINKLER FINAL PARTIAL APPROVAL FOR THE FOLLOWING UNITS

2. 4601, 4602 AND 4501 OK FOR BUFFER FLOORS.
SPRINKLER FINAL REWUIRED ONCE PAINTING HAS BEEN COMPLETED

3. COMBO UNIT 901 AND 1001 OK FOR SPRINKLER FINAL

4. VERIFIED ALL ROUGH, PRESSURE AND FIRE CAULKING FOR THE ABOVE UNITS

5. SRI FEES APPLY



Date:

5/8/2023 

Inspector:

John Molnar (MOLNAR) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
17901 COLLINS AVE , Sunny Isles Beach

37 floor combo unit Rough pressure fire caulking ok



Date:

4/26/2023 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

209 - FIRE FINAL

Status:

2 - APPROVED PARTIAL


PERMIT 2020056405
17901 COLLINS AVE
THE ESTATES OF ACQUALINA
NORTH TOWER

1. SPRINKLER FINAL APPROVED FOR THE FOLLOWING UNITS, ELEVATOR LOBBY AND BOH

3101
3601
4401
4402
4502

2. VERIFIED ALL OF THE ROUGH AND PRESSURE APPROVALS

3. SRI FEES APPLY



Date:

4/18/2023 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

209 - FIRE FINAL

Status:

2 - APPROVED PARTIAL


PERMIT 2020056405
17901 COLLIONS AVE
THE ESTATES OF ACQUALINA
NORTH TOWER

1. SPRINKLER FINAL PARTIAL APPROVAL

2. SPRINKLER FINAL FOR UNIT 4001 APPROVED
-ALL PENDING ITEMS FROM LIST DATED 4/6/23 HAVE BEEN COMPLETED
-ROUGH AND PRESSURE VERIFIED

3. SPRINKLER FINAL FOR UNIT 3601 NOT APPROVED
PENDING:

(1) S/W IN GREAT ROOM OVER FIRE PLACE CLOSEST TO THE SLIDING GLASS DOOR COVER PLATE SHALL BE FLUSH

(2) NEED TO FIX OPENING AROUND COVER PLATE FOR PENDANT OVER DOOR IN SERVICE/LAUNDRY ROOM

(3) NEED TO REPLACE PAINTED SIDEWALL HEAD IN BEDROOM 3 AND PROVIDE A COVER PLATRE.
KEEP HEAD AS EVIDENCE OF BEING REPLACED

(4) NEED TO FIX OPENING AROUND ESC PLATE FOR WEST FACING SW ON WEST BALCONY

4. VERIFIED PENDING ITEM FOR ROUGH APPROVAL FROM LIST DATED 11/15/22
FLEX HEAD BRACKET IN LAUNDRY ROOM OK

5. SRI FEES APPLY



Date:

4/6/2023 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


**ENTERED UNDER TCO DUE TO FEES BEING OWED**
PERMIT 2020056405
17901 COLLINS AVE
THE ESTSTES OF ACQUALINA
NORTH TOWER

1. SPRINKLER FINAL INSPECTION

2. SPRINKLER FINAL APPROVED FOR UNIT 3401 ONLY
VERIFIED ROUGH, PRESSURE AND FIRE CAULKING APPROVAL FOR 34TH FLOOR

3. SPRINKLER FINAL NOT APPROVED FOR 4001
VERIFIED ROUGH, PRESSURE AND FIRE CAULKING FOR 40TH FLOOR
PENDING:

-LAUNDRY ROOM NEED TO FIX TILE WHERE SPRINKLER IS LOCATED AND NEED TO INSTALL ALL TILES IN LAUNDRY ROOM FOR FINAL

-NEED TO PROVIDE ESC PLATE FOR HEAD IN SAUNA

-NEED TO PROVIDE ESC PLATE FOR S/W IN MASTER BATHROOM BY TUB

4. SPRINKLER FINAL FOR UNITS 4401 AND 4402 ARE PENDING PROVIDING PROOF OF ROUGH AND PRESSURE APPROVAL FOR BALCONY SW FLEX HEAD, LAUNDRY ROOM AND ELECTRICAL ROOM

5. SRI FEES APPLY



Date:

3/27/2023 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2020056405
17901 COLLINS AVE
THE ESTATES OF ACQUALINA
NORTH TOWER

1. SPRINKLER FINAL APPROVED FOR UNIT 2401
VERIFIED ROUGH, PRESSURE AND FIRE CAULK APPROVALS

2. SPRINKLER FINAL APPROVED FOR UNIT 3501 PENDING REVISION OF PLANS. REVISE PLANS TO SHOW CHANGE TO MASTERBEDROOM SHOWER.
SHOW NO TUB AND SHOWER ENCLOSURE WITH NO STEAMER. SHOW NO SIDEWALL IN SOFFITT FACING GLASS.
VERIFIED ROUGH, PRESSURE AND FIRE CAULIKNG APPROVALS

3. SRI FEES APPLY



Date:

3/21/2023 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

209 - FIRE FINAL

Status:

2 - APPROVED PARTIAL


PERMIT 2020056405
17901 COLLINS AVE
THE ESTATES OF ACQUALINA

1. SPRINKLER FINAL APPROVED FOR THE FOLLOWING UNITS

-4101
VERIFIED R & P APPROVAL 5/5/21-9/9/21 BOH 12/29/21

-2001 & 2002
VERIFIED R & P APPROVAL 11/3, 11/18 & 12/20

2. SRI FEES APPLY



Date:

3/8/2023 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2020056405
17901 COLLINS AVE
THE ESTATES OF ACQUALINA
NORTH TOWER

1. SPRINKLER FINAL NOT APPROVED

2. NEED TO VERFIY ROUGH AND PRESSURE APPROVALS

3. 4301 ESC PLATE WEST BALCONY MISSING
FINISH PAINT BOTH BALCONIES
AND MOTHER IN LAW
INSTYALL TILE IN LAUNDRY ROOM

4. UNIT 2001 UNIT NEEDS FINAL PAINT

5. 2002
REPLACE COVER PLATE IN BATH 5 WEST
PROVIDE COVER PLATE FOR SW IN BATH 5 west
FIX LOBBY ESC PLATE
FINAL PAINT ENTIRE UNIT ABD BALCONY
FIX GREAT ROOM ESC PLATE

6. SRI FEES APPLY



Date:

3/6/2023 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2020056405
17901 COLLINS AVE
THE ESTATES OF ACQUALINA
NORTH TOWER

1. INSPECTION TO TEST CO/SMOKE DETECTORS

2. THE FOLLOWING UNITS OK FOR CO AND S/D
4402,4301,4202,4101,3902,2001

3.UNIT 4401 NOT PART OF INSPECTION HOWEVER NEED TO REPLACE PENDANT IN WEST HALLWAY. THE SPRINKLER IS BENT

4. SRI FEES APPLY



Date:

3/1/2023 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2020056405
17901 COLLINS AVE
THE ESTATES OF ACQUALINA
NORTH TOWER

1. ROUGH AND PRESSURE FOR 4602 BALCONY ONLY COMPLETED
-APPROVAL PENDING PROVIDING THE APPROVED PLANS

2. SPRINKLER FINAL APPROVED FOR UNIT 4302 ENTIRE UNIT AND BALCONY
-VERIFIED SPRINKLER ROUGH AND PRESSURE APPROVAL
LT. HARRISON 5/26
JABALI 7/8/22

3. PROVIDE PROOF OF ROUGH AND PRESSURE APPROVAL FOR BALCONY 49TH FLOOR OR
BALCONY WALKED FOR ROUGH, WILL NEED TO DO ROUGH AND PRESSURE

4. SRI FEES APPLY



Date:

2/28/2023 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2020056405
17901 COLLINS AVE
THE ESTATES OF ACQUALINA
NORTH TOWER

1. SPRINKLER ROUGH AND PRESSURE NOT APPROVED FOR BALCONIES FLOOR 49 AND 4602

2. NEED TO PROVIDE A PRESSURE TEST FOR AT LEAST 2 HRS AT MIN 200PSI NFPA 13

3. UNIT 49 NEED TO REVISE PLANS AND HAVE STAMPED AND APPROVED TO REFLECT THE TYPE OF PENDANTS USED FOR BALCONY ON SPRINKLER LEGEND
PROVIDE SPECS TO VERIFY COVERAGE

4. PROVIDE MEANS TO VERIFY PENDANT ON BALCONY

5. FOR UNIT 4602 BALCONY, IF SOFIIT WITH SW INSTALLED IN GREATER THAN 8" AND PENDANT IS REQUIRED UNDERNEATH NFPA 13

6. SRI FEES APPLY



Date:

2/16/2023 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2020056405
17901 COLLINS AVE
THE ESTATES OF ACQUALINA
NORTH TOWER

1. SPRINKLER FINAL PARTIAL APPROVAL FOR 4102

-NEED TO REPLACE PAINTED HEAD IN MASTER SHOWER

-RELOCATE IN IN MASTER BEDROOM SMALL CLOSET

2. SPRINKLER FINAL APPROVED FOR 4201

3. SPRINKLER FINAL PARTIAL APPROVAL 4202

-FIX GAP AROUND ESC. PLATE IN MASTER SHOWER

4. VERIFIED ROUGH, PRESSURE AND FIRE CAULKING APPROVALS

5. SRI FEES APPLY



Date:

2/6/2023 

Inspector:

Walter  Wray (WRAYWW) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


Balcony railings checked and okay on units 4601 4602-4501-4502-4001 3401 3201-3001-901 and 1001



Date:

1/23/2023 

Inspector:

John Molnar (MOLNAR) 

Type:

206 - FIRE ROUGH

Status:

34 - INSPECTION CANCELLATION


2020056405
17901 COLLINS AVE , Sunny Isles Beach

Inspection scheduled under the wrong permit #



Date:

1/18/2023 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2020056405
17901 COLLINS AVE
THE ESTATES OF ACQUALINA
NORTH TOWER

1. SPRINKLER FINAL APPROVED FOR UNITS 3901,3902 & 4002

2. PENDING ITEMS FROM PREVIOUS LIST FOR UNITS 3902 AND 4002 HAVE BEEN COMPLETED

3. SRI FEES APPLY



Date:

1/17/2023 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2020056405
17901 COLLINS AVE
NORTH TOWER

1. SPRINKLER FINAL NOT APPROVED FOR UNITS 3902 AND 4002


2. UNIT 3902 WEST BEDROOM INSIDE FRONT DOOR MISSING ESC PLATE NFPA 13
-NEED TO REPLACE PAINTED HEADS IN MASTER BATHROOM STEAM SHOWER NFPA 13:6.2

3. UNIT 4002 MISSING ESC PLATE OUTSIDE THE FRONT DOOR TO MASTER BEDROOM
-FIX ESC PLATE OUTSIDE FRONT DOOR MASTER BEDROOM
-FIX ESC PLATE IN KITCHEN IN FRONT OF PIZZA OVEN
-REPLACE PAINTED HES WEST CORRIDOR IN FRONT OF SMALL CLOSET (1ST HEAD)

4. KEEP ALL PAINTED HEADS AS EVIDENCE OF BEING REPLACED

5. SRI FEES APPLY



Date:

1/16/2023 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2020056405
17901 COLLINS AVE
NORTH TOWER
UNITS 3502 & 3802 ONLY

1. SPRINKLER FINAL APPROVED FOR UNITS 3502 & 3802 ONLY

2. SRI FEES APPLY



Date:

1/12/2023 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2020056405
17901 COLLINS AVE
THE ESTATES OF ACQUALINA
NORTH TOWER

1. UNIT 4101
SPRINKLER ROUGH APPROVED FOR PENDANT IN SOFFIT OF WEST BALCONY

2. SRI FEES APPLY



Date:

12/28/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2020056405
17901 COLLINS AVE
THE ESTATES OF ACQUALINA
NORTH TOWER

1. SPRINKLER FINAL APPROVED FOR UNIT 3402 ONLY

2. SPRINKLER ROUGH AND PRESSURE APPROVAL FOR FLOOR 34 PREVIOUSLY VERIFIED

3. VERIFIED PRESSURE ON THE SYSTEM

4. SRI FEES APPLY



Date:

12/12/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2020056405
17901 COLLINS AVE
NORTH TOWER

1. SPRINKLER FINAL FOR SHELL COVERAGE APPROVED FOR FLOOR 48
ALL CEILING DRYWALL AND TAPE HAS BEEN INSTALLED
THIS UNIT IS IN SHELL CONDITION ONLY

2. ALL PREVIOUS PENDING ITEMS FOR FLOOR 48 HAVE BEEN COMPLETED

3. SRI FEES APPLY



Date:

12/5/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2020056405
17901 COLLINS AVE
NORTH TOWER

1. CONTINUED INSPECTIONS FOR FLOORS 48 AND 49

2. NEED TO INSTALL ALL ACCESS COVERS BOTH FLOORS, REMOVE CAP ON FLOOR 49 LAUNDRY ROOM, COMPLETE SOFFITTS ON BALCONY 49TH FLOOR
COMPLETE TAPING OF DRYWALL THROUGH OUT (PENDING AREAS)

3. SRI FEES APPLY



Date:

12/1/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2020056405
17901 COLLINS AVE
THE ESTATES OF ACQUALINA
NORTH TOWER

1. SPRINKLER INSPECTION CONTINUED

2. VERIFIED THAT FLOORS 48 AND 49 HAVE PARTIALLY BEEN COMPLETED FOR DRY WALL

3. FINAL STILL PENDING

4. SRI FEES APPLY



Date:

11/29/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2020056405
17901 COLLINS AVE
THE ESTATES OF ACQUALINA
NORTH TOWER

1. SPRINKLER INSPECTION CONTINUED

2. VERIFIED PENDINIG ITEMS REQUIRED FOR TCO FROM JABALI S LIST DATED 11/28/22
FL 50
4602
4301
4101
4001-NEED TO FIX TILE AROUND ESC PLATE FOR FINAL
FL 37 STAIR 2 RELIEF VALVE INSTALLED
-3702 GAUGE REMOVED AND OK

3. FL 49 UNIT NOT READY
FL 48 UNIT NOT READY


4. ALL PENDING ITEMS FOR SPRINKLER FINAL ARE STILL PENDING

5. AFFIDAVIT SHALL BE ORIGINAL AND NOT ELECTRONIC SIGNATURE

6. PRIOR TO SPRINKLER FINAL, ALL LIST WILL HAVE TO BE VERIFIED FOR PENDING ITEMS FOR SPRINKLER FINAL

7. SRI FEES APPLY

8. ADDITIONAL COMMENTS TO FOLLOW BY LT. WRAY



Date:

11/29/2022 

Inspector:

Walter  Wray (WRAYWW) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


1. Spr Final Partial approval 22 FL
- S/W in Master Bed that needs to be 4" off wall still pending
- ONLY APPROVED FOR SHELL COVERAGE. TEMP PENDENTS HAVE BEEN INSTALLED IN LAUNDRY FOR SHELL COVERAGE. FLEX BRACKET WILL NEED TO BE UNSPECTED WHEN INSTALLED.

2. UNIT #3501 - temporary upright installed in sauna. Flex bracket will need to be inspected when it is installed.

3. #3402 - Flex bracket in sauna needs to be installed according to the manufacturer s listing.

4. #3401 - all items completed. Okay to close ceiling

5. All other TCO items from WRay s list dated 11/29/22 have been completed



Date:

11/29/2022 

Inspector:

Walter  Wray (WRAYWW) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


Permit #2020-056405

1. Items completed from Wray?s list dated 11/26/22:
- 48 FL OK
- #2501 OK
- Elevator shaft Pvt Garage OK
- Head added Lobby level 5
2. Items completed from LT De alfaraz?s list dated 11/23/22 (11/21/22):
- Item #2, units 3001 and 3201 pending final paint, #901, #1001, #6, head guard added, and #8
3. Item #9 completed from Wray?s list dated 11/21/22:
4. Sprinkler Final 22 FL
- Eschutcheon plate missing in Master Bed and Bedroom #2
- S/W in Master Bed < 4? from wall (circled in blue hi-lighter on plans). Will still need to maintain the min. 12? from the A/C register when relocated.
- Ceilings in both Laundry rooms not completed
5. Sprinkler Final FL?s 34-36 partial approval
6. Bedroom #3 in units 3402, 3502, and 3602 have the S/W > 9? from the wall
7. #3501 ? West balcony soffit not completed and ceiling not in for the Sauna (will need to view/inspect flex bracket before closing the ceiling)
8. #3402 ? Drywall mud on Master Bath shower
- Sauna missing head (will need to view/inspect flex bracket before closing the ceiling)
- Eschutcheon plate missing in Laundry
9. #3401 - Eschutcheon plate missing in hallway closet AND in SW bedroom
- Sauna ceiling not installed (will need to view/inspect flex bracket before closing the ceiling)



Date:

11/28/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2020056405
17901 COLLINS AVE

1. SPRINKLER INSPECTIONS CONTINUED

2. FLOORS 52 TO 37 WALKED FOR FINALS

3. PENDING ITEMS

-52 UNIT APPROVED FOR SHELL CONDITION FINAL. ELEVATOR FOYER SHALL BE PAINTED FOR FINAL

-51 UNIT APPROVED FOR SHELL CONDITION FINAL.

-50 SPRINKLER HEAD IN ELEVATOR FOYER BY FRONT DOOR HAS BEEN COVERED (REQUIRED FOR TCO)

-49 UNIT NOT READY (REQUIRED FOR TCO)

-48 UNIT NOT READY (REQUIRED FOR TCO)

-47 NEED TO COMPLETE SOFFITTS FOR BOTH BALCONIES, FINAL PAINT BOTH BALCONIES

-4602 EAST BALCONY ESC PLATES (REQUIRED FOR TCO) FINAL PAINT FOR BALCONIES, FINAL CEILING PAINT UNIT,

-4501 FINAL PAINT UNIT BALCONY

-4502 FINAL PAINT UNIT AND BALCONY

-4401 FINAL PAINT UNIT, BOTH BALCONIES

-4402 FINAL PAINT UNIT, BOTH BALCONIES

-4301 MISSING HEAD IN SERVICE ROOM, 1 CLOSET LOCKED 2ND BEDROOM, (REQUIRED FOR TCO) FINAL PAINT UNIT AND BALCONY

-4302 REPLACE 2 HEADS IN MASTERBATH BATH/SHOWER FINAL PAINT BALCONIES, FINAL PAINT UNIT

-4201 FINAL PAINT UNIT, BALCONIES

-4101 ELEVATOR FOYER FIX ESC PLATE IN SOFFITT, NEED TO INSTALL HEAD UNDERNEATH LARGE SOFFITT WEST BALCONY. FINAL PAINT BALCONIES

-4002 REPLACE 2 GROUTED HEADS IN MASTERBATH BATH/SHOWER, REPLACE HEAD IN WEST HALLWAY IN FRONT OF 1/2 BATH , FINAL PAINT BALCONIES

-4001 LAUNDRY ROOM NEED TO COMPLETE WALL/CEILING (REQUIRED FOR TCO) FINAL PAINT BALCONIES

-3902 REPLACE HEADS IN MASTERBATHROOM BATH/SHOWER, FINAL PAINT UNIT,BALCONIES

-3802 HEADS ARE MIXED IN MASTER BATHROOM BATH/SHOWER. HEADS SHALL BE OF THE SAME RESPONSE NFPA 13. FINAL PAINT BALCONIES

-3702 NEED TO INSTALL SPRINKLER HEAD WHERE PRESSURE GAUGE IS IN UNIT, NEED TO INSTALL TEST HOSE AT RISER STAIR 5, FINAL PAINT BALCONIES

4. PRIOR TO FINAL NEED TO INSTALL HEADS IN ALL 02 TYPICAL UNITS MASTER BATHROOM BATH/SHOWER PER APPROVED PLANS.
PLANS CALL FOR VK 102 PENDANT 1/2" 360 K-5.6 FOR STEAM SHOWER

VK 305 SEMI RECESSED SIDEWALL 200 DEGREE

5. PLANS SHALL BE REVISED, STAMPED AND APPROVED TO SHOW THE DIMENSIONS OF THE SOFFITTS ON THE BALCONIES. AND NOTE THAT THE SOFFITTS GREATER THAN 8" DO NOT HAVE A HEAD UNDERNEATH

6. SRI FEES APPLY



Date:

11/28/2022 

Inspector:

Walter  Wray (WRAYWW) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


1. Items completed from previous lists.

2. Partial spr finals floors 34-36 North Tower (comments will be sent to Jabali)



Date:

11/26/2022 

Inspector:

Walter  Wray (WRAYWW) 

Type:

209 - FIRE FINAL

Status:

2 - APPROVED PARTIAL


1. Completed items from Jabali s list dated 11/15/22:

#2 - All completed except fire caulking on balconies of 48 FL, 1602, and the affidavit

#3 - #3101 need ceiling paint
- 2501 - all ok except for west open balcony

#5 - 2702 needs to be painted
- 2801 ok for spr final

2. Completed items from Wray s list dated 11/21/22:

#2, 5, 6, 11-16 OK

#10 - ok EXCEPT elevator pit still PENDING

3. Items completed from Jabali s list dated 11/22/22:

#2 - levels 52, 51, 50, and 47 ok

#6 - levels 52 and 49 ok

#7 - all items were completed except for signage at roof manifold and missing head in elevator Lobby level 5

4. Items completed from De alfaraz s list dated 11/21/22:

#2 - ok except for elevator lobby

#1001 - still pending all items, and need to relocate sidewall at the top of the stair so that it is more than 12" away from the AC register

2001 and 2002 ok

2101 ok except for painting not completed



Date:

11/23/2022 

Inspector:

Jose De Alfaraz (JOSEED) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


Aqualina North Tower

Sprinkler 2019073478
11/21/22

1. Sprinkler rough partial approved for the suite 501 and 502. The pressure is okay.

2. Still pending three spk heads for rough inspection for suite 501 and three sprinkler heads for 502. Marked on the plans.

3. Still pending sprinkler finals for the following units:

2501 Missing Sauna ceiling
3001 spk final pending
3101 spk final pending
3201 spk final pending

901 Relocate the sprinkler head that is below the spiral stairs to be underneath the lower ceiling to collect the heat. The outside patio spk heads at the East balcony are covered.

1001 Both mechanical closets has the spk head covered, the East and West side outside patios all the heads are covered, The Her closet is missing the ceiling grid.

2001 Add ceiling tiles, add ceiling grid, Bedroom 5 sidewall missing and inside bathroom 5 missing spk head, great room is missing a sidewall sprinkler head.

2002 Outside patio spk heads, missing ceiling tiles, Bathroom "02" sidewall head missing, balcony area and sauna needs re-inspected

2101 missing ceiling grid, master bath missing sidewall head, Sauna missing ceiling, needs final painting, missing ceiling grid at both service corridors.

Entire unit level 21 pending spk finals
Entire unit level 22 pending spk finals
2702 Missing Sauna Ceiling
2801 Missing Master bedroom sidewall

4. All common areas/back of the house areas are okay for sprinkler final from floors 46 to 34.

5. All apartment units from floors 46 to 34 are still pending sprinkler finals.

6. Need to provide signage at the Street level Flow Bell to read: WHEN BELL IS RINGING CALL 911.

7. Suite 3302, 2602, 2701 are okay for sprinkler finals.

8. Nothing else was verified for spk final. See the sprinkler reports by FF Jabali and Lt. Wray for additional comments.



Date:

11/22/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2020056405
17901 COLLINS AVE
NORTH TOWER

1. SPRINKLER INSPECTION CONTINUED

2. THE APPROVED REVISED PLANS HAVE BEEN PROVIDED FOR FLOORS 5,37,47,50,51 & 52
THE UNITS HAVE BEEN WALKED FOR ROUGH AND PRESSURE

LEVEL 52 PRESSURE APPROVED, ROUGH PARTIAL APPROVAL, FIRE CAULK OK
-INSTALL 175 DEGREE HEAD PER PLANS (SEE PLANS)
-INSTALL 2 HEADS PER PLANS
-LOWER 1 HEAD (SEE PLANS) BEING OBSTRUCTED BY PIPE

LEVEL 51 PRESSURE APPROVED, ROUGH PARTIAL, FIRE CAULK OK
-NEED TO INSTALL 2 HEADS (SEE PLANS)

LEVEL 50 PRESSURE APPROVED, ROUGH PARTIAL
-NEED TO INSTALL 3 HEADS (SEE PLANS)

LEVEL 47 ROUGH AND PRESSURE APPROVED
-FIRE CAULK EAST BALCONY INSIDE AND OUTSIDE

LEVEL 37 ROUGH AND PRESSURE APPROVED FIRE CAULK OK

LEVEL 5 INSPECTED BY LT. deALFARAZ (COOMENTS TO FOLLOW)

THESE UNITS SHALL BE WALKED FOR FINAL

3. ITEM #2 FROM LIST DATED 11/15/22 ALL COMPLETED EXCEPT FOR
-LEVEL 48 ALL ITEMS ARE PENDING
-HEAD ADDED AND RELOCATED IN THE BASEMENT OK ADD HEAD GUARD

4. ITEM #3 FROM LIST DATED 11/15/22 ALL UNITS PENDING

5. ITEM #4 FROM LIST 11/15/22 ALL ITEMS COMPLETED

6. ITEM #5 FROM LIST 11/15/22
-ALL ITEMS PENDING EXCEPT 2602-2701 WHICH WERE INSPECTED AND OK BY LT deALFARAZ

BOH LEVELS 34-52 WALKED BY deALFARAZ AND JABALI AND OK EXCEPT ITEMS NOTED BELOW FROM JABALI lT. DEALFARAZ NOTES TO FOLLOW
-52 FIX THE TILE AROUND THE ESC PLATE BOH ELEVATOR , FIX ESC PLATE OVER FOYER FRONT DOOR IN THE UNIT
-49 FIX TILE AROUND ESC PLATE BOH ELEVATOR
LEVELS 34 TO 52 ENTIRE UNIT FINALS PENDING UNITS WERE NOT READY FOR FINAL

7. ADDITIONAL PENDING ITEMS FOR FINAL FOR THE FOLLOWING AREAS
LEVEL 55
-STAIR 5 MISSING PRV SIGN (NOT A TCO ITEM)
-PROVIDE SIGNAGE AT THE ROOF MANIFOLDS (NOT A TCO ITEM)
-ELECTRICAL ROOM PENDING FINAL WALK (DOOR WAS LOCKED)
-MECHANICAL ROOM 1 LEVEL 53 ADD 2 HEADS BY SOUTH DOOR (NOT A TCO ITEM)
-LEVEL 51 BOH OK
-LEVEL 50 INSTALL PRESSURE RELIEF @ RISER
-LEVEL 49 FIX ESC PLATE BOH ELEVATOR
-LEVEL 48 OK
-LEVEL 5 BOH AND BOTH FOYERS NEED TO PAINT FOR FINAL, ONE ESC PLATE NOT FLUSH (NOT A TCO ITEM)
ADD 1 HEAD IN FOYER IN FRONT OF DOORS

8. PROVIDE SPRINKLER COVERAGE IN BDA ROOM

9. THERE ARE ADDITIONAL COMMENTS FOR OTHER AREAS INSPECTED BY LT. WRAY AND LT. de ALFARAZ

10. PRIOR TO SIGN OFF OF SPRINKLER FINAL FOR THE BUILDING, ALL AREAS SHALL BE PAINTED

11. SRI FEES APPLY

12. NEED TO COMPLY WITH ITEMS FROM JABALI, LT. WRAY AND LT deALFARAZ LIST



Date:

11/21/2022 

Inspector:

Walter  Wray (WRAYWW) 

Type:

209 - FIRE FINAL

Status:

2 - APPROVED PARTIAL


1. Sprinkler final partial approval for North Lobby floor and basement North

2. Need to reposition hanger in Mech Rm of North Lobby so that it is not w/in 3" of the upright head ( hanger will need to be on other side of the duct). NFPA 13:9.2.3.2

3. Finish painting all sprinkler pipe on the Basement and Garage levels. WASA D-8

4. Sprinkler Final Garage 11 DENIED

5. Provide proof of all sprinkler rough and pressure approvals for Garage level

6. 2 heads in garage number 12 are obstructured by the beam.

7. Add heads and ceiling pockets of irrigation pump room, and private garages one two and three. NFPA 13

8. Confirm that the Cabanas will not be included in this TCO.

9. Need sidewall heads installed under each roll up garage door of private garage.

10. Need to check storage rooms behind private garages 14 and 15

11. Need to relocate upright sprinkler head a minimum of 4 inches from wall in generator room (see plans)

12. Install missing cover plate in trash room

13. Provide access to storage room in private garage 18

14. Add head in North loading dock so that there is coverage within 10 ft of the wall (see plans)

15. Two heads obstructed by AC duct will need to be lowered 1 to 6 in below the beam (see plans)

16. Replace three painted upright heads by ramp of North loading dock. Save The Painted heads for the next inspector. NFPA 13:6.2.6.2.2

17. No sprinkler heads or piping has been installed in the stair leading to the pool deck, in the area leading to the pool deck on the pool deck, pool restrooms, and Storage

18. Add a head under each stair in each private garage leading to the Cabanas. NFPA 13:4.1

All other areas on Garage level checked n ok



Date:

11/16/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2020056405
17901 COLLINS AVE
NORTH TOWER

1. CONTINUED SPRINKLER INSPECTIONS

2. VERIFIED THE FOLLOWING ITEMS FROM THE PREVIOUS LIST DATED 11/15
UNDER #2

-4602 FLEX HEAD BRACKET HAS BEEN INSTALLED
-4502 HEAD HAS BEEN RELOCATED IN MASTERBEDROOM CLOSET
-3602 FLEX HEAD BRACKE MASTERBEDROOM

3. ALL OTHER PENDING ITEMS ARE STILL PENDING

4. SRI FEES APPLY



Date:

11/15/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2020056405
17901 COLLINS AVE
THE ESTATES OF ACQUALINA
NORTH TOWER

1. SPRINKLER ROUGH, PRESSURE AND FINALS THAT HAVE BEEN VERIFIED AND PENDING FOR THE FOLLOWING:

-LEVELS 5,37,47,50,51 & 52 ARE WAITING ON APPROVED PLANS PRIOR TO ROUGH AND PRESSURE INSPECTION

2. THE FOLLOWING UNITS ARE PENDING ROUGH ONLY. ALL OF THE PRESSURE TEST HAVE BEEN VERIFIED

-4602 FLEX HEAD BRACKET IN LAUNDRY ROOM
-4501 FLEX HEAD BRACKET IN LAUNDRY ROOM/SERVICE ROOM
-4502 CLOSET MASTERBEDROOM RELOCATE
-3601 FLEX HEAD BRAXKET LAUNDRY ROOM
-3602 FLEX HEAD BRACKET MASTER BEDROOM
-LEVEL 49 FLEX HEAD BRACKET FOR SAUNA
-LEVEL 48 - RELOCATE HEAD IN LAUNDRY ROOM THAT EXCEEDS MAX DISTENCE FROM THE WALL
-RELOCATE S/W NW BALCONY MIN 4" OFF THE WALL
-FLEX HEAD BRACKET FOR SAUNA
-BOTH EAST BALCONIES PENDING FIRE CAULKING
-LOWER SW IN SOUTH WEST BEDROOM MIN 4" BELOW THE CEILING
-1602 ELEVATOR FOYER FIX ESC PLATE IN TRAY CEILING NO FLUSH
-BASEMENT BY THE EXIT ACCESS FROM THE TENANT STORAGE TO THE SERVICE ELEVATOR LOBBY NEED TO RELOCATE PENDANT MIN 4" OFF THE WALL AND ADD COVERAGE UNDERNEATH FIRE RATED SHAFT

2. FOR ALL OF THE AREAS WHERE THE ROUGH, PRESSURE AND FIRE CAULKING HAVE ALREADY BEEN CLOSED AND INSPECTOR UNABLE TO VERIFY VISUALLY
SPRINKLERMATIC AND SUFFOLK SHALL PROVIDE NOTARIZED AFFIDAVIT ATTESTING AND ASSUMING RESPONSIBILITY THAT THE INSTALLATION OF THE SPRINKLER SYSTEM HAS BEEN INSTALLED IN ACCORDANCE WITH AND COMPLIES WITH NFPA 13
THIS AFFIDAVIT IS REQUIRED PRIOR TO PARTIAL SPRINKLER FINAL APPROVAL AND PRIOR TO TCO.
**THIS IS REQUIRED FOR TCO**

3. UNITS PRVIOUSLY WALKED FOR FINAL THAT ARE PENDING

-2501 WEST HALLWAY SMALL CLOSET, WEST OPEN BALCONY, BEDROOM 2 ESC PLATE
-3001 WEST BALCONY NORTH OPEN TERRACE
-3101 SAUNA WEST BALCONY
-3201 WEST BALCONY NORTH OPEN TERRACE, ESC. PLATE LAUNDRY ROOM
-3302 SAUNA WEST BALCONY

4. STANDPIPE HIGH AND LOW ZONE STAIR 5 & 6 HAVE BEEN WALKED FOR FINAL ALL OK EXCEPT

-RISER CLAMP FOR STAIR 6 FLOOR 16
-RISER CLAMP STAIR 5 LEVEL 6 6" RISER
-2 MISSING CAPS FOR HOSE VALVE GROUND LEVEL STAIR 5

5. THE FOLLOWING ARE ALL PENDING FOR COMPLET SPRINKLER FINAL INSPECTION
901
1001
2001
2002
ENTIRE UNIT LEVEL 21
ENTIRE UNIT LEVEL 22
2602
2701
2702
2801
LEVELS 34 TO 55
LOBBY
GROUND
BASEMENT
BOH LEVELS 34 TO 52

-ONCE PLANS HAVE BEEN APPROVED AND ROUGH AND PRESSURE APPROVED
LEVELS 5,37,47,50,51 & 52 WILL REQUIRE SPRINKLER FINALS

6. FLOORS 4,22,48,49 AND ALL OTHER PENDING FLOORS FOR FINALS AND BALCONIES SHALL HAVE FINISHED CEILINGS, SOFFITTS WHICH INCLUDES DRYWALL, TAPE AND PAINT
ALL BALCONIES SHALL BE PAINTED AS WELL

7. PROVIDE SIGNAGE FOR ALL OF THE FIRE DEPARTMENT CONNECTIONS THAT STATE
"AUTOMATIC SPRINKLER AND STANDPIPE"

8. PLANS SHALL BE REVISED, STAMPED AND APPROVED BY FINAL TO SHOW AS BUILT
NFPA 1: 1.14.5

9. THE CABANAS ARE STILL PENDING ROUGH, PRESSURE AND FINAL INSPECTIONS

10. THIS LIST SUPERSEDES ALL OTHERS

11. SRI FEES APPLY






Date:

11/14/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2020056405
17901 COLLINS AVE
NORTH TOWER

1. FIRE COMMENTS FOR SPRINKLER ROUGH, PRESSURES AND FINALS TO FOLLOW

2. SRI FEES APPLY



Date:

11/10/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2020056405
17901 COLLINS AVE
NORTH TOWER

1. CONTINUED ROUGH, PRESSURE AND FIRE CAULKING PENDING INSPECTIONS
FLOORS 34 TO 46

2. COMMENTS TO FOLLOW

3. SRI FEES APPLY



Date:

11/10/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2020056405
17901 COLLINS AVE
NORTH TOWER

1. SPRINKLER ROUGH, PRESSURE AND FIRE CAULING FOR PENDING ITEMS/AREAS FROM PREVIOUS INSPECTION FROM 11/3 FLOORS 33-6 ONLY HAVE BEEN COMPLETED EXCEPT FOR THE FOLLOWING

-PENDING CUSTOM UNITS 901 AND 1001

2. INSPECTOR WAS ABLE TO VERIFY ALL FIRE CAULKING, SPRINKLER PIPING AND FLEX HEADS FOR ALL ACOUSTICAL AREAS THAT WERE PENDING

-UNABLE TO VERIFY FIRE CAULKING , SPRINKLER PIPE AND ANY FLEX HEADS IN ALL PENDING HARD CEILING AREAS

3 SRI FEES APPLY



Date:

11/9/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


Permit 2020056405
17901 Collins Ave

1. Fire final for low zone standpipe not approved
No floors were walked for final

2. Pressure is REQUIRED for any final inspection

3. Fees apply



Date:

11/8/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY




Date:

11/8/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY




Date:

11/8/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


Permit 2020056405
17901 Collins Ave
North Tower

1. Sprinkler final walked for the following units that are OK.
3301, 3202, 3102, 3002, 2901, 2902, 2802, 2601, 2502, 2402, 2301, 2302, 1902, 801

-units 2301 and 260 one were pending from previous list

Eunice walk for a final that are pending
3302 pending sauna West balcony
3201 pending west balcony N. Open Terrace
3101 Sauna West balcony
3001 west balcony N open terrace
2501 west hallway, small closet, West balcony N. Open Terrace, S/W over a door in bedroom 2, East balcony, pending painting
2401 pending painting of both balconies, AC closet by front door and master bedroom AC closet, pending paint and remove tape from pipe

2. All finals are pending verification of rough and pressure approvals

3. Sri feees apply



Date:

11/7/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2020056405
1. CONTINUATION OF LOG BOOK ROUGH AND PRESSURES FLOORS 3,4 44THRU 52
COMMENTS TO FOLLOW



Date:

11/7/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2020056405
17901 COLLINS AVE
THE ESTATES OF ACQUALINA
NORTH TOWER


INSPECTION FOR 11/3/22
1. SPRINKLERS ROUGH AND PRESSURES HAVE BEEN VERIFIED FOR FLOORS 5 THRU 43 ONLY EXCEPT FOR THE FOLLOWING
FLOORS:
5 PENDING APPROVAL OF PLANS FOR SHELL COVERAGE FOR INSPECTION
6 OK
7 PENDING FIRE CAULKING
8 PENDING FIRE CAULKING AND UNIT 801 PENDING
9 PENDING LAUNDRY UNIT 901 AND SERVICE ROOM
10 BOH 1001, LAUNDRY ROOM , SERVICE ROOM AND FIRE CAULK
11 OK
12 OK
14 COMMON AREAS, SMALL CLOSET ENTRANCE 1401
15 COMMON AREA . LAUNDRY ROOM
16 ROOM @ CRANE, BALCONIES, LAUNDRY ROOM
17 EAST BALCONIES, LAUNDRY RM
18 LAUNDRY ROOM
19 UNIT 1901 LAUNDRY ROOM
20 BEDROOM 2001 PENDING ROUGH , BALCONIES, ELECTRICAL ROOM, LAUNDRY ROOM, COMMON AREAS
21 OK
22 OK
23 LAUNDRY ROOM, ELECTRICAL ROOM, TRASH CHUTE
24 EAST BALCONIES, 2401 NW BEDROOM
25 OK
26 BOH
27 LAUNDRY ROOM, EAST BALCONIES
28 ALL BALCONIES, BOH, ELECTRICAL ROOM, LAUNDRY ROOM
29 BOH, LAUNDRY ROOMS, 2901 WEST BALCONIES
30 BOH, ELEC. RM, LAUNDRY RM. TRASH CHUTE, UNIT 1 CLOSET
31 CLOSET WEST SIDE BEDROOM 02 UNIT , LAUNDRY ROOM
32 UNIT 2 SMALL CLOSET, EAST AND WEST BALCONIES
33 LAUNDRY RM, SMALL CLOSET 02 , BOH 02 UNIT
34 OK
35 3501 SERVICE RM, 3502 LAUNDRY RM, MASTER BATH
36 3601 LAUNDRY RM, 3602 LAUNDRY RM, MASTER BATH, ELEV LOBBY AND FIRE CAULK
37 WAITING ON PLANS FOR SHELL COVERAGE TO DO INSPECTION
38 BOH
39 3902 WEST CORRIDOR, LAUNDRY RM, FIRE CAULK PENDING
40 OK
41 ELECTRICAL ROOM, LAUNDRY RM. SAUNA PENDING ROUGH, THE PRESSURE WAS ON ENTIRE FLOOR
42 4202 FAMILY RM NW CORNER PENDANTS
43 FIRE STOP BALCONIES


2. FINALS THAT WERE WALKED
FLOORS
6 OK
7 OK
8 PENDING 801
9 PENDING 901
10 PENDING 1001
11 OK
12 OK
14 PENDING
15 OK
16 PENDING
17 PENDING
18 PENDING
19 PENDING

PENDING ITEMS FOR R & P HAVE TO BE COMPLETED FOR FINAL.
NO OTHER FLOORS SCHEDULED FOR FINALS



Date:

11/7/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2020056405
17901 COLLINS AVE
THE ESTATES OF ACQUALINA
NORTH TOWER


INSPECTION FOR 11/3/22
1. SPRINKLERS ROUGH AND PRESSURES HAVE BEEN VERIFIED FOR FLOORS 5 THRU 43 ONLY EXCEPT FOR THE FOLLOWING
FLOORS:
5 PENDING APPROVAL OF PLANS FOR SHELL COVERAGE FOR INSPECTION
6 OK
7 PENDING FIRE CAULKING
8 PENDING FIRE CAULKING AND UNIT 801 PENDING
9 PENDING LAUNDRY UNIT 901 AND SERVICE ROOM
10 BOH 1001, LAUNDRY ROOM , SERVICE ROOM AND FIRE CAULK
11 OK
12 OK
14 COMMON AREAS, SMALL CLOSET ENTRANCE 1401
15 COMMON AREA . LAUNDRY ROOM
16 ROOM @ CRANE, BALCONIES, LAUNDRY ROOM
17 EAST BALCONIES, LAUNDRY RM
18 LAUNDRY ROOM
19 UNIT 1901 LAUNDRY ROOM
20 BEDROOM 2001 PENDING ROUGH , BALCONIES, ELECTRICAL ROOM, LAUNDRY ROOM, COMMON AREAS
21 OK
22 OK
23 LAUNDRY ROOM, ELECTRICAL ROOM, TRASH CHUTE
24 EAST BALCONIES, 2401 NW BEDROOM
25 OK
26 BOH
27 LAUNDRY ROOM, EAST BALCONIES
28 ALL BALCONIES, BOH, ELECTRICAL ROOM, LAUNDRY ROOM
29 BOH, LAUNDRY ROOMS, 2901 WEST BALCONIES
30 BOH, ELEC. RM, LAUNDRY RM. TRASH CHUTE, UNIT 1 CLOSET
31 CLOSET WEST SIDE BEDROOM 02 UNIT , LAUNDRY ROOM
32 UNIT 2 SMALL CLOSET, EAST AND WEST BALCONIES
33 LAUNDRY RM, SMALL CLOSET 02 , BOH 02 UNIT
34 OK
35 3501 SERVICE RM, 3502 LAUNDRY RM, MASTER BATH
36 3601 LAUNDRY RM, 3602 LAUNDRY RM, MASTER BATH, ELEV LOBBY AND FIRE CAULK
37 WAITING ON PLANS FOR SHELL COVERAGE TO DO INSPECTION
38 BOH
39 3902 WEST CORRIDOR, LAUNDRY RM, FIRE CAULK PENDING
40 OK
41 ELECTRICAL ROOM, LAUNDRY RM. SAUNA PENDING ROUGH, THE PRESSURE WAS ON ENTIRE FLOOR
42 4202 FAMILY RM NW CORNER PENDANTS
43 FIRE STOP BALCONIES


2. FINALS THAT WERE WALKED
FLOORS
6 OK
7 OK
8 PENDING 801
9 PENDING 901
10 PENDING 1001
11 OK
12 OK
14 PENDING
15 OK
16 PENDING
17 PENDING
18 PENDING
19 PENDING

PENDING ITEMS FOR R & P HAVE TO BE COMPLETED FOR FINAL.
NO OTHER FLOORS SCHEDULED FOR FINALS



Date:

11/4/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2020056405
1. COMMENTS FOR INSPECTION TO FOLLOW



Date:

11/1/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2020056405
17901 COLLINS AVE
NORTH TOWER

1. INSPECTION FOR PENDING ITEMS ON FLOOR 33

2. ROUGH AND PRESSURE APPROVED FOR PENDING HEADS IN 3302
1 HEAD IN SAUNA VK102 360 DEGREES F
1 HEAD IN FRONT OF MASTERBATH VK494 200 DEGREES F

3. ROUGH AND PRESSURE APPROVED FOR PENDING HEAD IN FRONT OF SAUNA S/W BALCONY
VK 468 175 DEGRRE F
NEED TO REFLECT ON REVISED PLAN THIS HEAD IN SPRINKLER LEGEND

THIS HEAD WAS PENDING FROM LT. GUILER 2/22/21

4. SRI FEES APPLY




Date:

10/31/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2020056405
17901 COOLINS AVE
NORTH TOWER

1. INSPECTION TO GO THROUGH COMMENTS

2. WAS ABLE TO VERIFY SOME OF THE FLOORS.

3. THE LOG BOOK SHALL BE PUT IN ORDER AND MOST RECENT COMMENTS SHALL BE PRINTED OUT.

4. SRI FEES APPLY





Date:

10/24/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2020056405
17901 COLLINS AVE
THE ESTATES OF ACQUALINA
NORTH TOWER ONLY

1. SPRINKLER FINAL PARTIAL APPROVAL FOR THE STANDPIPE HIGH ZONE FLOORS 25 THRU 55 AND EXPRESS PIPE ON FLOOR 25 FOR STAIR 5 (EAST) AND STAIR 6 (WEST)

2. VERIFIED ROUGH AND PRESSURE FOR HIGH ZONE AND EXPRESS PIPE FLOOR 25
AND LOW ZONE FLOORS 1 THRU 25 STAIR 5 & STAIR 6

-HIGH ZONE AND EXPRESS R & P APPROVED BY LT. GUILER 6/13/22
-LOW ZONE AND EXPRESS R & P APPROVED BY LT. CARBONELL 8/18/22

3. PENDING ITEMS FOR FINAL FOR HIGH ZONE ONLY
-FLOOR 53 NEED TO CHANGE OUT CLAMP ON LARGER PIPE
-FLOOR BETWEEN 50 AND 49 (INTERMEDIATE) NEED TO PROVIDE A CLAMP ON BOTH PIPES
-FLOOR 49 STAIR 5 INSTALL PRV SIGN
-FLOOR 39 STAIR 5 INSTALL PRV SIGN
-FLOOR 37 STAIR 5 INSTALL RELIEF HOSE ON RISER
-FLOOR 36 STAIR 6 INSTALL RELIEF HOSE ON RISER
-FLOOR 35 STAIR 5 INSTALL RELIEF HOSE ON RISER
-FLOOR 27 STAIR 5 INSTALL RELIEF HOSE ON RISER
-NEED TO PINT RISER RED FROM IN STAIR 6 FLOORS 49 TO 55

-SPRINKLER FINAL FOR UNITS
4. INSPECTED THE FOLLOWING UNIT FOR SPRINKLER FINAL THAT ARE OK
-2801, 2701, 2601 & 2602

5. PENDING UNIT 2502 PENDANT IN SAUNA

6. UNIT 2301 AND 3002 UNABLE TO ENTER THE UNIT DUE TO FLOORS BEING WORKED ON

7. VERIFIED ROUGH AND PRESSURE APPROVAL FOR THE ABOVE UNITS
-FLOOR 26 R & P UNITS ONLY LT. MOLNAR 1/15
-FLOOR 27 R & P LT. GARCIA
-FLOOR 28 R & P UNITS ONLY LT. CARBONELL 1/15

8. SPRINKLER ROUGH APPROVED BY LT. KAPPES FOR SERVICE ROOM/ELECTRICAL ROOM
INCLUDE 2801, 2701, 2601, 2602 & 2502 6/2
NEED TO VERIFY THAT THIS INCLUDES THE PRESSURE. (PRESSURE WAS NOT DOCUMENTED)

9. SRI FEES APPLY






Date:

10/17/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2020056405
17901 COLLINS AVE
NORTH TOWER

1. INSPECTION TO GO THROUGH SPRINKLER COMMENTS

2. NOT COMPLETED AT THIS TIME. ONCE ALL PREVIOUS INSPECTIONS HAVE BEEN VERIFIED, COMMENTS WILL FOLLOW

3. SRI FEES APPLY



Date:

9/26/2022 

Inspector:

John Molnar (MOLNAR) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
17901 COLLINS AVE , Sunny Isles Beach

21st floor rough pressure Fire caulking all ok
This is a T.I unit with its own plans



Date:

9/23/2022 

Inspector:

Byron Kappes (E153438) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405

Acqualina North Tower
17901 COLLINS AVE
Sunny Isles Beach

Sprinkler rough and pressure partial approval.

1. Sprinkler rough and pressure approved for unit 3601 west balcony, 3501 west balcony and spa, and 2702 east balcony only.

Lt B. Kappes



Date:

9/16/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


PERMIT 2020056405
17901 COLLINS AVE , Sunny Isles Beach
ESTATES OF ACQUALINA
NORTH TOWER

1. ROUGH AND PRESSURE APPROVED FOR EAST BALCONIES
UNIT 1801 & 1802

BALCONIES WEST SIDE APPROVED BY LT. GUILER 2/9/2021

2. ROUGH AND PRESSURE APPROVED FOR WEST BALCONY UNIT 3002
BALCONY EAST SIDE BALCONY APPROVED BY LT. MOLNAR 2/2/22




Date:

9/14/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

206 - FIRE ROUGH

Status:

3 - REJECTED NOT TO CODE


PERMIT 2020056405
17901 COLLINS AVE , Sunny Isles Beach
ESTATED OF ACQUALINA
NORTH TOWER ONLY

1. SPRINKLER ROUGH AND PRESSURE NORT APPROVED

2. COMPLY WITH LIST DATED 8/31/22 TO OPEN ALL SOFFITTS ON BALCONIES EAST AND WEST BALCONIES FOR UNITS
-3002
-2702
-1801
-1802

3. IF THESE AREAS HAVE BEEN INSPECTED AND APPROVED PROVIDE PROOF OF APPROVAL

4. WHENEVER ANY INSTALLATION SUBJECT TO INSPECTION PRIOR TO USE IS COVERED OR CONCEALED WITHOUT FIRST HAVING BEEN INSPECTED, THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE THAT SUCH WORK BE EXPOSED FOR INSPECTION
NFPA 1:1.7.13.2

5. FEES APPLY




Date:

9/12/2022 

Inspector:

John Molnar (MOLNAR) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
17901 COLLINS AVE , Sunny Isles Beach

The 21st floor was purchased as a whole and the Sprk layout has changed.
The new plans for the new layout shall be stamped approved prior to the inspection



Date:

9/2/2022 

Inspector:

Byron Kappes (E153438) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405

Acqualina North Tower
17901 COLLINS AVE
Sunny Isles Beach

Sprinkler rough partial approval.

1. Sprinkler rough approved for service/electrical room for floors 4201, 4202
3901, 3902
3801, 3802
3501, 3502
3201, 3202
3101, 3102
3001, 3002
2701, 2702
2601, 2602
2501, 2502

Lt B. Kappes



Date:

8/31/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


PERMIT 2020056405
17901 COLLINS AVE
ACQUALINA ESTATES
NORTH TOWER

1.ROUGH AND PRESSURE INSPECTION FOR BALCONIES ONLY FOR THE FOLLOWING UNITS THAT ARE APPROVED

-UNIT 4602 PRESSURE APPROVED, ROUGH PARTIAL APPROVAL. PENDING INSTALLING FRAMING FOR FLEX HEAD BRACKETS

-ROUGH AND PRESSURE APPROVED FOR
3001, 2901, 2801, 2002, 1902

2. THE FOLLOWING UNITS ARE PENDING OPENING THE SOFFITT
-3002,2702, 1801, 1802





Date:

8/30/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

206 - FIRE ROUGH

Status:

3 - REJECTED NOT TO CODE


PERMIT 2020056405
17901 COLLINS AVE , Sunny Isles Beach
NORTH TOWER

1. SPRINKLER ROUGH AND PRESSURE NOT APPROVED FOR BALCONIES FOR FLOORS 18,19 & 20

2. THE PIPING HAS BEEN COVERED. NEED TO EXPOSE PIPING FOR INSPECTION
NFPA 1

3. RE INSPECTION FEES APPLY



Date:

8/19/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

209 - FIRE FINAL

Status:

68 - CANCELLATION BY INTERNET


Canceled by internet
Permit already scheduled



Date:

8/18/2022 

Inspector:

Marc Harrison (E88884) 

Type:

209 - FIRE FINAL

Status:

2 - APPROVED PARTIAL


2020056405

17901 COLLINS AVE , Sunny Isles Beach

Sprinkler final partial approval.
1. 1601,1602,1701,1702,1801,1802,1901 entire units approved.
2. 1902 unit interior ok, pending sidewalls on balcony.

Lt. Harrison



Date:

8/17/2022 

Inspector:

Steven  Clements (E164643) 

Type:

209 - FIRE FINAL

Status:

2 - APPROVED PARTIAL


2020056405
Acqualina North Tower
17901 COLLINS AVE

Sprinkler finals are approved for the entire unit to include balconies and saunas:
1201
1202
1401
1402
1502
1501 (PENDING)

Lt S.Clements
8/17/22



Date:

8/12/2022 

Inspector:

Tina Guiler (TINAG) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


2020056405
Aqualina
17901 COLLINS AVE , Sunny Isles Beach
8/11/2022


Fire Sprinkler FINAL Partial Approval

1- Spk final Approved for Back of House, electrical rooms, & trash chutes for Floors 41 through 54, all spk final okay.

2- Spk Final Approved for Level 54 Stairwell #6 .

3- Spk Final Approved Level 55 Stairwell #5.

pending-

4- Roof Level 55 plans show spk installed in machine room, either install sk as per plans or revise plans.


Lt. Guiler



Date:

8/3/2022 

Inspector:

Marc Harrison (E88884) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405

17901 COLLINS AVE , Sunny Isles Beach

Sprinkler rough and pressure partial approval for the elevator lobby area on 48th and 47th floor. Refer to Lt. Jabali s notes below.

Lt. Harrison



Date:

7/25/2022 

Inspector:

Albert Carbonell  (ALCARBO) 

Type:

209 - FIRE FINAL

Status:

2 - APPROVED PARTIAL


2020056405
ACQUALINA NORTH TOWER
17901 COLLINS AVE

FIRE SPRINKLER FINAL PARTIAL APPROVAL

1) RE-INSPECTED UNIT 1101, OKAY

**PENDING**

2) PLAN REVISION REQUIRED FOR FINAL FOR ADDED, DELETED, RELOCATED, SPRINKLER COVERAGE.

LT CARBONELL
07\25\2022



Date:

7/21/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2020056405
17901 COLLINS AVE , Sunny Isles Beach
NORTH TOWER

1. SPRINKLER FINAL PARTIAL APPROVAL FOR THE FOLLOWING:

8TH FLOOR
-SPRINKLER FINAL APPROVED FOR ENTIRE 8TH FL EXCEPT FOR UNIT 801
UNIT WAS WALKED FOR FINAL HOWEVER NEED TO PROVIDE PROOF OF ROUGH APPROVAL FOR THE UNIT, THE PRESSURE WAS APPROVED FOR THE FLOOR. THE EAST BALCONY ROUGH WAS APPROVED

9TH FLOOR
-UNIT 902 SPRINKLER FINAL PARTIAL APPROVAL
PROVIDE PROOF OF ROUGH FOR COMMON AREAS/BOH AND LAUNDRY ROOM

-SPRINKLER FINAL APPROVED FOR ELEVATOR LOBBY AND TRASH CHUTE

10TH FLOOR
-SPRINKLER FINAL FOR UNIT 1002 OK EXCEPT PROVIDE PROOF OF SPRINKLER ROUGH APPROVAL FOR LAUNDRY ROOM
-ELEVATOR LOBBY, BOH, ELECTRICAL ROOM, TRASH CHUTE ALL OK FOR FINAL

-ELEVATOR LOBBY, BOH, ELECTRICAL ROOM, TRASH CHUTE ALL OK FOR FINAL

11TH FLOOR
-SPRINKLER FINAL APPROVED FOR ENTIRE FLOOR EXCEPT FOR UNIT 1101
VERIFIED ALL ROUGH AND PRESSURE APPROVALS





Date:

7/20/2022 

Inspector:

Dianne Gary (DGARY) 

Type:

209 - FIRE FINAL

Status:

2 - APPROVED PARTIAL


Permit number: 2020056405

Acqualina North
17901 Collins Avenue
Sunny Isles Beach, FL.

NFPA 1:1.14.4 Review and approval by the AHJ shall not relieve the applicant of the responsibility of compliance with this code.

1. Fire sprinkler final partially approved.

Sprinkler final approved for the entire 6th and 7th floors.



Date:

7/8/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
17901 COLLINS AVE , Sunny Isles Beach
NORTH TOWER

1. SPRINKLER ROUGH AND PRESSURE APPROVED FOR FLOORS 47 & 48 BACK OF HOUSE WHICH INCLUDES THE ELECTRICAL ROOM, TRASH CHUTE FOR FLOOR 48 AND TRASH CHUTE VESTIBULE FOR FLOORS 47 & 48
FIRE CAULKING OK

2. BOTH ELEVATOR LOBBY S ARE PENDING
THE DRYWALL HAS BEEN INSTALLED AT THE CEILING. THE DRYWALL SHALL BE REMOVED TO PERFORM A COMPLETE ROUGH INSPECTION
WHENEVER ANY INSTALLATION SUBJECT TO INSPECTION PRIOR TO USE IS COVERED OR CONCEALED WITHOUT HAVING FIRST BEEM INSPECTED, THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE THAT SUCH WORK BE EXPOSED FOR INSPECTION NFPA 1: 1.7.13.2

3. THE ROUGH AND PRESSURE FOR BOH FOR FLOORS 49 & 50 WERE APPROVED BY LT. GARY 3/2/22. PER ANGEL THE THE FRAMING WAS NOT INSTALLED AND THE FLEX HEAD BRACKETS WERE NOT INSTALLED AT THAT TIME.
THIS INSPECTION WAS TO INSPECT FLEX HEAD BRACKETS. BRACKETS INSPECTED AND OK

4. PENDING ITEM (3) CRANE MOUNT PATIO FROM LT. HARRISON S LIST DATED 5/26
HAS BEEN COMPLETED. ALL HEADS AND FLEX HEADS HAVE BEEN INSTALLED IN ROOM WHERE CRANE WAS LOCATED ROUGH AND PRESSURE OK




Date:

6/13/2022 

Inspector:

Tina Guiler (TINAG) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
17901 COLLINS AVE , Sunny Isles Beach
6/13/2022

Fire Sprinkler Rough Partial Approval

1- STAIRWELL 5 - RISER R & P OKAY FROM 55TH FLOOR TO 25TH FLOOR.

2- STAIRWELL 6- RISER R & P OKAY FROM 54TH FLOOR TO 25TH FLOOR.


LT. GUILER



Date:

5/18/2022 

Inspector:

John Molnar (MOLNAR) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
17901 COLLINS AVE , Sunny Isles Beach

Previous comments regarding rough and plans revision entered under wrong permit disregard..

Today?s inspection
Inspected North Tower car entry way rough pressure approved for 12 heads page FP9-3B
Revise plans for this area for final to match the as builts



Date:

5/18/2022 

Inspector:

John Molnar (MOLNAR) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
17901 COLLINS AVE , Sunny Isles Beach

Sprk rough approved for scope of work
For final revise plans to show added heads drawn in with red ink



Date:

5/17/2022 

Inspector:

John Arrojo (ARROJOJ) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


17901 COLLINS AVE North tower

Rough approved for 10th floor for 2 spk heads marked on plans only.



Date:

5/2/2022 

Inspector:

Tina Guiler (TINAG) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
17901 COLLINS AVE , Sunny Isles Beach
North tower
5/2/2022

Fire Sprinkler Rough Approved for Back of house Service Elevator lobbies

1- Spk rough approved for service elevator lobbies only, back of house,
for floors-
31
30
29
22
18
17
16
15

2- Fire caulking okay in these areas.


Lt. Guiler



Date:

4/7/2022 

Inspector:

Steven  Clements (E164643) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
Acquaina N. Tower
17901 Collins Ave.

**Amalfi Residence**
901 and 1001
South Side of 9th and 10th floor

1. Sprinkler rough and pressure is a partial approval for the 9th and 10th floors for units 901 and 1001. This is a 2 story residence. See highlighted areas on plans pg. FP-2.4

2. This includes balconies, unit 901 back of house, electrical rooms, trash chute and elevator lobbies.

3. Fire caulk is approved.

Pending
1. Laundry rooms for 901 and 1001.

2. Service room for 1001.

3. Back of house for 1001.

4. Plans revisions to show as builts.

Lt S.Clements
4/7/22



Date:

3/14/2022 

Inspector:

Ricardo  Cruz (E32388) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


2020056405
Aqualina North Tower
17901 Collins Ave

Sprinkler rough partial approval


Floors 42-46
1. Rough approved for back of house, Electrical Rm, Trash rm and Trash chute.
2. Pending fire caulking in these areas.

Units 4201, 4301, 4401, 4501, 4601
3. Rough approved for Sprinklers in SW balcony. Fire caulk verified ok.

Lt. Cruz



Date:

2/23/2022 

Inspector:

Steven  Clements (E164643) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


#2020056405
Acqualina N.Tower
17901 Collins Ave.

1. Rough and pressure approved for single upright sprinkler in the 55th floor electrical room.

2. Pressure test approved for the 54th floor. Rough inspected and approved by Lt Kappes on 2/22/22.

3. Fire caulk approved for the 53rd floor electrical room per Lt Kappes 2/22/22 inspection comments.

Lt S.Clements



Date:

2/8/2022 

Inspector:

Dianne Gary (DGARY) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


Permit number: 2022056405

Acqualina North Tower
17901 Collins Avenue
Sunny Isles Beach, FL.

1. Fire sprinkler rough partially approved.

Rough approved for all balcony s on the 28, 26, 25, 24, and 23rd floors.

2. Flex heads still pending on the 27th and 22nd floors in the units only.

All of the other balcony heads in the 27th and 22nd (01) units are okay.



Date:

2/3/2022 

Inspector:

John Molnar (MOLNAR) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
17901 COLLINS AVE , Sunny Isles Beach
1) Floors 29-36 East balcony only rough approved and floors 38&39 East balcony rough approved
2) Floor 37 East balcony pending



Date:

1/26/2022 

Inspector:

Dianne Gary (DGARY) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


Permit number: 2020056405

Acqualina
17901 Collins Avenue
Sunny Isles Beach, FL.

1. Fire sprinkler rough and pressure partially approved for the SOUTH tower.

Rough and pressure approved for the back of house on the fourth floor, and back of house to the fir pump room, and the electrical room on the first floor. See plans pages FP-2.0C, 2.0A, and FP 9.4.



Date:

1/21/2022 

Inspector:

Albert Carbonell  (ALCARBO) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
ACQUALINA NORTH TOWER
17901 COLLINS AVE

FIRE SPRINKLER ROUGH PARTIAL APPROVAL FOR NORTH TOWER 2nd FLOOR BACK OF HOUSE
ONLY (HIGHLIGHTED ON APPROVED PLANS) ELEVATOR LABBY/ TRASHCHUTE VESTIBULE

1) INSPECTED FIRE CAULKING, OKAY TO CLOSE HARD CEILING IN THESE AREAS ONLY

**PENDING**

2) PLAN REVISION REQUIRED FOR FINAL FOR ADDED, DELETED, RELOCATED, SPRINKLER
COVERAGE.

LT CARBONELL
01\21\2022



Date:

1/20/2022 

Inspector:

Byron Kappes (E153438) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405

Acqualina North Tower
17901 COLLINS AVE
Sunny Isles Beach

Sprinkler rough and pressure partial approval.

1. Sprinkler rough and pressure approved for 7 heads in stair 1 parking marked on plans page FP-2.1C. Fire caulk okay for top of shaft elevator. Revise plans for final to show as builts marked on plans.

2. Sprinkler rough and pressure approved for 3 heads located in package room ground level parking garage marked on plans page FP- 2.0D.

Lt B. Kappes



Date:

12/29/2021 

Inspector:

Dianne Gary (DGARY) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


Permit number: 2020056405

Acqualina North
17901 Collins Avenue
Sunny Isles Beach, FL.

1. Fire sprinkler rough partially approved.

Rough approved for back of house to include laundry rooms from floors 41 down to 32. All okay except where listed below.

2. The laundry room for the 02 units on 39 and 33 are not ready, and the entire back of house area the 37th floor is still pending.

Pressure for all areas is approved.



Date:

12/9/2021 

Inspector:

Ricardo  Cruz (E32388) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
17901 COLLINS AVE

Sprinkler Rough partial approval

Floors 43-46

1. Rough approved for pendant in passenger/back of house elevator lobby.

Lt. Cruz



Date:

9/30/2021 

Inspector:

Marc Harrison (E88884) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


2020056405

17901 COLLINS AVE , Sunny Isles Beach

ROUGH AND PRESSURE PARTIAL APPROVAL FOR PREVIOUS PENDING ITEMS ISSUED BY
LT. J. GARCIA ON 46TH FLOOR UNITS 1 AND 2.

1. TRASH CHUTE OK TO CLOSE.

2. FIRE CAULKING OK.

3. UNIT 2 PATIO OK.

STILL PENDING.



Date:

9/28/2021 

Inspector:

Jorge  Garcia (E33268) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405

Acqualina North Tower
17901 COLLINS AVE
Sunny Isles Beach

FIRE SPRINKLER ROUGH PARTIAL APPROVAL

1. FIRE SPRINKLER ROUGH IS PARTIALLY APPROVED FOR THE 46TH FLOOR, UNITS 1 & 2.

2. PRESSUTE TEST WAS WITNESSED AND APPROVED FOR THE ENTIRE 46TH FLOOR OF THE NORTH TOWER.

3. SPRINKLER ROUGH IS APPROVED FOR BOTH UNITS 1 & 2, EXCEPT FOR THE BALCONY IN UNIT 02, BACK OF HOUSE, TRASH CHUTE, LAUNDRY ROOMS IN BOTH UNITS 1 & 2.

4. PENDING FIRE CAULKING THROUGHOUT. DO NOT CLOSE THE CEILINGS AND WALLS UNTIL FIRE CAULKING AND THE PENDING AREAS ABOVE ARE RE-INSPECTED.

LT. JORGE GARCIA
09.28.2021



Date:

9/22/2021 

Inspector:

Jason Moghari  (E184515) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


17901 COLLINS
Aqualina North

Back of house rough partial approval:

26 floor-
2601 laundry pending
2602 laundry ok
Cooridor ok
Main EL Riser Rm. ok

27 and 28 floor-
2701 and 2801 EL Rm. ok, laundry pending
2702 and 2802 laundry pending
Cooridor ok
Main EL Riser Rm. pending



Date:

9/21/2021 

Inspector:

Jason Moghari  (E184515) 

Type:

206 - FIRE ROUGH

Status:

4 - REJECTED PLAN & PERMIT MISSING


17901 COLLINS
Aqualina North Tower

R&P called for back of house floors 2,16,17,18,23. No legible plans on-site. 2nd floor was not ready. Preliminary walkthrough performed. These areas require re-inspection with legible Fire Approved plans.



Date:

8/10/2021 

Inspector:

Byron Kappes (E153438) 

Type:

206 - FIRE ROUGH

Status:

3 - REJECTED NOT TO CODE


2020056405

Acqualina North Tower
17901 COLLINS AVE
Sunny Isles Beach

Sprinkler rough partial approval.

1. Sprinkler rough approved for East balconies floors 14-21. Fire caulk okay except for balconies 17-21.

2. Sprinkler rough approved for back of house floors 14,19,20,21.

3. Sprinkler rough approved for laundry rooms in units 2002,1902,1502,1402 and 1401.

4. Pending sprinkler rough for entire floor 21. This unit was previously approved however the entire ceiling and framing has been removed and will require another sprinkler rough inspection.

Lt B. Kappes



Date:

8/4/2021 

Inspector:

Byron Kappes (E153438) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405

Acqualina North Tower
17901 COLLINS AVE
Sunny Isles Beach

Sprinkler rough partial approval.

1. Sprinkler rough approved for passenger elevator lobbies for floors 34,35 and 36 only. Fire caulk okay.

Lt B. Kappes



Date:

7/27/2021 

Inspector:

Ricardo  Cruz (E32388) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
17901 COLLINS AVE

Partial rough approved for elevator lobby floors 30-33

1. Rough approved only for pendants in elevator lobbies on floors 30, 31, 32, and 33.

2. Fire caulking verified ok.

3. I confirmed that pressure for pendant was approved on previous inspection.

4. OK to close ceiling.

Lt. Cruz



Date:

7/20/2021 

Inspector:

Ricardo  Cruz (E32388) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
Aqualina North tower
17901 COLLINS AVE

Rough Partial Approval

1. Rough approved for East balconies units 1201,1202,1101,1102,1002,902,801,802,701,702.

2. Rough approved for back of house floors 12,11,8,7.

3. Rough approved for laundry room in units 1202,1102,802,702

Lt. Cruz



Date:

7/16/2021 

Inspector:

Byron Kappes (E153438) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405

Acqualina north tower
17901 COLLINS AVE
Sunny Isles Beach

Sprinkler rough partial approval.

1. Sprinkler rough approved for both elevator lobbies on floors 26-29.

Lt B. Kappes



Date:

7/15/2021 

Inspector:

Tina Guiler (TINAG) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


Permit #2020056405
17901 COLLINS AVE , Sunny Isles Beach
North Tower
7/15/2021

Fire Sprinkler Rough & Pressure 45th Floor Partial Approval

1- 45th floor Pressure okay. Rough partial approval, Fire Caulking okay.

Pending Spk Rough:

2- Both Laundry rooms.

3- Pendant spk head in both elevator lobbies. (sidewalls okay)

4- Closet in master bedroom unit #4502 pending.

5- Back of house.

6- Electrical room.


Lt. Guiler



Date:

7/1/2021 

Inspector:

Tina Guiler (TINAG) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


Permit #2020056405
17901 COLLINS AVE , Sunny Isles Beach
North Tower
7/1/2021

Fire Sprinkler Rough & Pressure Partial Approval - 42nd floor

1- Fire spk R & P partial approval for 42nd floor. Pressure okay.

Pending for 42nd floor-

2- Elevator lobbies - pendant spk heads only.

3- Electrical room

4- Back of house & laundry rooms

5- 4202 unit- pending family room- next to balcony- NW corner, pendant spk head pending.


Lt. Guiler



Date:

6/10/2021 

Inspector:

Marc Harrison (E88884) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405

17901 COLLINS AVE , Sunny Isles Beach


44th floor North Tower Rough and Pressure approved for :
Units
Balcony sidewalls
Elevator lobby sidewalls in ceiling pockets
Trach chute
Electrical room in back of house

Pending (tentative)
1. Rough for Laundry room and electrical room for units.
2. Flexheads on balconies. Awaiting soffits.
3. Flexheads in elevator balconies.



Date:

5/26/2021 

Inspector:

John Molnar (MOLNAR) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
17901 COLLINS AVE , Sunny Isles Beach

43 floor Rough and Pressure approved. Fire caulking ok

Pending:

1. Flex heads on crane mount balcony, laundry room, elevator lobby and back of the house hallways.

2. Fire stop around exhaust vents to balconies for final.



Date:

5/14/2021 

Inspector:

Albert Carbonell  (ALCARBO) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
ACQUALINA NORTH TOWER
17901 COLLINS AVE

FIRE SPRINKLER ROUGH PARTIAL APPROVAL FOR NORTH TOWER EAST 6th FLOOR BALONIES ONLY

1) OKAY TO CLOSE HARD CEILING IN THESE AREAS ONLY

**PENDING**

2) PLAN REVISION REQUIRED FOR FINAL FOR ADDED, DELETED, RELOCATED, SPRINKLER
COVERAGE.

LT JOHNSON
LT CARBONELL
05\14\2021



Date:

5/13/2021 

Inspector:

John Molnar (MOLNAR) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
17901 COLLINS AVE , Sunny Isles Beach

1) Elevator lobbies floors 21thru25 rough pressure ok
Individual log book pages updated



Date:

5/5/2021 

Inspector:

Byron Kappes (E153438) 

Type:

206 - FIRE ROUGH

Status:

3 - REJECTED NOT TO CODE


2020056405

Acqualina north tower
17901 COLLINS AVE
Sunny Isles Beach

Sprinkler rough and pressure partial approval.

1. Sprinkler rough and pressure approved for the 41st floor north tower units and balconies only.

2. Pressure approved for back of house, electrical/laundry room and sauna.

3. Fire caulk approved.

4. Pending:

- sprinkler rough pending for back of house, electrical/laundry room, sauna.

Lt B. Kappes



Date:

4/26/2021 

Inspector:

John Molnar (MOLNAR) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
17901 COLLINS AVE , Sunny Isles Beach

1) 40th floor pressure ok
2) 40th rough partial approval trash chute ok fire caulking ok elevator lobby sidewall only ok
Balconies ok
Pending
3) Back of house is pending



Date:

4/20/2021 

Inspector:

John Molnar (MOLNAR) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
17901 COLLINS AVE , Sunny Isles Beach

1) Residence side only elevators lobby rough pressure ok floors 12 thru 20
Service elevator area pending



Date:

4/20/2021 

Inspector:

Nassoma Morgan (NMORGAN) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


Additional Comment:
These comments pertain specifically to West Balcony Unit 01 only.



Date:

4/20/2021 

Inspector:

Nassoma Morgan (NMORGAN) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
Estates of Aqualina
17901 Collins Ave

1. The purpose of the inspection was to determine if additional sprinkler coverage would be required on the balcony underneath the soffit that is over a door.

2. After consulting with the Sprinkler Plan Reviewer, additional coverage underneath that particular soffit over the door will not be required.

SRI Fees due.



Date:

4/20/2021 

Inspector:

Nassoma Morgan (NMORGAN) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL




Date:

4/16/2021 

Inspector:

Steven  Clements (E164643) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


#2020056405
ACQUALINA N.TOWER
17901 COLLINS AVE

1. ROUGH AND PRESSURE APPROVED FOR FLOORS 7-11 ELEVATOR LOBBIES EXCEPT AS NOTED AS PENDING.

2. VERIFIED NORMAL SYSTEM PRESSURE.

3. PENDING SPRINKLER INSTALLATION AT THE 10TH FLOOR SOUTH SIDE ELEVATOR LOBBY.

LT S.CLEMENTS



Date:

4/14/2021 

Inspector:

Tina Guiler (TINAG) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


PERMIT #2020056405
17901 COLLINS AVE , Sunny Isles Beach
Aqualina
4/14/2021

Fire Sprinkler Rough & Pressure Partial Approval 38th Floor

1- 38th floor - Spk Pressure okay. Fire Caulking Okay.

2- Spk Rough ok for 38th floor, areas pending below.

3- Trash chute okay.

Pending;

3- Both laundry rooms pending

4- back of house pending

5- Electrical room pending

6- Balconies on east side pending

7- elevator lobbies hangers okay, pending rough.


Lt. Guiler



Date:

4/13/2021 

Inspector:

Walter  Wray (WRAYWW) 

Type:

206 - FIRE ROUGH

Status:

3 - REJECTED NOT TO CODE


1. Sprinkler rough elevator Lobby North Tower floors 6 through 20 denied

2. Must have water in pipe with normal system pressure for any sprinkler inspection. NFPA 13: 25. 2. 1



Date:

4/5/2021 

Inspector:

John Molnar (MOLNAR) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
17901 COLLINS AVE , Sunny Isles Beach
1) 39 floor pressure approved
Rough partial approval pending below
1) Back,of house pending
2) East Balconies
3) Unit 3902 cooridor in unit and laundry room

From Lt.Kappas inspection done on 8/7/20
1) 6th floor back of house and laundry rooms rough approved
2) Balconies still pending

Above entries made in log book.



Date:

3/19/2021 

Inspector:

Albert Carbonell  (ALCARBO) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
ACQUALINA NORTH TOWER
17901 COLLINS AVE

FIRE SPRINKLER ROUGH PARTIAL APPROVAL FOR 02 UNITS FROM 30th -TO- 36th FLOOR PENDANTS ONLY.

1) INSPECTED FIRE CAULKING OKAY TO CLOSE HARD CEILING IN THESE AREAS ONLY

**PENDING**

2) ROUGH FOR LAUNDRY/ELECTRIC ROOM, BACK OF HOUSE, ALL BALCONYS, ELEVATOR LOBBY

3) PLAN REVISION REQUIRED FOR FINAL FOR ADDED, DELETED, RELOCATED, SPRINKLER COVERAGE.

LT CARBONELL
03\19\2021



Date:

3/17/2021 

Inspector:

Tina Guiler (TINAG) 

Type:

202 - FIRE PRESSURE TEST

Status:

4 - REJECTED PLAN & PERMIT MISSING


PERMIT #2020056405
17901 COLLINS AVE , Sunny Isles Beach
AQUALINA
3/17/2021

FIRE SPK ROUGH NOT APPROVED

1- PROVIDE APPROVED SET OF PLANS STAMPED BY FIRE FOR LOBBY INSPECTION.
NFPA 1:1.14


LT. GUILER



Date:

3/16/2021 

Inspector:

John Molnar (MOLNAR) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
17901 COLLINS AVE , Sunny Isles Beach

36 th floor
1) Pressure ok for floor
Pending
1) Back of house areas
2) Both elevator lobbies
3)Unit 3601 laundry room and both balconies
4) Unti 3602 laundry room east balcony and master bathroom
Remaining rough ok



Date:

3/15/2021 

Inspector:

John Molnar (MOLNAR) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


Additional comments for 3/15 inspection
1) Pending unit 3501 balcony area with jacuzzi west side



Date:

3/15/2021 

Inspector:

John Molnar (MOLNAR) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
17901 COLLINS AVE , Sunny Isles Beach

35th floor Rough pressure partial approval
Pending
1) Unit 3502 master bathroom and service room pending
2) Unit 3501 service room pending
3) Back of house
Remainder of floor ok.



Date:

3/12/2021 

Inspector:

Steven  Clements (E164643) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


#2020056405
ACQUALINA NORTH TOWER
17901 COLLINS AVE

**6TH FLOOR**

1. ROUGH APPROVED FOR PENDANTS IN 6TH FLOOR ELEVATOR LOBBY.
2. OKAY TO CLOSE SOFFITS.

LT S.CLEMENTS



Date:

3/1/2021 

Inspector:

Tina Guiler (TINAG) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


PERMIT #2020056405
17901 COLLINS AVE , Sunny Isles Beach
3/1/2021


FIRE SPRINKLER ROUGH & PRESSURE FOR 34TH FLOOR PARTIAL APPROVAL

1- 34TH FLOOR ONLY- FIRE SPK PRESSURE OKAY. FIRE CAULKING OKAY, TRASH CHUTE OKAY, ELECTRCIAL ROOM OKAY. ALL OTHER AREAS OKAY EXCEPT FOR PENDING BELOW.

PENDING ON 34TH FLOOR:

2- PENDANT SPK HEAD IN ELEVATOR LOBBIES PENDING.

3- BOTH LAUNDRY ROOMS PENDING.

4- BACK OF HOUSE PENDING.

5- ALL EAST BALCONIES PENDING.

6- SMALL CLOSET IN UNIT 2 PENDING.

7- BATHROOM IN UNIT 2 1- SPK HEAD PENDING CLOSER TO WINDOW.

8- ALL OTHER AREAS OKAY ON THIS FLOOR.


LT. GUILER



Date:

2/22/2021 

Inspector:

Tina Guiler (TINAG) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


PERMIT #2020056405
17901 COLLINS AVE , Sunny Isles Beach
2/22/2021

FIRE SPRINKLER R & P PARTIAL APPROVAL 33RD FLOOR


33RD FLOOR ONLY-

1- R & P OKAY FOR ENTIRE FLOOR PENDING THESE ITEMS BELOW, FIRE CAULKING OKAY PENDING 1 ROOM LISTED BELOW.


2- PENDING ON 33RD FLOOR-
- LAUNDRY ROOMS
- ELEVATOR LOBBY PENDANT ONLY (SIDEWALL OKAY FOR R & P)
- SMALL CLOSET IN UNIT 2 ONLY
- EAST SIDE BALCONIES
- WEST BALCONY- 1 SPK HEAD OUTSIDE DOOR TO SERVICE BEDROOM
- BACK OF HOUSE
- FIRE CAULKING PENDING IN ELECTRCIAL ROOM IN BACK OF HOUSE.


LT. GUILER



Date:

2/16/2021 

Inspector:

Tina Guiler (TINAG) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


PERMIT #2020056405
17901 COLLINS AVE , Sunny Isles Beach
2/16/2021


FIRE SPRINKLER ROUGH & PRESSURE PARTIAL APPROVAL 32ND FLOOR

1- SPK ROUGH PARTIAL APPROVAL FOR 32ND FLOOR.

2- PRESSURE OKAY.

3- TRASHE CHUTE OKAY.

4- ALL OF FLOOR 32 OKAY EXCEPT FOR BELOW.

PENDING ON 32ND FLOOR FOR ROUGH;

5- BOTH ELEVATOR LOBBIES PENDING THE PENDANT HEADS.

6- PENDING BOTH LAUNDRY ROOMS IN UNITS.

7- PENDING IN UNIT 2, SMALL CLOSET NEXT TO AC CLOSET.

8- EAST BALCONIES PENDING.

9- WEST BALCONIES OKAY EXCEPT EXTRA ROOM.

10- MARKED PENDING AREAS ON PLANS IN RED.


LT. GUILER



Date:

2/11/2021 

Inspector:

Troy  Maness (E138446) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
Acqualina North Tower
17901 Collins ave.

1. Fire sprinkler R&P partial approval.

2. Previous pending items corrected and inspected:

Floor 17 hanger
Floors 11,12,&14 two screws in balcony flex head brackets



Date:

2/9/2021 

Inspector:

Tina Guiler (TINAG) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


#2020056405
17901 COLLINS AVE , Sunny Isles Beach
NORTH TOWER
2/9/2021

FIRE SPRINKLER ROUGH PARTIAL APPROVAL WEST BALCONIES FLOOR 11-21

1- SPRINKLER ROUGH FOR WEST BALCONIES -FLOORS 21 THROUGH 11.

2- VERIFIED SPK MODEL HEADS SIDEWALL VK460 & PENDANT VK468. NEED TO REVISE PLANS TO REFLECT CORRECT SIDEWALL INSTALLED.

PENDING:

3- Floor 17, 14, 12, 11- ON WEST BALCONIES -SPK FLEX HEAD BRACKETS MISSING SCREWS ON ONE SIDE OF THE BRACKETS. ALL SCREWS MUST BE IN PLACE IN BRACKET AS PER PLANS & FOR ROUGH APPROVAL. NEED TO RECHECK ROUGH FOR THESE FLOORS.

4- REVISE PLANS TO REFLECT SPK HEAD VK 460 MODEL INSTALLED FOR SIDE WALLS ON BALCONIES.


LT. GUILER



Date:

2/8/2021 

Inspector:

Steven  Clements (E164643) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


#2020056405
ACQUALINA NORTH TOWER
17901 COLLINS AVE.

31ST FLOOR

1. ROUGH AND PRESSURE PARTIAL APPROVAL FOR UNITS 1 AND 2, BALCONIES, ELEVATOR LOBBY SIDEWALLS AND BACK OF HOUSE ELECTRICAL ROOM.

2. FIRE CAULK - OKAY

3. PENDING SPRINKLER BRACKET AND FLEX HEAD INSTALL FOR UNIT 2 CLOSET NEAR FRONT ENTRANCE AND WEST SIDE BEDROOM.

4. PENDING BACK OF HOUSE AND LAUNDRY ROOMS.

5. OKAY TO CLOSE ELEVATOR LOBBY SOFFITS WITH SIDEWALLS.

LT S.CLEMENTS



Date:

2/1/2021 

Inspector:

Steven  Clements (E164643) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


#2020056405
ACQUALINA NORTH TOWER
17901 COLLINS AVE.

**30TH FLOOR**

1. ROUGH AND PRESSURE PARTIAL APPROVAL FOR THE 30TH FLOOR UNITS 1 & 2 AND TRASH CHUTE ONLY.

2. FIRE CAULK - OKAY

3. PENDING BALCONIES, ELEC/LAUNDRY ROOMS, BACK OF HOUSE, ELEVATOR LOBBIES AND CLOSET IN UNIT 1.

LT S.CLEMENTS



Date:

1/28/2021 

Inspector:

John Molnar (MOLNAR) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
17901 COLLINS AVE , Sunny Isles Beach
South tower
1) Floors 6,7,8,9,10 For units #2 west balcony heads rough ok
2) Floors 6,7,8 For units #1 west balconies heads rough ok Floors 9&10 pending for balconies units #1



Date:

1/22/2021 

Inspector:

Albert Carbonell  (ALCARBO) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
ACQUALINA NORTH TOWER
17901 COLLINS AVE.

FIRE SPRINKLER ROUGH AND PRESSURE PARTIAL APPROVAL FOR 29th FLOOR UNITS 1 AND 2.

1) INSPECTED FIRE CAULKING OKAY TO CLOSE HARD CEILING IN THESE AREAS ONLY

**PENDING**

2) ROUGH FOR LAUNDRY/ELECTRIC ROOM, BACK OF HOUSE, ALL BALCONYS, ELEVATOR LOBBY

3) PLAN REVISION REQUIRED FOR FINAL FOR ADDED, DELETED, RELOCATED, SPRINKLER COVERAGE.

LT CARBONELL
01\22\2021



Date:

1/20/2021 

Inspector:

Jorge  Garcia (E33268) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405

17901 COLLINS AVE , Sunny Isles Beach
AQUALINA NORTH TOWER

FIRE SPRINKLER ROUGH PARTIAL APPROVAL

1) FIRE SPRINKLER ROUGH APPROVED FOR ELEVATOR LOBBIES FLOORS 18-24 OF THE NORTH TOWER FOR THE SIDEWALL HEADS ONLY.

2) FIRE CAULKING OKAY FOR THE SIDEWALL HEADS IN ELEVATOR LOBBIES 18-24 NORTH TOWER.

3) ROUGH FOR PENDANT FLEX HEADS IN ELEVATOR LOBBIES 18-24 NORTH TOWER ARE STILL PENDING.

LT. JORGE GARCIA
01.20.2021



Date:

1/15/2021 

Inspector:

Albert Carbonell  (ALCARBO) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
ACQUALINA NORTH TOWER
17901 COLLINS AVE.

FIRE SPRINKLER ROUGH AND PRESSURE PARTIAL APPROVAL FOR 28th FLOOR UNITS 1 AND 2, TRASH CHUTE, TRASH CHUTE VESTIBULE.

1) INSPECTED FIRE CAULKING OKAY TO CLOSE HARD CEILING IN THESE AREAS ONLY

2) SIDEWALL SPRINKLERS IN THE ELEVATOR LOBBY ARE APPROVED AND OKAY TO CLOSE.

**PENDING**

3) LAUNDRY/ELECTRIC ROOM, BACK OF HOUSE, ALL BALCONYS, PENDANT FOR ELEVATOR LOBBY

4) PLAN REVISION REQUIRED FOR FINAL FOR ADDED, DELETED, RELOCATED, SPRINKLER COVERAGE.

LT CARBONELL
01\15\2021



Date:

1/11/2021 

Inspector:

Jorge  Garcia (E33268) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405

17901 COLLINS AVE, Sunny Isles Beach
AQUALINA NORTH TOWER

FIRE SPRINKLER ROUGH PARTIAL APPROVAL FOR 27TH FLOOR.

1) FIRE SPRINKLER PRESSURE TEST WITNESSED AND IS OKAY.

2) FIRE SPRINKLER ROUGH FOR UNITS 1 AND 2 OF THE 27TH FLOOR OF THE NORTH TOWER IS OKAY. VERIFIED BRACKETS FOR FLEX HEADS WERE SECURED, FIRE CAULKING OKAY AND COVERAGE OKAY.

3) IT IS OKAY TO CLOSE OUT CEILINGS ON THE 27TH FLOOR NORTH TOWER, EXCEPT FOR THE AREAS LISTED BELOW IN THE PENDING SECTION.

PENDING:

4) BOTH LAUNDRY ROOMS, BACK OF HOUSE AND EAST BALCONIES ARE STILL PENDING ROUGH.

5) REVISE PLANS TO SHOW ANY AS BUILT CHANGES PER NFPA 1:1.14.5

LT. JORGE GARCIA
01.11.2021



Date:

1/5/2021 

Inspector:

John Molnar (MOLNAR) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
17901 COLLINS AVE , Sunny Isles Beach

1) 26th floor rough pressure approved for,units only.
Back of house common areas pending



Date:

12/23/2020 

Inspector:

Ricardo  Cruz (E32388) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


AQUALINA NORTH TOWER
17901 COLLINS

R&P PARTIAL APPROVAL 25TH FLOOR

1. PRESSURE APPROVED FOR ALL AREAS.

2.R&P APPROVED FOR 25TH FLOOR UNITS, CORRIDORS AND WEST BALCONY

3. FIRE CAULK OK

4. OK TO CLOSE HARD CEILINGS

PENDING ROUGH

2. BACK OF HOUSE, LAUNDRY ROOM, ELECTRICAL RM UNIT 1, ELEVATOR LOBBY PENDANTS.

PENDING R&P

3. EAST BALCONIES PENDING R&P

LT. CRUZ





Date:

12/18/2020 

Inspector:

Albert Carbonell  (ALCARBO) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
ACQUALINA
17901 COLLINS AVE.

FIRE SPRINKLER ROUGH AND PRESSURE PARTIAL APPROVAL FOR 24th FLOOR UNITS, WEST BALCONY, TRASH CHUTE

1) INSPECTED FIRE CAULKING OKAY TO CLOSE HARD CEILING IN THESE AREAS ONLY

2) SIDEWALL SPRINKLERS IN THE ELEVATOR LOBBY ARE APPROVED AND OKAY TO CLOSE.

**PENDING**

3) LAUNDRY/ELECTRIC ROOM, BACK OF HOUSE, AND EAST BALCONY, PENDANT ELEVATOR LOBBY, 2401 NORTHWEST ROOM

4) PLAN REVISION REQUIRED FOR FINAL FOR ADDED, DELETED, RELOCATED, SPRINKLER COVERAGE.

LT CARBONELL
12\18\2020



Date:

12/4/2020 

Inspector:

Steven  Clements (E164643) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


#2020056405
ACQUALINA
17901 COLLINS AVE.

23RD FLOOR

1. ROUGH AND PRESSURE IS APPROVED FOR THE 23RD FLOOR UNITS AND WEST BALCONY.

2. FIRE CAULKING IS APPROVED.

3. SIDEWALL SPRINKLERS IN THE ELEVATOR LOBBY ARE APPROVED AND OKAY TO CLOSE.

4. PENDING LAUNDRY/ELECTRIC ROOM, BACK OF HOUSE, TRASH CHUTE AND EAST BALCONY.

5. THE MISSING BRACKET AND SPRINKLER ON THE 22ND FLOOR AS NOTED ON 11/19/20 INSPECTION HAS BEEN CORRECTED AND APPROVED

LT S.CLEMENTS



Date:

12/4/2020 

Inspector:

Steven  Clements (E164643) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


#2020056405
ACQUALINA
17901 COLLINS AVE.

23RD FLOOR

1. ROUGH AND PRESSURE IS APPROVED FOR THE 23RD FLOOR UNITS AND WEST BALCONY.

2. FIRE CAULKING IS APPROVED.

3. SIDEWALL SPRINKLERS IN THE ELEVATOR LOBBY ARE APPROVED AND OKAY TO CLOSE.

4. PENDING LAUNDRY/ELECTRIC ROOM, BACK OF HOUSE, TRASH CHUTE AND EAST BALCONY.

5. THE MISSING BRACKET AND SPRINKLER ON THE 22ND FLOOR AS NOTED ON 11/19/20 INSPECTION HAS BEEN CORRECTED AND APPROVED

LT S.CLEMENTS



Date:

11/19/2020 

Inspector:

Steven  Clements (E164643) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


#2020056405
ACQUALINA NORTH TOWER
17901 COLLINS AVE.

22ND FLOOR

1. ROUGH AND PRESSURE PARTIAL APPROVAL FOR THE 22ND FLOOR UNITS ONLY.

2. PRESSURE TEST AND FIRE CAULK - OKAY

3. TRASH CHUTE - OKAY

4. INSTALL MISSING BRACKET AND FLEX HEAD AS NOTED ON PLANS PG. FP-2

5. PENDING BACK OF HOUSE, ELECTRICAL/LAUNDRY ROOM AND BALCONIES.

LT S.CLEMENTS



Date:

11/18/2020 

Inspector:

John Molnar (MOLNAR) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
17901 COLLINS AVE , Sunny Isles Beach

North Tower
1) 1 head pending in closet unit 2002 from inspection done on 11/3/20 is ok
2) 16th floor rough pressure partial approval firs caulking ok
Pending
Bedroom were Crain was located, laundry and electrical room as well as all balconies



Date:

11/16/2020 

Inspector:

John Molnar (MOLNAR) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
17901 COLLINS AVE , Sunny Isles Beach

21 floor rough pressure fire caulking ok for units only
Pending: back of house, balcony and electrical room



Date:

11/13/2020 

Inspector:

Walter  Wray (WRAYWW) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


1. Sprinkler rough and fire caulking partial approval for elevator lobby S/W heads floors 6 through 18 ( 01 and 02 units)

2. Unit 1001 fire caulking not completed



Date:

11/3/2020 

Inspector:

Byron Kappes (E153438) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405

Acqualina North Tower
17901 COLLINS AVE
Sunny Isles Beach

Sprinkler rough and pressure partial approval.

1. Sprinkler rough and pressure approved for 19th floor units only. Fire caulk okay. Trash chute rough and pressure okay

2. Pending:

- balcones, laundry/electrical room, elevator lobbies common areas.

- bedroom in unit 2001 at southwest side of bldg marked on plans is pending rough. However, pressure okay.

- small closet in unit 2002 at northeast side marked on plans pending rough for flex head, no ceiling grid installed. However, pressure okay.

Lt B. Kappes



Date:

10/30/2020 

Inspector:

Byron Kappes (E153438) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405

Acqualina North Tower
17901 COLLINS AVE
Sunny Isles Beach

Sprinkler rough and pressure partial approval.

1. Sprinkler rough and pressure approved for the 19th floor units only. Fire caulk okay. NW balcony for unit 1901 rough and pressure approved.

2. Pending for 19 floor:

- balconies, electrical/laundry room, elevator lobbies and common areas.

Lt B. Kappes




Date:

10/16/2020 

Inspector:

Ricardo  Cruz (E32388) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


Aqualina North Tower
17901 Collins Ave 5th floor
#2020056405

1. Sprinkler rough and pressure partial approval. 5th floor North tower temp
offices.

2. Fire caulking still pending.



Date:

10/14/2020 

Inspector:

Tina Guiler (TINAG) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


PERMIT #2020056405
17901 COLLINS AVE
10/14/2020

FIRE SPRINKLER ROUGH & PRESSURE FOR 18TH FLOOR PARTIAL APPROVAL

1- R & P PARTIAL APPROVAL FOR 18TH FLOOR.

2- PRESSURE OKAY.

3- FIRE CAULKING OKAY EXCEPT FOR UNIT #1801 BY PORCH INSIDE, PROVIDE FIRE CAULKING.

4- PENDING FOR 18TH FLOOR: LAUNDRY ROOM, ELEVATOR LOBBY, PORCH AREAS.

5- TRASH CHUTE ON 18TH FOOR OKAY.


LT. GUILER



Date:

10/13/2020 

Inspector:

Byron Kappes (E153438) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405

Acqualina North Tower
17901 COLLINS AVE
Sunny Isles Beach

Sprinkler rough and pressure partial approval.

1. Sprinkler rough and pressure approved for 17th floor only. Fire caulk okay. Electric room okay.

2. Pending for 17th floor

- laundry room, balconies and elevator lobby.

3. Sprinkler rough and pressure approved for small closet next to master bedroom on 15th floor unit 1501.

Lt B. Kappes



Date:

10/9/2020 

Inspector:

Byron Kappes (E153438) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405

Acqualina North tower
17901 COLLINS AVE
Sunny Isles Beach

Sprinkler rough and pressure partial approval.

1. Sprinkler rough and pressure approved for 5th floor north tower only. Fire caulk okay. Rough and pressure approved for trash room and trash chute.

2. Pending:

- all closets regardless of size shall have sprinkler coverage as this space is temporarily approved for offices used by the GC. This is now categorized as commercial and they are not exempt line residential. Provide coverage where marked on plans.

- relocate A/C duct or sprinkler head marked on plans.

- fire caulk pending for one head marked on plans.

Lt B. Kappes



Date:

10/2/2020 

Inspector:

Steven  Clements (E164643) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


#2020056405
ACQUALINA
17901 COLLINS AVE.

15TH FLOOR

1. SPRINKLER ROUGH AND PRESSURE APPROVED FOR THE 15TH FLOOR UNITS ONLY.

2. FIRE CAULKING - OKAY

3. PENDING COMMON AREAS, LAUNDRY ROOMS AND BALCONIES.

LT S.CLEMENTS
10/2/20



Date:

9/25/2020 

Inspector:

Steven  Clements (E164643) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


#2020056405
ACQUALINA NORTH TOWER
17901 COLLINS AVE.

14TH FLOOR

1. ROUGH AND PRESSURE APPROVED FOR 14TH FLOOR UNITS AND TRASH CHUTE ONLY.

2. FIRE CAULK - OKAY

3. PENDING COMMON AREAS AND BALCONIES.

4. PENDING SMALL CLOSET AT ENTRANCE TO UNIT 1401.


12TH FLOOR

1. SMALL CLOSET AT ENTRANCE TO UNIT 1201 IS APPROVED AS PER LT KAPPES 9/24 INSPECTION OF THE 12TH FLOOR.

LT S.CLEMENTS
9/25/2020



Date:

9/24/2020 

Inspector:

Byron Kappes (E153438) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405

Acqualina North Tower
17901 COLLINS AVE
Sunny Isles Beach

Sprinkler rough and pressure partial approval.

1. Sprinkler rough and pressure approved for 12th floor.

2. Pending:

- rough pending for balconies, laundry rooms, elevator lobbies, small closet at entrance to master suite in unit 1201.

Lt B. Kappes



Date:

9/18/2020 

Inspector:

Albert Carbonell  (ALCARBO) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
AQUALINA NORTH TOWER
17901 COLLINS AVE

FIRE SPRINKLER ROUGH AND PRESSURE PARTIAL APPROVAL FOR 10th FLOOR UNIT 1002

1) RE-INSPECT UNIT 1002 BALCONIES, ELEVATOR LOBBY, AND LAUNDRY ROOM ONCE BUILT

1) PLAN REVISION REQUIRED FOR FINAL FOR ANY ADDED, DELETED, RELOCATED SPRINKLER COVERAGE.

LT CARBONELL
09\18\2020



Date:

9/11/2020 

Inspector:

Byron Kappes (E153438) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405

Acqualina north Tower
17901 COLLINS AVE
Sunny Isles Beach

Sprinkler rough and pressure partial approval.

1. Sprinkler rough and pressure approved for 11th floor.

2. Pending for 11th floor:

- common areas, electrical rooms, laundry rooms, balconies, elevator lobby.

Lt B. Kappes



Date:

9/3/2020 

Inspector:

Carla  Crook (CCROOK) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


Aqualina North

9th floor, unit A, rough and pressure approved.
Trash chute r and p approved
Fire caulk approved
Balcony approved

Pending
Laundry room and common areas



Date:

9/2/2020 

Inspector:

Oscar Bouza (OBB) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


THIS INSPECTION WAS FOR 8TH FLOOR ON NORTH TOWER.



Date:

9/2/2020 

Inspector:

Oscar Bouza (OBB) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


17901 COLLINS AVE
ACQUALINA TOWERS

FIRE SPRINKLER R&P PARTIAL APPROVAL

1- R&P PARTIAL APPROVAL FOR UNIT 802 NORTH. N.W. BALCONY AND LAUNDRY ROOM PENDING PENDING CEILING GRIDS.

2- PRESSURE TEST FOR ENTIRE FLOOR APPROVED. ROUGH INSPECTION PENDING FOR UNIT 801 AND COMMON AREAS.

3- FOR INFORMATION PURPOSES ONLY, PENDENT HEADS ARE 200 DEGREE HEADS AS PER PLANS LEGEND AND VERIFIED INSTALLED.

4- SIDEWALL SPRINKLER HEADS INSTALLED AS WATER CURTAINS ARE TYPICAL SIDEWALLS. PROVIDE SPECIFICATION SHEETS TO ASCERTAIN THEY CAN BE USED FOR THIS APPLICATION.

LT. BOUZA




Date:

8/21/2020 

Inspector:

Jorge  Garcia (E33268) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405

17901 COLLINS AVE , Sunny Isles Beach
AQUALINA NORTH TOWER

FIRE SPRINKLER ROUGH AND PRESSURE PARTIAL APPROVAL

1) FIRE SPRINKLER ROUGH AND PRESSURE IS APPROVED FOR THE GROUND FLOOR BULKMAIN, HIGH AND LOW ZONES ONLY, AS HIGHLIGHTED IN GREEN ON THE PLANS ON PAGE FP-0.1

2) REVISE THE PLANS TO SHOW AS BUILT CHANGES TO THE LAYOUT OF THE BULK MAIN AS DRAWN IN RED ON PAGE FP-0.1

LT. JORGE GARCIA
08/21/2020



Date:

8/18/2020 

Inspector:

Albert Carbonell  (ALCARBO) 

Type:

210 - FIRE STANDPIPE

Status:

2 - APPROVED PARTIAL


2020056405
AQUALINA NORTH TOWER
17901 COLLINS AVE

FIRE SPRINKLER ROUGH AND PRESSURE PARTIAL APPROVAL FOR NORTH TOWER WEST STAIRWELL 25 FLOOR TO 1 (LOW ZONE) AND SPREAD , OKAY.

1) PLAN REVISION REQUIRED FOR FINAL FOR ANY ADDED, DELETED, RELOCATED SPRINKLER COVERAGE.

LT CARBONELL
08\18\2020



Date:

8/17/2020 

Inspector:

Tina Guiler (TINAG) 

Type:

210 - FIRE STANDPIPE

Status:

2 - APPROVED PARTIAL


PERMIT# 2020056405
17901 COLLINS AVE , Sunny Isles Beach
AQUALINA
8/17/2020


FIRE SPK STANDPIPE PARTIAL APPROVAL

1- FIRE SPK STANDPIPE R & P OKAY FOR 25TH FLOOR TO 1ST FLOOR EAST STANDPIPE STAIRWELL.

2- WEST STAIRWELL 25TH FLOOR ONLY TRANSITION PIPES ONLY (2), PRESSURE OKAY. STANDPIPE PRESSURE REMAINS PENDING ON 25TH FLOOR.



LT. GUILER



Date:

8/14/2020 

Inspector:

Jorge  Garcia (E33268) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405

17901 COLLINS AVE, Sunny Isles Beach
AQUALINA NORTH TOWER
7TH FLOOR

FIRE SPRINKER ROUGH PARTIAL APPROVAL.

1) ALL PENDING ITEMS FROM LT. MOLNAR S INSPECTION FROM YESTERDAY 08/13/2020 ARE STILL PENDING:

2) IT IS OKAY TO CLOSE UP THE CEILINGS IN ALL AREAS EXCEPT THE FOLLOWING PENDING AREAS:

7TH FLOOR AREAS PENDING ROUGH INSPECTION:

3) ROUGH INSPECTION STILL NEEDS TO BE DONE FOR ALL THE COMMON AREAS: BALCONIES, ELEVATOR LOBBIES, ELECTRICAL ROOM AND LAUNDRY ROOM.

LT. JORGE GARCIA
08/14/2020



Date:

8/13/2020 

Inspector:

John Molnar (MOLNAR) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405
17901 COLLINS AVE , Sunny Isles Beach

1) pressure ok for 7th floor
2) Rough partial approval for 7th floor several heads still not installed in brackets do not close ceilings until unit rough is approved for 7 floor



Date:

8/7/2020 

Inspector:

Byron Kappes (E153438) 

Type:

206 - FIRE ROUGH

Status:

2 - APPROVED PARTIAL


2020056405

Acqualina North Tower
17901 COLLINS AVE
Sunny Isles Beach

Sprinkler rough and pressure partial approval.

1. Sprinkler rough and pressure approved for 6th floor units only. Pressure approved for common area.

2. Pending:

- rough pending for common areas.

- rough and pressure pending for balconies and laundry rooms.

Lt B. Kappes