Inspection Result Comments

Sunday, October 11, 2026

Permit Number:  2021033830


Date:

10/22/2021 

Inspector:

Troy  Maness (E138446) 

Type:

209 - FIRE FINAL

Status:

1 - APPROVED


2021033830
373 NE 167 ST , North Miami Beach

1. Fire final approved. All previous pending items completed and inspected.



Date:

10/18/2021 

Inspector:

Tina Guiler (TINAG) 

Type:

209 - FIRE FINAL

Status:

2 - APPROVED PARTIAL


Permit #2021033830
373 NE 167 ST , North Miami Beach
10/18/2021

Fire Final Not Approved

1- Remove slide lock on back door. Lock on door cannot require any special knowledge. NFPA 101:7.2.1.5.3.

2- Provide exit sign for rear door above door marked on plans.

3- Provide covers for all electrical/light switches.

4- Unable to test em lights, not marked on panel and patients in therapy. Label em lights on electrical panel. Need to test em lights.

5- Provide signage for electrical panel that states, "No Storage within 3 of electrical panel". Remove any equipment stored in front of panel.

6- Close off new area to customers & employees until approved by fire. No stocking in this area until a CO or TCO is approved.

7- Provide a "full" fire extinguisher. almost empty.

8- Provide door bar on exit door in front of new area.


Lt. Guiler