Inspection Result Comments

Monday, October 19, 2026

Permit Number:  2022012085


Date:

4/13/2023 

Inspector:

Ryan Townsend (RYANT) 

Type:

209 - FIRE FINAL

Status:

1 - APPROVED


2022012085
19555 BISCAYNE BLVD
Bloomingdales

All fees have been paid; this permit is not approved.

Lt Townsend
4/13/23



Date:

4/11/2023 

Inspector:

Dianne Gary (DGARY) 

Type:

209 - FIRE FINAL

Status:

2 - APPROVED PARTIAL


Permit number: 2022012085/ M2022002158. Aventura BCOM-211-003

Bloomingdales
19555 Biscayne Boulevard
Aventura, FL.

NFPA 1:1.14.4 Review and approval by the AHJ shall not relieve the applicant of the responsibility of compliance with this code.

1. Fire final partially approved.

Approval is contingent upon the payment of $210.00 fee for violation number B257407

Sprinkler and fire alarm are approved.



Date:

4/7/2023 

Inspector:

Sheran Johnson (SAJOHNS) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


Permit: 2022012085
Name: BLOOMINGDALES PHASE 4
Address: 19555 BISCAYNES BLVD

Citation was issued on 4/7/2023 at 10:30 am. Citation # B257407. Section 14-39 Failure to obtain required permit or violation of condition of permit, or failure to obtain required fire department approval to use or occupancy. REF NO. 4401. CODE 14-39.

OCCUPYING WITHOUT A TCO/CO SINCE April 6, 2023.

Please DO NOT CLOSE THIS PERMIT OUT.

LT. S. Johnson 4-7-2023



Date:

3/16/2023 

Inspector:

Sheran Johnson (SAJOHNS) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


Citation*** B257362 VOIDED****

Lt. JOhnson



Date:

3/6/2023 

Inspector:

Sheran Johnson (SAJOHNS) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


Permit: 2022012085
Name: BLOOMINGDALES PHASE 4
Address: 19555 BISCAYNES BLVD

Citation was issued on 3/6/2023 at 3:30 Pm. Citation # B257362. Section 14-39 Failure to obtain required permit or violation of condition of permit, or failure to obtain required fire department approval to use or occupancy. REF NO. 4401. CODE 14-39.

OCCUPYING WITHOUT A TCO/CO SINCE FEBRUARY 28, 2023.

Please DO NOT CLOSE THIS PERMIT OUT.

LT. S. Johnson 3-6-2023



Date:

3/3/2023 

Inspector:

Dianne Gary (DGARY) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


Permit number: 2022012085/ M2022002158. Aventura BCOM-211-003

Bloomingdale?s
19555 Biscayne Boulevard
Aventura, FL.

NFPA 1:1.14.4 Review and approval by the AHJ shall not relieve the applicant of the responsibility of compliance with this code.

1. Fire TCO extension recommended for 30 days for phases one, 2A, 2B, 3A, 3B, and 4.

The reason for the TCO extension is so that the client can continue to use the space whilst is the items below are addressed.

2. The fire sprinkler permit 2022035767 is pending revisions, and the fire alarm permit 2023007404 is pending testing.

3. Ensure that all escutcheon plates are intact and install throughout the phases.

All other life safety parameters have been met.



Date:

2/23/2023 

Inspector:

Sheran Johnson (SAJOHNS) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


On February 23, 2023, I spoke with customer/GC Mr. Yohan Gonzales 786-603-8531 was advising that her current Temporary Certificate of Occupancy will expire on February 28, 2023.

In order to remain in compliance, he must schedule a Temporary Certificate of Occupancy Extension or Fire Final for his Certificate of Occupancy.

The TCO must be fully process and paid for, also the paperwork must be sign by the New Construction Bureau Office-in-Charge, before February 28, 2023, or a Notice of Violation (NOV) will be issued.

Lt. Johnson 2/23/2023



Date:

12/13/2022 

Inspector:

Byron Kappes (E153438) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


2022012085

Bloomingdales phase IV
19555 Biscayne Boulevard
Aventura, FL

Fire TCO recommended for 90 days for phase 4 with Captains approval. Reason for TCO project being done in phases.

1. Verify fire alarm plans and permit approved prior to CO.

Lt B. Kappes



Date:

12/13/2022 

Inspector:

Dianne Gary (DGARY) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


Permit number: 2022012085

NFPA 1:1.14.4 Review and approval by the AHJ shall not relieve the applicant of the responsibility of compliance with this code.

Bloomingdales phase IV
19555 Biscayne Boulevard
Aventura, FL.

1. Fire TCO not approved.

2. Complete all construction for the TCO and remove all construction debris.



Date:

10/17/2022 

Inspector:

Dianne Gary (DGARY) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


Permit number: 2022012085/ M20220018801

Bloomingdales
19555 Biscayne Boulevard
Aventura, FL.

NFPA 1:1.14.4 Review and approval by the AHJ shall not relieve the applicant of the responsibility of compliance with this code.

1. Fire TCO recommended for 90 days for phase 3A.

The reason for the TCO is so that Phase 3A can be occupied whilst all other phases under construction are approved.

sprinkler 2022035767

fire alarm permit not available



Date:

10/14/2022 

Inspector:

Byron Kappes (E153438) 

Type:

208 - FIRE TCO INSPECTION

Status:

7 - NOT READY FOR INSPECTION


2022012085

19555 BISCAYNE BLVD
Aventura

Fire TCO not approved.

1. Spoke with GC who stated they were not ready for inspection and will reschedule.

Lt B. Kappes



Date:

10/5/2022 

Inspector:

John Molnar (MOLNAR) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


2022012085
19555 BISCAYNE BLVD , Aventura


Bloomingdale s Phase 3

A 90 day TCO is recommended with Captains approval.
Please bring the Dade county TCO form along with any municipality form and/or hardship letter, if required, to the Fire Prevention desk at 11805 SW 26TH ST. Please call 786.315.2771 to schedule a TCO appointment.

Full life safety was done for phase 3 and ok
Sprk final approved for this area.



Date:

10/4/2022 

Inspector:

John Molnar (MOLNAR) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


2022012085
19555 BISCAYNE BLVD , Aventura

Inspection was for phase 3

A full life safety inspection was done following is pending

1) provide proof of Sprk final in these areas and install all missing euscheon plates

Previous TCO areas are unaffected



Date:

8/4/2022 

Inspector:

Marc Harrison (E88884) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


2022012085

19555 BISCAYNE BLVD , Aventura

Bloomingdale s Phase 2b Rear stock room.

A 90 day TCO is recommended with Captain?s approval. Please bring the Dade county TCO form along with any municipality form and/or hardship letter, if required, to the Fire Prevention desk at 11805 SW 26TH ST. Please call 786.315.2771 to schedule a TCO appointment.

On 8/1/22 Lt. Arrojo gave a TCO for phase 2B, but the rear stock room was not included. This inspection adds the rear stock room and completes phase 2B.

Fire alarm plans submittal and approval is pending.

Lt. Harrison



Date:

8/1/2022 

Inspector:

John Arrojo (ARROJOJ) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


19555 BISCAYNE BLVD
BLOMINGDALES
PHASE 2B FLOOR SPACE AREA AS NOTED ON PHASING PLAN AND STOCK ROOM FIRST FLOOR

++DO NOT CLOSE THIS PERMIT WITHOUT FIRE ALARM BEING CLOSED+++

TCO FOR 90 DAYS RECOMMENDED PENDING THE CAPTAINS SIGNATURE

REASON FOR TCO IS COMPLETION OF SCOPE OF WORK AND FINAL APPROVAL OF F/A

PROVIDE A NOTARIZED LETTER FROM ENGINEER OF RECORD SPECIFYING TESTING OF EM LIGHTING IN AREAS WHERE A GENERATOR IS PROVIDED TO SUPPORT EM SYTEMS.

ALL OTHER LIFESAFETY ITEMS VERIFIED AND OK.



Date:

7/7/2022 

Inspector:

Tina Guiler (TINAG) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


2022012085
19555 BISCAYNE BLVD
BLOMINGDALES
PHASE 2A WOMENS SHOES & WOMENS STOCK ROOM FIRST FLOOR

++DO NOT CLOSE THIS PERMIT WITHOUT FIRE ALARM BEING CLOSED+++

1- TCO FOR 90 DAYS RECOMMENDED PENDING THE CAPTAINS SIGNATURE FOR BLOOMINGDALES FIRST FLOOR WOMENS SHOES SALES AREA & WOMENS STOCK ROOM ONLY.
THE TCO IS NOT VALID WITHOUT THE CAPTAINS SIGNATURE
NEED TO SCHEDULE AN APPOINTMENT WITH THE OFFICE FOR TCO


2- THE SPRINKLER FINAL WAS APPROVED FOR PHASE 2A 2022035767, REASON FOR TCO, CONSTRUTCTION STILL PENING IN OPTHER AREAS, F/A PERMOT & PLANS NEED TO BE PULLED FOR FUTURE WORK BEING ONE.

3- EM LIGHTS OKAY, FE, CURRENT F/A DEVICES TESTED & OKAY FOR THE WOMENS STOCK ROOM. FOR THIS TCO.

4- PENDING- PLANS AND PERMIT FOR FIRE ALARM AND TESTING OF RELOCATED DEVICES IN STOCK ROOM WHEN WORK IS COMPLETE.

SRI FEES APPLY

LT. GUILER



Date:

6/29/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


PERMIT 2022012085
19555 BISCAYNE BLVD , Aventura
BLOOMINGDALES
PHASE 2A WOMENS SHOES STOCK ROOM

***NOTE THIS PERMIT SHALL NOT BE CLOSED PRIOR TO FIRE ALARM BEING APPROVED***

1. PER THE OFFICE, THE INSPECTION WAS CANCELED

2. PER YOHAN 4 FIRE ALARM DEVICES WERE NOT WORKING

3. INSPECTION WAS TO CHECK FIRE ALARM DEVICES FOR FUNCTIONALITY AND TCO FOR STOCK ROOM.
NEED TO PULL PLANS AND PERMIT AND HAVE PLANS APPROVED FOR RELOCATION OF DEVICES AND ALL OTHER FIRE ALARM WORK THAT EITHER HAS BEEN DONE, OR WILL BE DONE IN THE FUTURE.
THIS PERMIT SHALL NOT BE CLOSED PRIOR TO APPROVAL OF FIRE ALARM PERMIT ONCE PULLED.
THERE WILL BE A LIMITED TIME PERIOD TO PULL PLANS AND PERMIT FOR FIRE ALARM.
IF APPROVAL OF PLANS TAKES AN EXTENDED PERIOD OF TIME, AT MNIMUM PROVIDE PROCESS NUMBER FOR SUBMISSION OF PLANS

4. RE INSPECTION FEES APPLY





Date:

6/24/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


UNABLE TO ENTER UNDER 208 TCO

PERMIT 2022035767
PROCESS M2022002158
AVENTURA BCOM2111-0003
19555 BISCAYNE BLVD
BLOMINGDALES
PHASE 2A WOMENS SHOES FIRST FLOOR
SALES AREA AND STOCK ROOM

1. A LIFE SAFETY INSPECTION HAS BEEN COMPLETED. RECOMMENDING TCO PENDING THE CAPTAINS SIGNATURE FOR BLOOMINGDALES FIRST FLOOR WOMENS SHOES SALES AREA ONLY
THE TCO IS NOT VALID WITHOUT THE CAPTAINS SIGNATURE
NEED TO SCHEDULE AN APPOINTMENT WITH THE OFFICE FOR TCO

2. THE STOCK AREA IS NOT PART OF THIS TCO RECOMMENDATION

3. THE SPRINKLER FINAL WAS APPROVED FOR PHASE 2A 2022035767

4. ALL PREVIOUS PENDING ITEMS FROM PREVIOUS LIST DATED 6/23 HAVE BEEN COMPLETED FOR THIS PHASE EXCEPT
- PLANS AND PERMIT FOR FIRE ALARM AND TESTING OF RELOCATED DEVICES IN STOCK ROOM

-THERE ARE NO RELOCATED DEVICES ON THE SALES FLOOR AREA

5. PENDING ITEM #12 FROM LIST DATED 6/23 FOR SPRINKLER COVERAGE GREATER THAN 4 FT SHALL BE COMPLETED. THIS AREA IS IN PHASE 1 WHICH HAS ALREADY BEEN TCO

6. PRIOR TO THE COMPLETION OF ALL SPRINKLER WORK, THERE ARE EXISTING HEADS THAT ARE NOT IN THE SPRINKLER SCOPE OF WORK THAT ARE IN THE SAME COMPARTMENT, BUY HAVE A DIFFERENT RESPONSE. THESE HEADS WILL HAVE TO BE CHANGED TO STANDARD RESPONSE WHICH MATCHES THE ENTIRE AREA. THERE ARE APPROX 9 HEADS.

7. SRI FEES APPLY



Date:

6/23/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

209 - FIRE FINAL

Status:

3 - REJECTED NOT TO CODE


**SYSTEM WOULD NOT ALLOW TO DISPOSITION UNDER 208**

PERMIT 2022012085
PROCESS M2022002158
AVENTURA BCOM2111-0003
19555 BISCAYNE BLVD
BLOOMINGDALES
PHASE 2A WOMENS SHOES FIRST FLOOR ONLY

1. TCO NOT APPROVED

2. SPRINKLER FINAL FOR 2A WAS APPROVED PERMIT 2022035767

3. NEED TO PULL PLANS AND PERMIT FOR FIRE ALARM AND HAVE PLANS APPROVED AND SCHEDULE FIRE ALARM INSPECTION FOR FIRE ALARM WORK DONE

4. THE EXISTING FIRE ALARM DEVICES HAVE BEEN RELOCATED WITHOUT PLANS AND PERMIT
2 DEVICES ARE CURRENTLY NOT INSTALLED PER NFPA 72
ONE DEVICE IS A WALL MOUNTED DEVICE MOUNTED ON THE CEILING
ONE WALL MOUNTED DEVICE HAS BEEN INSTALLED GREATER THAN 96"
ONCE PLANS AND PERMIT HAVE BEEN PULLED AND APPROVED, THESE DEVICES SHALL BE CORRECTED

5. BEING THAT THESE EXISTING DEVICES HAVE ALREADY BEEN RELOCATED, NEED TO TEST FOR FUNCTIONALITY. HAVE THE FIRE ALARM COMPANY ON SITE AND COORDINATE WITH THE MALL FOR TESTING

6. NEED TO LOCATE BREAKERS FOR EM LIGHTS AND TEST

7. NEED TO RELOCATE 2 EXIT SIGNS, ADD 2 ADDITIONAL EXIT SIGNS AND REMOVE THE EXIT SIGN THAT LEADS TO PHASE 2B WHICH IS THE NEXT PHASE TO BE DONE. ONCE PHASE 2B HAS BEEN COMPLETED, THE EXIT SIGN SHALL BE RE INSTALLED PER PLANS.

8. NEED TO MOUNT FIRE EXTINGUISHER. EXTINGUISHER SHALL BE MOUNTED NO HIGHER THAN 5 FT TO THE TOP OF THE HANDLE NFPA 10

9. NEED TO COMPLETE THE FLOOR TRANSITION AT ENTRANCE TO THE STOCK ROOM
NFPA 101:7

10. NEED TO REMOVE ALL BOXES, AND INSTALL ALL SHELVING

11. REMOVE ALL CONSTRUCTION DEBRIS AND TOOLS AND CART FROM PHASE 2A AREA.
PROVIDE BARRIER SEPARATING CONSTRUCTION MATERIAL FOR PHASE 2B FROM PHASE 2A

12. THERE IS ONE AREA IN QUESTION FOR DUCT WORK BEING GREATER THAN 4 FT. PROVIDE LADDER SO THE DUCT WORK CAN BE MEASURED. IF 4FT OR GREATER, NEED TO PROVIDE SPRINKLER COVERAGE UNDERNEATH NFPA 13

13. SRI FEES APPLY



Date:

6/23/2022 

Inspector:

John Molnar (MOLNAR) 

Type:

208 - FIRE TCO INSPECTION

Status:

7 - NOT READY FOR INSPECTION


2022012085
19555 BISCAYNE BLVD

Unable to conduct a proper life safety inspection in this area
To much construction equipment and construction still not completed



Date:

6/8/2022 

Inspector:

Marc Harrison (E88884) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


2022012085

19555 BISCAYNE BLVD , Aventura

Bloomingdale s

1- TCO recommended for 30 days for Phase 2A (sunglasses area), & Phase 1 ONLY, pending captains approval.

2- Construction being done in phases and plans review is in for fire alarm.

3- SPK- #2022035767- partial approval
Fire alarm- ??

3- All life safety okay for these phases.

Lt. Harrison



Date:

6/2/2022 

Inspector:

Sheran Johnson (SAJOHNS) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


On June 2, 2022, customer Mr. Scott Wright 352-229-7319 was advise that his client current Temporary Certificate of Occupancy will expired on June 9, 2022. (TCO for Phase 1 Cosmetic + Storage room, Phase 2 Sunglass Hut only)

In order to remain in compliance, he must schedule a Temporary Certificate of Occupancy Extension or Fire Final for his Certificate of Occupancy.

The TCO must be fully process and paid for, also the paperwork must be sign by the New Construction Bureau Office-in-Charge, before June 9, 2022 or a Notice of Violation (NOV) will be issued.

Lt. Johnson 6/2/2022



Date:

5/10/2022 

Inspector:

Tumaini Jabali (JABALIT) 

Type:

219 - FIRE - INSPECTION COMMENT

Status:

90 - FIRE - COMMENTS ONLY


Comments only
TCO recommended by Lt. Guiler and Lt. Molnar for

Phase 1 cosmetic area and storage room only.
Per Lt. Molnar fire alarm is for storage room only and plans and permit are being submitted for that room.

Phase 2A for sunglass hut only Per Lt. Molnar no fire alarm work is being done in that area



Date:

5/5/2022 

Inspector:

Tina Guiler (TINAG) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


2022012085
Bloomingdales
19555 BISCAYNE BLVD , Aventura
5/5/2022

1- TCO recommended for 30 days for Phase 2A (sunglasses area), & Phase 1 ONLY, pending captains approval.

2- Construction being done in phases, contractor needs to call for fire alarm inspection for any further tco extensions.

3- SPK- #2022035767- partial approval
Fire alarm- ??

3- All life safety okay for these phases.

4- Contact Yohan Gonzalez 786-603-8531, or GC rep- Scott Wright 352-229-7319.

5- Call for TCO appt. 786-315-2771


Lt. Guiler



Date:

5/4/2022 

Inspector:

John Molnar (MOLNAR) 

Type:

208 - FIRE TCO INSPECTION

Status:

47 - APPROVED FOR TEMPORARY ONLY


2022012085
19555 BISCAYNE BLVD , Aventura

This inspection. Was for the cosmetic stock room which is part of phase 1.

This room can be added to the phase 1 TCO recommendation.

This completes all phase 1



Date:

4/27/2022 

Inspector:

John Molnar (MOLNAR) 

Type:

208 - FIRE TCO INSPECTION

Status:

2 - APPROVED PARTIAL


2022012085
19555 BISCAYNE BLVD , Aventura

30 day TCO recommended for phase 1 as follows

This TCO covers Phase 1 retail and shoe stock room only.
Life safety inspection was completed for these areas are ok
SPRK for these areas are ok permit # 2022035767
No Fire Alarm work was done in the above areas.

Pending
Cosmetic stock room is part of phase 1 but not approved at this time.
Reason is the walls do not go to the ceiling, it ends approximately 4? from the roof deck thus creating a plenum.
Either bring the wall up to the roof or comply with NFPA13:8.15.23
Also the FA is still pending in this area.



Date:

4/25/2022 

Inspector:

John Molnar (MOLNAR) 

Type:

208 - FIRE TCO INSPECTION

Status:

3 - REJECTED NOT TO CODE


2022012085
19555 BISCAYNE BLVD , Aventura

This is a 5 phase remodel in Bloomingdale?s with FA and Sprk work
GC wants a TCO phase 1

1) A full life safety inspection for phase 1 has been done following pending
2) Complete the FA work and have it inspected
3) Get Sprk final for phase 1 GC states Sprk final was done on Friday 4/22 as a SRI no notes entered at this time
All other life safety items for phase 1 is done and ok

FA permit # pending
Sprk permit # 2022035767 final for phase 1



Date:

4/20/2022 

Inspector:

Marc Harrison (E88884) 

Type:

208 - FIRE TCO INSPECTION

Status:

4 - REJECTED PLAN & PERMIT MISSING


2022012085
19555 BISCAYNE BLVD , Aventura
Bloomingdales
TCO rejected for Phase 1.
1. Install EM lighting for storage room as per plans E-130
2. Install all fixtures in Phase 1 area as per plans A-100. Fixture will prevent cold soldering of head in main area.
3. Submit alarm plans and have reviewed by MDFR for devices removed and for coverage requirements as per note on plan FA-100. Inspection of system required.
$. Have plans and Dade county permit on site. NFPA 1:1.14.1
Sprinkler permit partial approval #2022035767
Lt. Harrison